4-6 PROTECTIVE FUNCTION
04-10
4-6-1 Protective Function List
Protective Function
< Cooling mode >
Detect Parts
Operating Condition
Operation
Discharge Temp
Protection 1
Discharge Temp
Thermistor
The signal that opens the EEV
is sent to the indoor unit
DISTH: Actual discharge Temp
DISTR: Target discharge Temp
THII: Suction Temp
TSLP: Low pressure power saturation
Start: After 3 min startup, keep DISTH 100 or when the accumulated
time of operation at over 10degC of Suction SH (Suction
temperature - TSLP) continues over 30 minutes.
>=
Release: DISTH 95 and TH11 - TSLP 5
<=
<=
Discharge Temp
Protection 2
Discharge Temp
Thermistor
EEV2 increases 30Pulse/30sec.
Start: DISTH 107
>=
Release: DISTH 100
<=
Discharge Temp
Protection Stop
Discharge Temp
Thermistor
Release: 3 minutes have passed, and DISTH 80
<=
The compressor stops.
(more than 3 minutes)
Start: DISTH 120
>=
Start:
The operation repeats 3 times within 40 minutes.
Release: Reset the outdoor unit.
The compressor stops.
(Permanent stop)
Error indication : refer to 06-20 26
High Pressure
Protection
High Pressure
Sensor
Release: 2 minutes have passed, HPS<3.5MPa and
release of the of the High Pressure Protection Stop.
Start: HPS 3.74MPa
>=
SV1 opens
High Pressure
Protection Stop
High Pressure
Sensor
Start: HPS 4.1MPa
>=
Release: 3 minutes have passed, and HPS<3.5MPa.
All the compressors of the
outdoor unit stop.
(more than 3 minutes)
HPS:High Pressure Sensor value
Start: The operation repeats 3 times in an hour.
Release: 10 minutes have passed, and HPS<3.5MPa.
All the compressors of the
outdoor unit stop.
(more than 10 minutes)
HPS : High pressure sensor value
Error indication : refer to 06-26
(Stop : LPS 0.1Mpa 2min at TEST RUN)
Start: The operation repeats 5 times in 3 hours.
Release: Reset the outdoor unit.
Low Pressure
Protection
Low Pressure
Sensor
Start: LPS 0.65MPa and INV 30Hz
<=
<=
<=
Release: 5 minutes have passed, INV 50Hz and release of the
of the Low Pressure Protection Stop.
>=
SV1 opens
LPS: Low Pressure Sensor value
INV: Operation frequency of the
DC scroll compressor
Low Pressure
Protection Stop
Low Pressure
Sensor
Release: 3 minutes have passed, and LPS 0.2MPa.
>=
Start: LPS 0.1MPa and 10 minutes have passed.
<=
All the compressors of the
outdoor unit stop.
(more than 3 minutes)
All the compressors of the
outdoor unit stop.
permanent stop
Error indication : refer to 06-27
Abnormal high
pressure protection
control
High pressure
saturation temperature
(calculated from
discharge pressure
sensor value)
- If the high pressure saturation temperature becomes higher than 60.5degC for 25 seconds, the capacity increase
of the compressor is prohibited.
- If the high pressure saturation temperature further keeps the condition higher than 62degC for 25 seconds, the
compressor capacity is reduced.
- It is released when the high pressure saturation temperature becomes lower than 59.5degC and continues for 25
seconds.
Содержание AB*A12
Страница 6: ...1 TEST RUN ...
Страница 13: ...2 FUNCTION OF PRINTED CIRCUIT BOARD ...
Страница 58: ...3 INVERTER CONTROL ...
Страница 62: ...4 OUTDOOR UNIT OPERATION CONTROL ...
Страница 74: ...5 INDOOR UNIT OPERATION ...
Страница 90: ...6 TROUBLE SHOOTING ...
Страница 199: ...7 APPENDING DATA UNIT ...
Страница 207: ...7 3 WIRING DIAGRAM 07 08 7 3 1 Indoor Unit COMPACT CASSETTE TYPE MODELS AUXB07 AUXB09 AUXB12 AUXB14 AUXB18 ...
Страница 208: ...07 09 MODELS AU A20 AU A25 AU A30 ...
Страница 209: ...07 10 MODELS AU A36 AU A45 AU A54 ...
Страница 210: ...07 11 COMPACT DUCT TYPE MODELS ARXB07 ARXB09 ARXB12 ARXB14 ARXB18 ...
Страница 211: ...07 12 MODEL ARXB25 MODELS ARXB30 ARXB36 ARXB45 LOW STATIC PRESSURE DUCT TYPE ...
Страница 212: ...07 13 MODELS ARXA30 ARXA36 ARXA45 MODEL ARXA25 DUCT TYPE ...
Страница 213: ...07 14 MODELS ARXC36 ARXC45 ARXC60 HIGH STATIC PRESSURE DUCT TYPE ...
Страница 214: ...07 15 MODEL ARXC90 ...
Страница 215: ...07 16 FLOOR CEILING TYPE MODELS AB A12 AB A14 AB A18 AB A24 ...
Страница 216: ...07 17 CEILING TYPE MODELS AB A30 AB A36 AB A45 AB A54 ...
Страница 217: ...07 18 COMPACT WALL MOUNTED TYPE Comfort model MODELS AS E07 AS E09 AS E12 AS E14 ...
Страница 218: ...07 19 WALL MOUNTED TYPE MODELS AS A18 AS A24 AS A30 ...
Страница 219: ...07 20 CEILING WALL TYPE MODELS AW A07 AW A09 AW A12 AW A14 AW A18 AW A24 AW A30 ...
Страница 220: ...07 21 7 3 2 Outdoor Unit MODELS AJ A72LBTF AJ A90LBTF ...
Страница 221: ...07 22 MODEL AJ 126LBTF ...
Страница 222: ...07 23 MODELS AJ A72UBTF AJ A90UBTF ...
Страница 223: ...07 24 MODEL AJ 126UBTF ...
Страница 230: ...8 DISASSEMBLY ILLUSTRATION PARTS LIST ...
Страница 232: ...Model AJ 126LBTF 104 111 100 101 107 112 103 105 102 110 106 08 02 ...
Страница 233: ...Model AJ 126LBTF 151 150 155 156 154 152 161 158 157 160 159 153 08 03 ...
Страница 238: ...Model AJ 126UBTF 100 101 107 105 102 110 106 08 08 104 111 112 ...
Страница 243: ...Model AJ A90LBTF 104 111 100 101 107 112 103 105 102 110 106 AJ A72LBTF 08 13 ...
Страница 244: ...151 150 155 156 154 152 161 158 157 160 159 153 08 14 Model AJ A90LBTF AJ A72LBTF ...
Страница 249: ...Model AJ A90UBTF 100 101 107 105 102 110 106 AJ A72UBTF 08 19 104 111 112 ...
Страница 287: ......
Страница 289: ......