FR Скачать руководство пользователя страница 105](http://html1.mh-extra.com/html/fuji-electric/frn0001c2s-2a-frn0002c2s-2a-frn0004c2s-2a-frn0006c2s-2a-frn0010c2s-2a-frn0012c2s-2a-frn0020c2s-2a-frn0025c2s-2a-frn0033c2s-2a-fr/frn0001c2s-2a-frn0002c2s-2a-frn0004c2s-2a-frn0006c2s-2a-frn0010c2s-2a-frn0012c2s-2a-frn0020c2s-2a-frn0025c2s-2a-frn0033c2s-2a-fr_instruction-manual_2341870105.webp)
5-6
E codes: Extension Terminal Functions
Code
Name
Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
E01
Terminal [X1] Function
Selecting function code data assigns the
corresponding function to terminals [X1] to
[X3] as listed below.
–
–
N
Y
0
5-44
E02
Terminal [X2] Function
0 (1000): Select multistep frequency (
SS1
)
–
–
N
Y
7
E03
Terminal [X3] Function
1 (1001): Select multistep frequency (
SS2
)
–
–
N
Y
8
2 (1002): Select multistep frequency (
SS4
)
3 (1003): Select multistep frequency (
SS8
)
4 (1004): Select ACC/DEC time
(
RT1
)
6 (1006): Enable 3-wire operation
(
HLD
)
7 (1007): Coast to a stop
(
BX
)
8 (1008): Reset alarm
(
RST
)
9 (1009): Enable external alarm trip (
THR
)
10 (1010): Ready for jogging
(
JOG
)
11 (1011): Select frequency command 2/1
(
Hz2/Hz1
)
12 (1012): Select motor 2/motor 1 (
M2/M1
)
13:
Enable DC braking
(
DCBRK
)
17 (1017): UP (Increase output frequency)
(
UP
)
18 (1018): DOWN (Decrease output
frequency)
(
DOWN
)
19 (1019): Enable data change with keypad
(
WE-KP
)
20 (1020): Cancel PID control
(
Hz/PID
)
21 (1021): Switch normal/inverse operation
(
IVS
)
24 (1024): Enable communications link
via RS-485
(
LE
)
33 (1033): Reset PID integral and
differential components
(
PID-RST
)
34 (1034): Hold PID integral component
(
PID-HLD
)
Setting the value in parentheses ( ) shown
above assigns a negative logic input
(Active-OFF) to a terminal.
Note that, in the case of
THR
, data "1009" is
for normal logic (Active-ON) and "9," for
negative logic (Active-OFF).
Signals having no value in parentheses ( )
cannot be used for negative logic.
E10
Acceleration Time 2
0.00 to 3600
Note: Entering 0.00 cancels the acceleration
time, requiring external soft-start and -stop.
0.01
s
Y
Y
6.00
5-25
E11
Deceleration Time 2
0.00 to 3600
Note: Entering 0.00 cancels the deceleration
time, requiring external soft-start and -stop.
0.01
s
Y
Y
6.00