4.5 Periodic inspection and cleaning (approx. 1,000 hrs)
For fuels with a low ash content, cleaning and inspection after approx. 1,000 service
hours is usually sufficient (under normal use conditions, approximately every quarter).
For less efficient fuels and fuels with a high ash content (indicated by short emptying
intervals for the ash container), the work should be carried out more frequently
accordingly.
WARNING
Inspection and cleaning work on a system which is operational:
Risk of serious injuries from automatic startup of the system and severe burns
from hot parts and the flue gas pipe!
When working on the system:
❒ always wear protective gloves
❒ only operate the boiler using the handles provided
❒ switch off the boiler by tapping “Boiler off” at the mode icon
➥ The boiler follows the shutdown procedure and switches to “Switched off
OFF“ status
❒ switch off the main switch and take precautions to prevent accidental
switching on
❒ allow the boiler to cool off for at least 1 hour
❒ once all of the tasks have been completed, turn the main switch back on and
switch the boiler on in the desired mode
4.5.1 Cleaning the ash transfer chamber
(Pos. A
⇨ See "Periodic inspection and cleaning" [page 42]
)
1. Remove the cleaning door at the back of the boiler
2. Check the ash level and clean the ash transfer chamber if necessary
– Tip: use an ash vacuum!
Servicing
4
Periodic inspection and cleaning (approx. 1,000 hrs)
Operating Instructions | B1300015_en
43