Troubleshooting
Fault messages
Fröling Heizkessel- und Behälterbau Ges.m.b.H, Industriestraße 12, A-4710 Grieskirchen
Page 21
Tel. +43 (0) 7248 606-0 Fax +43 (0) 7248 606-600 [email protected]
www.froeling.com
Edition: 23.03.2005
5
5 Troubleshooting
There are two main types of fault: internal and external.
5.1 External
faults
U
The heating EMERGENCY STOP switch has been pressed.
U
A house fuse (FI-protective circuit breaker) or a fuse in the control system has tripped
U
The safety temperature limiter has triggered.
5.2 Internal
boiler
faults
When a fault has occurred and
has not yet been cleared:
- Status LED
7.6
or
8.5
blinks red
- A fault message is displayed on the
display
Internally, a distinction is made between a fault and a warning. A fault has the same effect as an
“EMERGENCY STOP” and shuts down the system immediately. A warning, on the other hand,
shuts down the system in a controlled manner.
Fault message list:
À
See the operating instructions for the “Digitronic S 3100” or “Lambdatronic S 3100”
5.2.1
Resetting the safety temperature limiter (STB)
The safety temperature limiter shuts down the
boiler when it reaches a maximum temperature
of 105°C.
After the boiler has cooled down, the safety
temperature limiter
10
must be manually
unlocked:
U
Unscrew the cap on the safety temperature
limiter
U
Release the safety temperature limiter by
pressing with a thin rod.
5.2.2
Acknowledging a fault message
Trace and remove the fault and then:
U
Press enter key