110
INF-TN2FSC-E
“SUPPLY TEMPERATURE”:
Sets the feeding temperature.
When you select “ANALOg INPUT
CHANNEL1”, current input of CH1
is set to returning temperature.
Set the 10.3.2(1) Input CH1 of clause
definition to “CURRENT (SUPPLY
TEMP.)”.
When you set the definition of In-
put CH2 to the “CURRENT (TEMP
DIFF.)”, the SUPPLY TEMP. will be
disabled.
When you select “TEMPERATURE
SETTINg”, the temperature you
entered is set to feeding temperature.
Setting range : –40 to 240ºC
“MODE”
: Select the “ENERgY MODE”.
When you select “NOT USED”, calo-
rie is not measured.
“OPERATION”
: Sets the environment for the pipe to be
measured. Select from the menu for
setting.
* Not cooling/heating operation (when
you select “OTHERS”, set the conver-
sion coefficient of heat quantity.)
Setting range: 1.000 to 9.999
“FLUX MEASUREMENT”:
Sets the position to measure the flow
rate of heating medium.