10
920-087-06
Wall Sleeve Installation Instructions (PDXWS)
NOTE: Insure that the unit is only installed in a wall structurally adequate to support the unit including the sleeve, chassis and
accessories. If the sleeve projects more than 8" into the room, a subbase or other means of support MUST be used. Please read
these instructions completely before attempting installation.
For Deep Wall Installation See Section II
The following instructions apply ONLY to walls less than
13 ¼" in depth.
1. From inside the building, position the wall sleeve in the
opening and push it through the wall so it protrudes at least
¼" on the outside, note Figure 5.
2. Position the wall sleeve with a slight tilt towards the outside
to facilitate condensate drainage. It should be level side-
to-side and the front should be ¼ bubble higher than the
back.
Electrical shock hazard.
Turn electric power OFF at the fuse box or service panel
before making any electrical connections and ensure a
proper ground connection is made before connecting line
voltage. Failure to do so can result in property damage,
personal injury and/or death.
Typical Wall Sleeve Installation
Figure 5
42¼"
(107.3 cm) min.
50" (127 cm) max.
10"
(25.4 cm)
max.
16¼
"
(41.3 cm)
13¾
"
(34.9 cm)
Lintel to support masonry walls
Electrical receptacle
Wall opening
Wall sleeve
Insulation
Smooth side of screw
clip facing into room
Electrical receptacle
Insulation
Note: All 230/208V units are manufactured with a 60" power cord. The receptacle
locations above must be followed to ensure proper connections.
Falling Object Hazard
Not following Installation Instructions
for mounting your air conditioner can
result in property damage, injury, or
death.
WARNING
NOTICE
DO NOT allow any pitch toward the inside.
Potential property damage can occur if instructions
are not followed.
WARNING