6.5.3 Positioning the doors
The example below shows how to position the fuel loading door. The procedure is the
same for positioning the combustion chamber door!
2-3 cm
r
Loosen the lock nuts on the locking cams at the top and bottom
r
Close the door
Ä
With a gap of approx. 2 to 3 cm there should be a noticeable resistance
r
If the resistance is too low or too high, move the locking cams backwards or forwards
using the key provided (SW 32 mm)
Ä
The movement of the locking cams causes the hinged plate to move, allowing the
contact pressure to be adjusted
Ä
Caution: The two locking cams (top and bottom) must be adjusted equally!
r
Close the door
r
If the door will not close, move the locking cams forward slightly
Ä
Caution: The two locking cams (top and bottom) must be adjusted equally!
r
Tighten the lock nuts (M8)