14
External Input/Output Terminal
Input/
output
No.
Terminal
name
Function
Analog
output
9
V-OUT
Analog voltage output terminal.
10
I-OUT
Analog current output terminal.
11
COM
COM terminal for analog voltage and current voltage.
Do not short-circuit external input/output terminals
Nos. 18 and 24.
Input
12
RESET
Clears judgment results and sets digital zero.
13
FREE
Constantly outputs comparison results.
14
END
Judges and outputs results.
You can change the input logic of external input/output terminal
No. 14 END. See Page 55 Control input logic.
15
MODE
Not for use when Hold mode selection is set By menu.
When Hold mode selection is By signal, it holds a sample
with OFF (HIGH) and holds a peak with ON (LOW).
16
SEL 1
Not for use when Setting Memory is set By menu.
When Setting Memory is set to By signal, you can change
Setting Memory between SEL 1 and SEL 2.
17
SEL 2
18
COM
COM terminal of external input.
Do not short-circuit external input/output terminal
Nos. 11.
Output
19
OV
Produces output when it detects an anomaly of a load
cell.
20
LO
Produces output when the judgment result is LO.
21
OF
Set load arrival output. Differs from the judgment result.
Regardless of the input edge of END, it produces output
when the set load arrives.
22
HI
Produces output when the judgment result is HI.
23
GO
Produces output when the judgment result is GO.
24
COM
COM terminal of external output.
Do not short-circuit external input/output terminal
Nos. 11.