FR Скачать руководство пользователя страница 258](http://html1.mh-extra.com/html/fuji-electric/frn0001c2s-2a-frn0002c2s-2a-frn0004c2s-2a-frn0006c2s-2a-frn0010c2s-2a-frn0012c2s-2a-frn0020c2s-2a-frn0025c2s-2a-frn0033c2s-2a-fr/frn0001c2s-2a-frn0002c2s-2a-frn0004c2s-2a-frn0006c2s-2a-frn0010c2s-2a-frn0012c2s-2a-frn0020c2s-2a-frn0025c2s-2a-frn0033c2s-2a-fr_instruction-manual_2341870258.webp)
11-7
Table 11.2 Leakage Current of EMC-compliant Filter (optional)
Input power
Inverter type
Filter type
Leakage current (mA)
*1)
Normal
Worst
Three-phase 200 V
FRN0001C2S-2A
FS5956-6-46
(EFL-0.75E11-2)
3.0
*2)
3.0
*2)
FRN0002C2S-2A
FRN0004C2S-2A
FRN0006C2S-2A
FRN0010C2S-2A
FS5956-26-47
(EFL-4.0E11-2)
3.0
*2)
3.0
*2)
FRN0012C2S-2A
FRN0020C2S-2A
FRN0025C2S-2A
FS5956-53-52
11.0
*2)
11.0
*2)
FRN0033C2S-2A
FRN0047C2S-2A
EFL-15SP-2
20.0
*2)
20.0
*2)
FRN0060C2S-2A
Three-phase 400 V
FRN0002C2S-4
FS20229-3, 5-07
3.0
*3)
18.0
*3)
FRN0004C2S-4
FRN0005C2S-4
FS20229-9-07
3.0
*3)
18.0
*3)
FRN0007C2S-4
FRN0011C2S-4
FS20229-13-07
3.0
*3)
18.0
*3)
FRN0013C2S-4
FS21559-24-07-1
4.0
*3)
59.0
*3)
FRN0018C2S--4
FRN0024C2S--4
FS21312-44-07
4.0
*4)
167.0
*4)
FRN0030C2S--4
Single-phase 200 V
FRN0001C2S-7
FS8082-10-07
4.0
*5)
8.1
*5)
FRN0002C2S-7
FRN0004C2S-7
FRN0006C2S-7
FRN0010C2S-7
FS20159-17-07
4.2
*5)
8.4
*5)
FRN0012C2S-7
FS20159-25-07
4.2
*5)
8.4
*5)
Note: A box (
) in the above table replaces A, C, or E depending on the shipping destination.
*1) The worst condition includes a phase loss in the supply line.
*2) The values are calculated assuming the power supplies of three-phase 240 V (50 Hz).
*3) The values are calculated assuming the power supplies of three-phase 400 V (50 Hz).
*4) The values are calculated assuming the power supplies of three-phase 480 V (50 Hz).
*5) The values are calculated assuming the power supplies of single-phase 230 V (50 Hz).