FR Скачать руководство пользователя страница 117](http://html1.mh-extra.com/html/fuji-electric/frn0001c2s-2a-frn0002c2s-2a-frn0004c2s-2a-frn0006c2s-2a-frn0010c2s-2a-frn0012c2s-2a-frn0020c2s-2a-frn0025c2s-2a-frn0033c2s-2a-fr/frn0001c2s-2a-frn0002c2s-2a-frn0004c2s-2a-frn0006c2s-2a-frn0010c2s-2a-frn0012c2s-2a-frn0020c2s-2a-frn0025c2s-2a-frn0033c2s-2a-fr_instruction-manual_2341870117.webp)
5-18
J codes: Application Functions
Code
Name
Data setting range
Incre-
ment
Unit
Change
when
running
Data
copying
Default
setting
Refer
to
page:
J01
PID Control
0: Disable
–
–
N
Y
0
–
(Mode selection) 1: Enable (Process control, normal
operation)
2: Enable (Process control, inverse
operation)
J02
(Remote command SV) 0: UP/DOWN keys on keypad
–
–
N
Y
0
1: PID process command 1
(Analog input terminals [12] and [C1])
3: Terminal command
UP
/
DOWN
control
4: Command via communications link
J03
P (Gain) 0.000 to 30.000 *2
0.001
times
Y
Y
0.100
J04
I (Integral time) 0.0 to 3600.0 *2
0.1
s
Y
Y
0.0
J05
D (Differential time) 0.00 to 600.00 *2
0.01
s
Y
Y
0.00
J06
(Feedback filter) 0.0 to 900.0
0.1
s
Y
Y
0.5
J15
(Operation level
for slow flowrate stop)
0.0 (Disable), 1.0 to 400.0
0.1
Hz
Y
Y
0.0
J16
(Elapsed time
from slow flowrate stop)
0 to 3600
1
s
Y
Y
30
J17
(Initiation frequency) 0.0 to 400.0
0.1
Hz
Y
Y
0.0
J23
(Initiation deviation level
for slow flowrate stop)
0.0 to 100.0
0.1
%
Y
Y
0.0
J24
(Start latency time
for slow flowrate stop)
0 to 3660
1
s
Y
Y
0
J68
Braking Signal
0 to 200 *3
1
%
Y
Y
100
(Brake OFF current)
J69
(Brake OFF frequency) 0.0 to 25.0
0.1
Hz
Y
Y
1.0
J70
(Brake OFF timer) 0.0 to 5.0
0.1
s
Y
Y
1.0
J71
(Brake ON frequency) 0.0 to 25.0
0.1
Hz
Y
Y
1.0
J72
(Brake ON timer) 0.0 to 5.0
0.1
s
Y
Y
1.0
*2 When you make settings from the keypad, the incremental unit is restricted by the number of digits that the LED monitor can display.
(Example) If the setting range is from -200.00 to 200.00, the incremental unit is:
"1" for -200 to -100, "0.1" for -99.9 to -10.0 and for 100.0 to 200.0, and "0.01" for -9.99 to -0.01 and for 0.00 to 99.99.
*3 For the single-phase 100 V class series, the percentage is relative to the reference current; for other series, it is relative to the rated output current.