Mode
Description
Information
Default
pin
DRM5
+P
nom
≤
0% without discon-
nection from grid
Limits the effective power out-
put
6
DRM6
+P
nom
≤
50%
Limits the effective power out-
put
7
DRM7
+P
nom
≤
75% & -Q
rel
*
≥
0%
restricts the effective power
output
and
sets the reactive power
8
DRM8
+P
nom
≤
100%
Normal operation without re-
striction
9
FDI
on the Fronius DRM interface
*
The values for Q
rel
can be adjusted in the UC Editor menu item.
The nominal device output is always meant when referring to the inverter's remote con-
trol capability.
IMPORTANT!
If no DRM control (DRED) is connected to Datamanager and the "AUS –
Demand Response Mode (DRM)" function is activated, the inverter switches to standby
mode.
IO control
The pins for the IO control can be set here. Additional settings can be adjusted in the
"PSC editor - IO control" menu.
IO control
Default
pin
IO control
Default
pin
IO control 1 (optional)
2
IO control 6 (optional)
7
IO control 2 (optional)
3
IO control 7 (optional)
8
IO control 3 (optional)
4
IO control 8 (optional)
9
IO control 4 (optional)
5
IO control feedback
(optional)
0
IO control 5 (optional)
6
Load manage-
ment
Up to four pins for the load management can be selected here. Further settings for the
load management are available in the load management menu item.
Default pin: 1
71
EN-US
Содержание Datamanager 2.0
Страница 2: ......
Страница 6: ...6 ...
Страница 7: ...General information 7 ...
Страница 8: ...8 ...
Страница 30: ...30 ...
Страница 31: ...Installing Fronius Datamanager 2 0 31 ...
Страница 32: ...32 ...
Страница 34: ...The next slot must be kept free Never remove an existing ENS plug in card ENS Datamanager 34 ...
Страница 49: ...Establishing a Connection to Froni us Datamanager 2 0 49 ...
Страница 50: ...50 ...
Страница 53: ...Current Data Services and Settings on Fronius Datamanager 2 0 53 ...
Страница 54: ...54 ...
Страница 86: ...86 ...
Страница 87: ...87 EN US ...
Страница 88: ... ...