08

6.3 Installation foundation

6.3.1 Base structure

Outdoor unit base structure design should take account of 

the following considerations:
1) A solid base prevents excess vibration and noise. Outdoor 

unit bases should be constructed on solid ground or on 

structures of sufficient strength to support the units’ weight.
2) Bases should be at least 200mm high to provide sufficient 

access for installation of piping. Snow protection should also 

be considered for the base height.
3) Either steel or concrete bases may be suitable.
4) A typical concrete base design is shown in Fig. 6-5. A 

typical concrete specification is 1 part cement, 2 parts sand 

and 4 parts crushed stone with steel reinforcing bar. The 

edges of the base should be chamfered.
5) To ensure that all contact points are equally secure, bases 

should be completely level. Base design should ensure that 

the points on the units’ bases designed for weight-bearing 

support are fully supported.

ŐPP

Concrete base
 h

Ő

200mm

Rubber anti-vibration pads

Solid ground / surface

Ő

200mm

Outdoor unit

Fig. 6-5 Front view of base structure

6.3.2  Location drawing of installation 

foundation of the unit: (unit: mm) 

1) If the unit is located so high that it is inconvenient for 

maintenance personnel to conduct maintenance, the suitable 

scaffold can be provided around the unit.

2) The scaffold must be able to bear the weight of 

maintenance personnel and maintenance facilities.

3) The bottom frame of the unit is not allowed to be 

embedded into the concrete of installation foundation.

4) A drainage ditch should be provided to allow drainage of 

condensate that may form on the heat exchangers when 

the units are running in heating mode. The drainage should 

ensure that condensate is directed away from roadways and 

footpaths, especially in locations where the climate is such 

that condensate may freeze.

 (unit: mm) 

 

Drainage channel 

Anchor bolt

 

Inlet and outlet 

pipe side

Electric control 

box side

Fig. 6-6 Top view of schematic diagram of installation 

dimension of KEM-30 DRS4

(unit: mm) 

 

Drainage channel 

Anchor bolt

Electric control 

Inlet and outlet 

box side

pipe side

Fig. 6-7 Top view of schematic diagram of installation 

dimension of KEM-60 DRS4

6.4 Installation of damping devices

6.4.1  Damping devices must be provided 

between the unit and its foundation.

By means of the Φ15mm diameter installation holes on the 

steel frame of the unit base, the unit can be fastened on 

the foundation through the spring damper. See Fig.6-6, 6-7 

(Schematic diagram of installation dimension of the unit) for 

details about center distance of the installation holes. The 

damper does not go with the unit, and the user can select 

the damper according to the relevant requirements. When 

the unit is installed on the high roof or the area sensitive 

to vibration, please consult the relevant persons before 

selecting the damper.

6.4.2 Installation steps of the damper

Step 1. Make sure that the flatness of the concrete foundation 

is within ±3mm, and then place the unit on the cushion block.
Step 2. Raise the unit to the height suitable for installation of 

the damping device.
Step 3. Remove the clamp nuts of the damper. Place the unit 

on the damper, and align the fixing bolt holes of the damper 

with the fixing holes on the unit base.
Step 4. Return the clamp nuts of the damper to the fixing 

holes on the unit base, and tighten them into the damper. 
Step 5. Adjust the operational height of the damper base, and 

screw down the leveling bolts. Tighten the bolts by one circle 

to ensure equal height adjustment variance of the damper.
Step 6. The lock bolts can be tightened after the correct 

operational height is reached.

Содержание Kaysun KEM-30 DRS4

Страница 1: ...you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference KEM 30 DRS4 KEM 60 DRS4 OWNER S INSTALLATION MANU...

Страница 2: ...on 08 6 4 Installation of damping devices 08 6 5 Installation of device to prevent snow build up and strong breeze 09 7 CONNECTION DRAWING OF PIPELINE SYSTEM 10 8 OVERVIEW OF THE UNIT 8 1 Main parts o...

Страница 3: ...irst startup after shutdown 33 11 8 Refrigeration system 33 11 9 Disassembling compressor 33 11 10 Auxiliary electric heater 33 11 11 System antifreezing 33 11 12 Replacement of safety valve 34 11 13...

Страница 4: ......

Страница 5: ...power supply is 380 415V 3N 50Hz the minimum allowable voltage is 342V and the maximum voltage is 456V 2 To maintain better performance please operate the unit under the following outdoor temperature...

Страница 6: ...s also used to alert against unsafe practices Indicates situations that could only result in accidental equipment or property damage Explanation of symbols displayed on the indoor unit or outdoor unit...

Страница 7: ...ls electric shocks or fire After completing the installation work check to make sure that there is no refrigerant leakage Never directly touch any leaking refrigerant as it could cause severe frostbit...

Страница 8: ...ans in accordance with national wiring regulation and this circuit diagram An all pole disconnection device which has at least 3mm separation distance in all pole and a residual current device RCD wit...

Страница 9: ...and copper pipes 4 If the unit is within the reach of unauthorized personnel take protective measures for safety considerations such as installing a fence These measures can prevent man caused or acci...

Страница 10: ...ine dimensional of KEM 30 DRS4 6 1 2 KEM 60 DRS4 B Left view Front view E D F A C Top view Fig 6 2 Outline dimensional of KEM 60 DRS4 Table 6 1 Model KEM 30 DRS4 KEM 60 DRS4 A 1870 2220 B 1000 1325 C...

Страница 11: ...rsian blinds are required the total loss of static pressure should be less than the static pressure outside the fan The space between the unit and sunk fence or Persian blinds should also meet the req...

Страница 12: ...is directed away from roadways and footpaths especially in locations where the climate is such that condensate may freeze unit mm Drainage channel Anchor bolt Inlet and outlet pipe side Electric cont...

Страница 13: ...w 1 Measures to prevent build up of snow The base height should be as least the same as the predicted snow depth in the local area Outdoor unit Base height Fig 6 10 Snow prevention base height 2 Light...

Страница 14: ...ain valve Two way valve Three way valve Terminal Auxiliary electric heater unit unit Y type filter requiring 40 meshes unit Fig 7 1 Connection drawing of pipeline system 8 OVERVIEW OF THE UNIT 8 1 Mai...

Страница 15: ...r 1 Door 2 Door 3 Door 4 Fig 8 3 Doors of KEM 30 DRS4 Door 1 give access to the compartment of water pipes and water side heat exchanger Door 2 3 4 give access to the hydraulic compartment and electri...

Страница 16: ...sure switch 28 Fast oil return solenoid valve 7 Oil separator 29 Low pressure switch 8 4 way valve 30 Filter 9 System pressure sensor 31 Capillary 10 DC fan 32 Outdoor ambient temperature sensor 11 Co...

Страница 17: ...erature control switch 1 33 Suction temperature sensor 8 Discharge temperature control switch 2 34 Low pressure switch 9 One way valve1 35 Filter 10 One way valve2 36 Capillary 11 High pressure switch...

Страница 18: ...ted only in the early period after the power supply is connected and they are not detected while the unit is in operation 2 CN12 Quick return oil solenoid valve 3 CN5 EVA HEAT Water side heat exchange...

Страница 19: ...erature sensor of the condenser T5 water tank temperature sensor T6A Refrigerant inlet temperature of EVI plate heat exchanger T6B Refrigerant inlet temperature of EVI plate heat exchanger 24 CN16 Sys...

Страница 20: ...ntrol valid for S12 2 ON S12 3 Normal cooling mode valid for S12 3 OFF factory default Low temperature cooling valid for S12 3 ON 41 CN7 TEMP SW Target water temperature switching port 42 ENC2 POWER D...

Страница 21: ...nnecting the power supply Please carefully read the labels on the electric cabinet The user s attempt to repair the controller is prohibited since improper repair may cause electric shock damages to t...

Страница 22: ...Electrical wiring precaution c d Power wiring must be entrusted to professionals with electrician qualification Fig 8 9 4 Electrical wiring precaution d 8 5 5 Power supply specification Table 8 6 Ite...

Страница 23: ...current Grounding 3 Grounding 2 Grounding 1 Grounding wire Lightning arrester Power distribution transformer Manual switch Fuses Power 380 415V 3N 50Hz Unit Fig 8 10 Requirements of power supply wirin...

Страница 24: ...to monitor the state of com pressor When the compressor is operating the light will be powered on The wiring of water pump and pipeline auxiliary heater and ac light of the state of compressor is as...

Страница 25: ...o the ALARM ports of the module units as follows electric control box ALARM port Device provided by user Fig 8 16 Wiring of ALARM port If the unit is operating unnormally the ALARM port is closed othe...

Страница 26: ...ry heater according to the actual parameter of products and national Contactor Contactor Power Transformer AC220 240V AC 8 5 V CN2 CN60 IRU SLSHOLQH CN74 CN61 0 1 21752 5 21752 5 CN60 CN74 CN61 5 5 5...

Страница 27: ...0V AC 8 5 V CN2 CN60 IRU SLSHOLQH CN74 CN61 0 1 21752 5 21752 5 CN60 CN74 CN61 5 5 5 5 021 725 5 21752 5 CN60 CN74 CN61 5 5 5 5 021 725 5 21752 5 7 7 20 7 X Y X Y X Y 203 67 7 3803 1 CN83 7 CN30 7 7 C...

Страница 28: ...chased by the user k All low positions of the water system should be provided with drainage ports to drain water in the evaporator and the system completely and all high positions should be supplied w...

Страница 29: ...c 1 1 4 KEM 60 DRS4 Hoop connection DN50 Fig 8 20 connection mode of KEM 30 DRS4 pipe Fig 8 21 connection mode of KEM 60 DRS4 pipe 8 6 3 Design of the store tank in the system kW is the unit for cooli...

Страница 30: ...water resistance h2 Pump water resistance h3 Water resistance of the longest water loop distance includes pipe resistance different valve s resistance flexible pipe resistance pipe elbow and three way...

Страница 31: ...24 Installation of multi module no more than 16 modules 2 Table of diameter parameters of main inlet and outlet pipes Table 8 10 Cooling capacity Total inlet and outlet water pipe inside nominal diam...

Страница 32: ...up at low outdoor ambient temperatures During initial start up and when water temperature is low it is important that the water is heated gradually Failure to do so may result in concrete floors crack...

Страница 33: ...a fault code If a fault occurs remove the fault first and start the unit according to the operating method in the unit control instruction after determining that there is no fault existing in the unit...

Страница 34: ...A system discharge temperature sensorfailure Recovered upon error recovery 2Ed B system discharge temperature sensor failure Recovered upon error recovery 16 EF Unit water return temperature sensor fa...

Страница 35: ...system B 68 F7 Not insert electronic expansion valve Recovered by power off 70 xF9 Inverter module temperature sensor error x 1 means Tfin1 x 2 means Tfin2 72 Fb Pressure sensor error Recovered upon...

Страница 36: ...nt air conditioner errors which bring inconvenience to your life and work 2 Maintenance of main parts Close attention should be paid to the discharge and suction pressure during the running process Fi...

Страница 37: ...d water circulate and start up unit and make the low pressure control switch short circuit if necessary Slowly inject refrigerant into the system and check suction and discharge pressure 11 9 Disassem...

Страница 38: ...et of safty valve 7 8 UNF Fig 11 1 Replacement of safety valve WARNING The air outlet of safety valve must be connected to the appropriate pipe which can direct the leaking refrigerant to the appropri...

Страница 39: ...ately ventilated before breaking into the system or conducting any hot work A degree of ventilation shall continue during the period that the work is carried out The ventilation should safely disperse...

Страница 40: ...detection fluids are suitable for use with most refrigerants but the use of detergents containing chlorine shall be avoided as the chlorine may react with the refrigerant and corrode the copper pipe...

Страница 41: ...oning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropriate refrigerant recovery cylinders are employed Ens...

Страница 42: ...pressure 5 Check running current 6 Whether unit has been through refrigerant leakage test 7 Whether there is noise on all the panels ofunit 8 Check whether the main power source connection iscorrect R...

Страница 43: ...ressure switch freeze proof device water flow volume controller Overcurrent device power phase sequence device etc Refrigerant Type R 32 Water pipe system Charging volume kg 7 9 14 0 Waterflow volume...

Страница 44: ...0 Tj 25 C Pdc 13 15 kW Tj 25 C EERd 5 35 Tj 20 C Pdc 6 58 kW Tj 20 C EERd 6 90 Degradation co efficient for chillers Cdc 0 90 Power consumption in modes other than active mode Off mode POFF 0 02 kW Cr...

Страница 45: ...3 86 kW Tj 25 C EERd 4 50 Tj 20 C Pdc 11 72 kW Tj 20 C EERd 5 04 Degradation co efficient for chillers Cdc 0 9 Power consumption in modes other than active mode Off mode POFF 0 030 kW Crankcase heater...

Страница 46: ...operating limit temperature WTOL C Cycling interval capacity for heating at Tj 2 C Pcych kW Cycling interval efficiency at Tj 7 C COPcyc Degradation coefficient 4 at T 2 C Cdh Cycling interval capacit...

Страница 47: ...t T 7 C Cdh Heating water operating limit temperature WTOL C Cycling interval capacity for heating at Tj 2 C Pcych kW Degradation coefficient 4 at T 2 C Cdh Cycling interval efficiency at Tj 7 C COPcy...

Страница 48: ......

Отзывы: