PREPARE THE BURNER FOR START-UP
Start-up checklist – Verify the following before attempting to start burner
o Combustion air supply and venting have been inspected and verified to be free of obstruction
and installed in accordance with all applicable codes.
o Fuel connection to nozzle line assembly is secure.
o Fuel supply line is correctly installed, the oil tank is sufficiently filled, and shut-off valves are
open.
START THE BURNER
WARNING
Do not proceed unless all prior steps in this manual have been completed. Failure to
comply could result in severe personal injury, death or substantial property damage.
WARNING
Do not attempt to start the burner when excess oil has accumulated, when the appliance is
full of vapor or when the combustion chamber is very hot. Do not attempt to re-establish
flame with the burner running if the flames should be extinguished during start-up, venting
or adjustment. Allow the unit to cool off and all vapors to dissipate before attempting
another start. Failure to comply with these guidelines could cause an explosion or fire,
resulting in severe personal injury, death or substantial property damage.
AIR SETTING
The low fire cam should be set at 30 and the
high fire cam at 45. Refer to figure shown below.
In some cases these air-setting needs to be adjusted.
To do this insert your flue gas analyzer into the flue, 6 inches above the top of unit.
Measure you excess O2% and CO2% levels. Set your air shutter to bring your O2% levels
between 5-6%. Your CO2% will be between 9-10% and your CO levels should be around
zero. Alternately, set the burner for #1 smoke spot on the Bacharach scale.
9
High Fire Cam 45 SetPoint
Low Fire Cam 30 SetPoint
Transition cam set at 35
(Between high and low fire cams)