Requirements of the Rack
When installing rack systems of several other manufacturers, the following
applies:
3rd-Party Rack
Some general conditions must observed:
–
Installation dimensions (see the dimensions shown in
–
The operability of the server safety mechanisms, e.g. stoppers or holding
back systems, must be guaranteed.
–
The form of the rack support uprights must ensure the frontal screwing on of
the telescope rails.
–
Frontally bolted telescopic rails or gliding rails.
The rails are provided with a linear alignment facility to ensure also an
adjustment to different rack depths.
–
No support for the cable management delivered with the mounting kit.
–
Climatic conditions.
An air intake unimpeded to a large extent in the rack front and an air
discharge in the rear cover of the rack are necessary for the ventilation of the
installed server.
In principle, the ventilation concept envisages that the necessary cooling is
reached by the horizontal self-ventilation of the installed devices (air flow
from the front to the rear).
–
Power supply.
Presence of appropriate socket strips must be ensured for the installation in
3rd-Party Racks.
1
rack front side
2
rack rear side
A
rack depth (comparison PRIMECENTER Rack 940/1000 mm)
B
rack width (comparison PRIMECENTER Rack 700 mm)
C
clearance of the 19-inch installation level
C1
front 19-inch installation level
C2
rear 19-inch installation level
D
area for cable routing (cable area depth) and ventilation
E
area for front panel and ventilation
F
right and left area for support systems
P
PRIMERGY installation depth
a1
front left support upright
a2
front right support upright
b1
rear left support upright
b2
rear right support upright