![Fuji Electric FSC-2 Скачать руководство пользователя страница 117](http://html1.mh-extra.com/html/fuji-electric/fsc-2/fsc-2_instruction-manual_2341885117.webp)
108
INF-TN2FSC-E
(5) AO CALIBRATION: when adjusting output circuit (prepare an ammeter)
Calibration procedure
10.3.2(1) set the “ANALOg INPUT/OUTPUT” to the “USED”
[Operation]
(1) Move the cursor to the “OUTPUT” on the SETTINg screen by pressing the or key
and display the OUTPUT screen.
Press the
ENT
key, and the cursor moves to 4 mA.
(2) Select either 4 mA or 20 mA by the or , and press the
ENT
key.
Adjust the output circuit so that outputs are adjusted to either 4 mA (0% output calibration)
or 20 mA (100% output calibration) by pressing the or key.
(3) Press the
ENT
key to set up.
ENT
Adjust output to 20mA
and press .
ENT
Adjust output to 4 mA
with an ammeter and
press .
ENT
ENT
“Output calibration” by
pressing the or key.
“Output calibration” by
pressing the or key.
key
key
Transition from
4 mA to 20 mA
or vice versa.