Connection requirements of chilled water pipes
a) All chilled water pipelines should be thoroughly 

flushed, to be free of any impurity, before the unit is 

operated. Anyimpurity should not be flushed to or into the 

heat exchanger.
b) Water must enter the heat exchanger through the inlet; 

otherwise the performance of the unit will decline.
c) The inlet pipe of the evaporator must be provided with 

a target flow controller, to realize flow-break protection 

for the unit. Both ends of the target flow controller must 

be supplied with horizontal straight pipe sections whose 

diameter is 5 times that of the inlet pipe. The target 

flow controller must be installed in strict accordance 

with “Installation & Regulation Guide for Target Flow 

Controller” (Fig.8-28, 8-29). The wires of the target flow 

controller should be led to the electric cabinet through 

shielded cable (see Electric Controlling Schematic 

Diagram for details). The working pressure of the target 

flow controller is 1.0MPa, and its interface is 1 inch in 

diameter. After the pipelines are installed, the target flow 

controller will be set properly according to the rated water 

flow of the unit.
d) The pump installed in the water pipeline system should 

beequipped with starter. The pump will directly press 

water into the heat exchanger of the water system.

e) The pipes and their ports must be independently 

supported but should not be supported on the unit.
f) The pipes and their ports of the heat exchanger should 

be easy to disassemble for operation and cleaning, as 

well as inspection of port pipes of the evaporator.
g) The evaporator should be provided with a filter with 

more than 40 meshes per inch at site. The filter should 

be installed near to the inlet port as much as possible, 

and be under heat preservation.
h) The by-pass pipes and by-pass valves as shown in 

Fig.8-23 must be mounted for the heat exchanger, to 

facilitate cleaning of the outside system of water passage 

before the unit is adjusted. During maintenance, the 

water passage of the heat exchanger can be cut off 

without disturbing other heat exchangers.
i) The flexible ports should be adopted between the 

interface of the heat exchanger and on-site pipeline, to 

reduce transfer of vibration to the building.
j) To facilitate maintenance, the inlet and outlet pipes 

should be provided with thermometer or manometer. 

The unit is not equipped with pressure and temperature 

instruments, so they need to be purchased by the user.
k) All low positions of the water system should be 

provided with drainage ports, to drain water in the 

evaporator and the system completely; and all high 

positions should be supplied with discharge valves, to 

facilitate expelling air from the pipeline. The discharge 

valves and drainage ports should not be under heat 

preservation, to facilitate maintenance.
l) All possible water pipes in the system to be chilled 

should be under heat preservation, including inlet pipes 

and flanges of the heat exchanger.
m) The outdoor chilled water pipelines should be 

wrapped with an auxiliary heating belt for heat 

preservation, and the material of the auxiliary heat belt 

should be PE, EDPM, etc., with thickness of 20mm, to 

prevent the pipelines from freezing and thus cracking 

under low temperature. The power supply of the heating 

belt should be equipped with an independent fuse.
n) When the ambient temperature is lower than 2°C, and 

the unit will be not used for a long time, water inside the 

unit should be drained. If the unit is not drained in winter, 

its power supply should not be cut off, and the fan coils 

in the water system must be provided with three-way 

valves, to ensure smooth circulation of the water system 

when the anti-freezing pump is started up in winter.
o) The common outlet pipelines of combined units should 

be provided with mixing water temperature sensor.

NOTE

CAUTION

CAUTION

WARNING

When the power cord is parallel to the signal wire, 

make sure that they are enclosed in respective 

conduits and are kept a reasonable wire spacing. 

(Distance between the power cord and signal wire: 

300mm if below 10A, and 500mm if below 50A) 

In the case of multiple units connection, the  

HMI of KEM-30 DRS4 and KEM-60 DRS4  

can be paralleled with in the same system.  

But, KEM-30 DRS4 and KEM-60 DRS4  

can not be paralleled with KEM-30 DNS3  

and KEM-60 DNS3

•  After the unit is in place, chilled water pipes 

can be laid.

•  The relevant installation regulations should be 

abided with when conducting connection of 

water pipes.

•  The pipelines should be free of any impurity, 

and all chilled water pipes must conform 

to local rules and regulations of pipeline 

engineering.

•  For the water pipeline network including 

filters and heat exchangers, dreg or dirt may 

seriously damages the heat exchangers and 

water pipes.

•  The installation persons or the users must 

ensure the quality of chilled water, and de-

icing salt mixtures and air should be excluded 

from the water system, since they may 

oxidize and corrode steel parts inside the 

heat exchanger.

8.6 Water system installation

8.6.1 Basic requirements of 

connection of chilled water pipes

Содержание Kaysun KEM-30 DRS4

Страница 1: ...you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference KEM 30 DRS4 KEM 60 DRS4 OWNER S INSTALLATION MANU...

Страница 2: ...on 08 6 4 Installation of damping devices 08 6 5 Installation of device to prevent snow build up and strong breeze 09 7 CONNECTION DRAWING OF PIPELINE SYSTEM 10 8 OVERVIEW OF THE UNIT 8 1 Main parts o...

Страница 3: ...irst startup after shutdown 33 11 8 Refrigeration system 33 11 9 Disassembling compressor 33 11 10 Auxiliary electric heater 33 11 11 System antifreezing 33 11 12 Replacement of safety valve 34 11 13...

Страница 4: ......

Страница 5: ...power supply is 380 415V 3N 50Hz the minimum allowable voltage is 342V and the maximum voltage is 456V 2 To maintain better performance please operate the unit under the following outdoor temperature...

Страница 6: ...s also used to alert against unsafe practices Indicates situations that could only result in accidental equipment or property damage Explanation of symbols displayed on the indoor unit or outdoor unit...

Страница 7: ...ls electric shocks or fire After completing the installation work check to make sure that there is no refrigerant leakage Never directly touch any leaking refrigerant as it could cause severe frostbit...

Страница 8: ...ans in accordance with national wiring regulation and this circuit diagram An all pole disconnection device which has at least 3mm separation distance in all pole and a residual current device RCD wit...

Страница 9: ...and copper pipes 4 If the unit is within the reach of unauthorized personnel take protective measures for safety considerations such as installing a fence These measures can prevent man caused or acci...

Страница 10: ...ine dimensional of KEM 30 DRS4 6 1 2 KEM 60 DRS4 B Left view Front view E D F A C Top view Fig 6 2 Outline dimensional of KEM 60 DRS4 Table 6 1 Model KEM 30 DRS4 KEM 60 DRS4 A 1870 2220 B 1000 1325 C...

Страница 11: ...rsian blinds are required the total loss of static pressure should be less than the static pressure outside the fan The space between the unit and sunk fence or Persian blinds should also meet the req...

Страница 12: ...is directed away from roadways and footpaths especially in locations where the climate is such that condensate may freeze unit mm Drainage channel Anchor bolt Inlet and outlet pipe side Electric cont...

Страница 13: ...w 1 Measures to prevent build up of snow The base height should be as least the same as the predicted snow depth in the local area Outdoor unit Base height Fig 6 10 Snow prevention base height 2 Light...

Страница 14: ...ain valve Two way valve Three way valve Terminal Auxiliary electric heater unit unit Y type filter requiring 40 meshes unit Fig 7 1 Connection drawing of pipeline system 8 OVERVIEW OF THE UNIT 8 1 Mai...

Страница 15: ...r 1 Door 2 Door 3 Door 4 Fig 8 3 Doors of KEM 30 DRS4 Door 1 give access to the compartment of water pipes and water side heat exchanger Door 2 3 4 give access to the hydraulic compartment and electri...

Страница 16: ...sure switch 28 Fast oil return solenoid valve 7 Oil separator 29 Low pressure switch 8 4 way valve 30 Filter 9 System pressure sensor 31 Capillary 10 DC fan 32 Outdoor ambient temperature sensor 11 Co...

Страница 17: ...erature control switch 1 33 Suction temperature sensor 8 Discharge temperature control switch 2 34 Low pressure switch 9 One way valve1 35 Filter 10 One way valve2 36 Capillary 11 High pressure switch...

Страница 18: ...ted only in the early period after the power supply is connected and they are not detected while the unit is in operation 2 CN12 Quick return oil solenoid valve 3 CN5 EVA HEAT Water side heat exchange...

Страница 19: ...erature sensor of the condenser T5 water tank temperature sensor T6A Refrigerant inlet temperature of EVI plate heat exchanger T6B Refrigerant inlet temperature of EVI plate heat exchanger 24 CN16 Sys...

Страница 20: ...ntrol valid for S12 2 ON S12 3 Normal cooling mode valid for S12 3 OFF factory default Low temperature cooling valid for S12 3 ON 41 CN7 TEMP SW Target water temperature switching port 42 ENC2 POWER D...

Страница 21: ...nnecting the power supply Please carefully read the labels on the electric cabinet The user s attempt to repair the controller is prohibited since improper repair may cause electric shock damages to t...

Страница 22: ...Electrical wiring precaution c d Power wiring must be entrusted to professionals with electrician qualification Fig 8 9 4 Electrical wiring precaution d 8 5 5 Power supply specification Table 8 6 Ite...

Страница 23: ...current Grounding 3 Grounding 2 Grounding 1 Grounding wire Lightning arrester Power distribution transformer Manual switch Fuses Power 380 415V 3N 50Hz Unit Fig 8 10 Requirements of power supply wirin...

Страница 24: ...to monitor the state of com pressor When the compressor is operating the light will be powered on The wiring of water pump and pipeline auxiliary heater and ac light of the state of compressor is as...

Страница 25: ...o the ALARM ports of the module units as follows electric control box ALARM port Device provided by user Fig 8 16 Wiring of ALARM port If the unit is operating unnormally the ALARM port is closed othe...

Страница 26: ...ry heater according to the actual parameter of products and national Contactor Contactor Power Transformer AC220 240V AC 8 5 V CN2 CN60 IRU SLSHOLQH CN74 CN61 0 1 21752 5 21752 5 CN60 CN74 CN61 5 5 5...

Страница 27: ...0V AC 8 5 V CN2 CN60 IRU SLSHOLQH CN74 CN61 0 1 21752 5 21752 5 CN60 CN74 CN61 5 5 5 5 021 725 5 21752 5 CN60 CN74 CN61 5 5 5 5 021 725 5 21752 5 7 7 20 7 X Y X Y X Y 203 67 7 3803 1 CN83 7 CN30 7 7 C...

Страница 28: ...chased by the user k All low positions of the water system should be provided with drainage ports to drain water in the evaporator and the system completely and all high positions should be supplied w...

Страница 29: ...c 1 1 4 KEM 60 DRS4 Hoop connection DN50 Fig 8 20 connection mode of KEM 30 DRS4 pipe Fig 8 21 connection mode of KEM 60 DRS4 pipe 8 6 3 Design of the store tank in the system kW is the unit for cooli...

Страница 30: ...water resistance h2 Pump water resistance h3 Water resistance of the longest water loop distance includes pipe resistance different valve s resistance flexible pipe resistance pipe elbow and three way...

Страница 31: ...24 Installation of multi module no more than 16 modules 2 Table of diameter parameters of main inlet and outlet pipes Table 8 10 Cooling capacity Total inlet and outlet water pipe inside nominal diam...

Страница 32: ...up at low outdoor ambient temperatures During initial start up and when water temperature is low it is important that the water is heated gradually Failure to do so may result in concrete floors crack...

Страница 33: ...a fault code If a fault occurs remove the fault first and start the unit according to the operating method in the unit control instruction after determining that there is no fault existing in the unit...

Страница 34: ...A system discharge temperature sensorfailure Recovered upon error recovery 2Ed B system discharge temperature sensor failure Recovered upon error recovery 16 EF Unit water return temperature sensor fa...

Страница 35: ...system B 68 F7 Not insert electronic expansion valve Recovered by power off 70 xF9 Inverter module temperature sensor error x 1 means Tfin1 x 2 means Tfin2 72 Fb Pressure sensor error Recovered upon...

Страница 36: ...nt air conditioner errors which bring inconvenience to your life and work 2 Maintenance of main parts Close attention should be paid to the discharge and suction pressure during the running process Fi...

Страница 37: ...d water circulate and start up unit and make the low pressure control switch short circuit if necessary Slowly inject refrigerant into the system and check suction and discharge pressure 11 9 Disassem...

Страница 38: ...et of safty valve 7 8 UNF Fig 11 1 Replacement of safety valve WARNING The air outlet of safety valve must be connected to the appropriate pipe which can direct the leaking refrigerant to the appropri...

Страница 39: ...ately ventilated before breaking into the system or conducting any hot work A degree of ventilation shall continue during the period that the work is carried out The ventilation should safely disperse...

Страница 40: ...detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe...

Страница 41: ...oning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ens...

Страница 42: ...pressure 5 Check running current 6 Whether unit has been through refrigerant leakage test 7 Whether there is noise on all the panels ofunit 8 Check whether the main power source connection iscorrect R...

Страница 43: ...ressure switch freeze proof device water flow volume controller Overcurrent device power phase sequence device etc Refrigerant Type R 32 Water pipe system Charging volume kg 7 9 14 0 Waterflow volume...

Страница 44: ...0 Tj 25 C Pdc 13 15 kW Tj 25 C EERd 5 35 Tj 20 C Pdc 6 58 kW Tj 20 C EERd 6 90 Degradation co efficient for chillers Cdc 0 90 Power consumption in modes other than active mode Off mode POFF 0 02 kW Cr...

Страница 45: ...3 86 kW Tj 25 C EERd 4 50 Tj 20 C Pdc 11 72 kW Tj 20 C EERd 5 04 Degradation co efficient for chillers Cdc 0 9 Power consumption in modes other than active mode Off mode POFF 0 030 kW Crankcase heater...

Страница 46: ...operating limit temperature WTOL C Cycling interval capacity for heating at Tj 2 C Pcych kW Cycling interval efficiency at Tj 7 C COPcyc Degradation coefficient 4 at T 2 C Cdh Cycling interval capacit...

Страница 47: ...t T 7 C Cdh Heating water operating limit temperature WTOL C Cycling interval capacity for heating at Tj 2 C Pcych kW Degradation coefficient 4 at T 2 C Cdh Cycling interval efficiency at Tj 7 C COPcy...

Страница 48: ......

Отзывы: