2-1
Chapter 2 MOUNTING AND WIRING OF THE INVERTER
2.1 Operating Environment
Install the inverter in an environment that satisfies the requirements listed in Table 2.1.
Table 2.1 Environmental Requirements
Item
Specifications
Site location Indoors
Ambient
temperature
-10 to +50
C (14 to 122
F) (IP20)
(Note 1)
Relative
humidity
5 to 95% (No condensation)
Atmosphere The inverter must not be exposed to dust,
direct sunlight, corrosive gases, flammable
gas, oil mist, vapor or water drops.
(Note 2)
The atmosphere can contain only a low level
of salt.
(0.01 mg/cm
2
or less per year)
The inverter must not be subjected to sudden
changes in temperature that will cause
condensation to form.
Altitude
1,000 m (3300 ft) max.
(Note 3)
Atmospheric
pressure
86 to 106 kPa
Vibration
3 mm (0.12 inch) (Max.
amplitude)
2 to less than 9 Hz
9.8 m/s
2
9 to less than 20 Hz
2 m/s
2
20 to less than 55 Hz
1 m/s
2
55 to less than 200 Hz
.
Please do not the deviant use the use environment.
Otherwise a failure could occur.
2.2 Installing the Inverter
(1) Mounting base
The temperature of the heat sink may rise up to approx.
90°C (194
F) during operation of the inverter, so the
inverter should be mounted on a base made of material
that can withstand temperatures of this level.
Install the inverter on a base made of metal or other
non-flammable material.
A fire may result with other material.
Table 2.2 Output Current Derating Factor in
Relation to Altitude
Altitude
Output current de-
rating factor
1000 m (
3300 ft)
or lower
1.00
1000 to 1500 m
(
3300 to 4900 ft)
0.97
1500 to 2000 m
(
4900 to 6600 ft)
0.95
2000 to 2500 m
(
6600 to 8200 ft)
0.91
2500 to 3000 m
(
8200 to 9800 ft)
0.88
(Note 1)
When inverters are mounted
side-by-side without any gap between them,
the ambient temperature should be within
the range from -10 to +40
C (14 to 104
F).
(Note 2)
Do not install the inverter in an
environment where it may be exposed to
cotton waste or moist dust or dirt which will
clog the heat sink in the inverter. If the
inverter is to be used in such an environ-
ment, install it in the panel of your system or
other dustproof containers.
(Note 3)
If you use the inverter in an altitude
above 1000 m (3300 ft), you should apply an
output current derating factor as listed in
Table 2.2.
Figure 2.1 Mounting Direction and
Required Clearances
Top 100
mm((3.9inches)
Bottom 100 mm
(3.9 inch)
Left
10mm
(0.39
inch)
Right
10mm
(0.39
inch)