26

920-087-06

Diagnostics

The Friedrich Smart Center continuously monitors the PTAC unit 
operation and will store service codes if certain conditions are 
witnessed.  In some cases the unit may take action and shut the 
unit off until conditions are corrected.
To access the error code menu press the 

‘Heat’

 and 

‘High Fan’ 

buttons simultaneously for three seconds. If error codes are 
present they will be displayed. If multiple codes exist you can 
toggle between messages using the temp   button. To clear 
all codes press the temp   button for three seconds while in 
the error code mode. To exit without changing codes press the 

‘Low Fan’

 button.

Test Mode

For service and diagnostic use only, the built-in timers and 
delays on the PTAC may be bypassed by pressing the 

‘Cool’

 

and 

‘Low Fan’

 buttons simultaneously for three seconds while 

in any mode to enter the test mode. 

CE

 will be displayed when 

entering test mode, and 

OE

 will be displayed when exiting. The 

test mode will automatically be exited 30 minutes after entering it 
or by pressing the 

‘Cool’

 and 

‘Low Fan’ 

buttons simultaneously 

for three seconds.

Digital Control Diagnostics and Test Mode

The chart below lists the possible error codes and their description:

Error

Code

Code Translation

Action Taken by Unit

Possible Cause

E F

“Error Free” - No Codes Stored

None

Unit Operating Normally

02

An extreme low voltage condition exists 
<198V for 230V units and <239V for 265V 
units. 

Shut down unit.  Display Error code and 

fl

 ash. 

Once voltage rises to normal level system power is 
restored.

• Inadequate power supply
• Defective breaker
• Blown fuse

03

Return air thermistor sensor open or short 
circuit

Set return air sensor = 75°F.  Alternately 

fl

 ash set 

point and error code.  Leave unit running.

• Defective sensor

04

Indoor coil thermistor sensor open or short 
circuit

Set ID coil temp = 40°F.  Alternately 

fl

 ash set point 

and error code.  Leave unit running.

• Defective sensor

05

Outdoor coil thermistor sensor open Or 
short circuit

Set OD coil temp = 20°F.  Alternately 

fl

 ash set point 

and error code.  Automatically change over to Elec-
tric heat Mode only.  Leave unit running.

• Defective sensor

06

If O.D. coil Temperature > 175 Deg F for 2 
consecutive minutes.  (Heat Pump models 
only)

Alternately 

fl

 ash set point and error code.  Shut unit 

down for 5 minutes, then try again 2 times, if fails 
the 3rd time then shut down unit.

• Dirty coil
• Fan motor failure
• Restricted air 

fl

 ow

• Non-condensables in
   refrigeration system

07

I.D coil temperature <30 Deg F for 2 con-
secutive minutes.

Alternately 

fl

 ash set point and error code.  Continue 

fan operation while the compressor is locked out 
until the indoor coil thermistor reaches 45° F, then 
energize the compressor.  However, compressor 
must still wait a lockout time of 180 to 240 seconds.

• Dirty 

fi

 lters

• Dirty coil
• Fan motor failure
• Restricted air

fl

 ow

• Improper refrigerant charge
• Restriction in refrigerant circuit

08

Unit cycles (Heat or Cool demand) > 9 times 
per hour

Store error code in memory.
Keep unit running

• Unit oversized
• Low load conditions

09

Unit cycles (Heat or Cool demand) < 3 times 
per hour

Store Error Code in memory.
Keep unit running

• Unit undersized
• High load conditions

10

Room Freeze Protection triggered

Alternately 

fl

 ash set point and error code.  Keep unit 

running.

• Room temperature fell below     
   40°F

11

No Signal to “GL or “GH” terminal (Remote 
Thermostat mode only)

Shut down unit. Display error code and 

fl

 ash.

• Defective remote thermostat
• Defective thermostat wiring

12

Discharge air temperature >185º F

Alternately 

fl

 ash set point and error code.  Open all 

relays and run high fan.  If condition repeats three 
times in one hour, shut down unit.

• Restricted air 

fl

 ow

• Fan motor failure

13

If Pressure limit switch opens

Turn OFF compressor. Alternate 

fl

 ash set point 

and error code

14

Discharge air temperature sensor open or 
shorted

Set the temperature sensor = 75º F Alternately 

fl

 ash 

set point and error code.  Leave unit running.

• Defective Sensor

 

Содержание PDH07K3SB1

Страница 1: ...920 087 06 4 08 PTAC PACKAGED TERMINAL AIR CONDITIONERS HEAT PUMPS Standard Control Remote Thermostat Seacoast Protected INSTALLATION OPERATION GUIDE...

Страница 2: ...trol Diagnostics and Test Mode 26 Accessories 27 28 Warranty 29 Table of Contents Your safety and the safety of others are very important CAUTION NOTICE We have provided many important safety messages...

Страница 3: ...3 920 087 06 Typical Unit Components Front cover Chassis Wall sleeve Outdoor grille...

Страница 4: ...and install the equipment Installation must be in conformance with the NFPA 70 2008 National Electric Code or current edition and Uniform Mechanical Code current edition and applicable local or natio...

Страница 5: ...AC units should be installed no closer than 12 apart when two units are side by side If three or more PTAC units are to operate next to one another allow a minimum of 36 between units Also a vertical...

Страница 6: ...new Friedrich digital PTAC features a self diagnostic program that can alert maintenance to component failures or operating problems The internal diagnostic program saves properties valuable time whe...

Страница 7: ...cause the indoor coil to freeze When the indoor coil reaches 30 F the compressor is diabled and the fan continues to operate based on demand Once the coil temperature returns to 45 F the compressor re...

Страница 8: ...locally to connect the internal drain tube to the drain system in the building 6 Referring to Detail A on page 9 locate and assemble the 2 two cover plates and gaskets over the drain holes at the rear...

Страница 9: ...ard the wall sleeve 3 Attach the drain tube assembly to one of the two drain holes at the rear of the wall sleeve The large flange on the mounting plate is positioned at the bottom of the sleeve facin...

Страница 10: ...e higher than the back Electrical shock hazard Turn electric power OFF at the fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before co...

Страница 11: ...re not followed Figure7 NOTE Construct wall opening to comply with all applicable building codes Main studs Jack studs Main studs Jack studs Lintel Mounting screw holes No holes in bottom of wall slee...

Страница 12: ...Secure the wall sleeve extension to the wall sleeve before installing it in the wall Refer to Figure 8 for a guide for fabrication ofacondensatedrippanel ThepanelMUSTextendthefulldepth of the wall sl...

Страница 13: ...outs facing down From inside the building maneuver the grille through the wall sleeve and pull toward you until the screw heads are inserted into the keyhole slots at the top of the wall sleeve Tighte...

Страница 14: ...eets the UL and NEC requirements for cord connected air conditioners effective August 2004 To test your power supply cord 1 Plug power supply cord into a grounded 3 prong outlet 2 Press RESET 3 Press...

Страница 15: ...ressor Chassis shipping bracket Shipping pallet IMPORTANT WheninstallingaFriedrichP SeriesPTACintoan existing sleeve it is important to ensure that the unit is installed completely Inspection of the a...

Страница 16: ...g brackets on the wall sleeve flange two per side 6 Install the front cover assembly including the discharge grille by placing the top of the cover onto the 90 angle bracket along the top of the chass...

Страница 17: ...onditions and in the event that the room falls below 40 F the unit will cycle on high fan with the electric heater This occurs regardless of mode 4 Emergency Heat Override Switch 7 In the unlikely eve...

Страница 18: ...mergencyHeatOperation In the event of a compressor failure in heat pump mode the com pressormaybelockedouttoprovideheatthroughtheresistance heater This feature ensures that even in the unlikely event...

Страница 19: ...ommand to the PTAC unit The remote signal has some ability to bounce off of walls and furniture similar to a television remote control The diagram below shows the typical operating range of the contro...

Страница 20: ...To revert back to the Smart Center control of the unit replace the jumper wire between the GL and GH terminals that was removed in step 1 ThermostatConnections C Common Ground W Call for Heating Y Cal...

Страница 21: ...r tampering with the unit s internal wiring can void the equipmentwarrantyandmayresultinpropertydamage personal injury or death Other manufacturer s PTACs and even older Friedrich models may have diff...

Страница 22: ...ure components and accessories such as the control door and front cover Check the unit air filter condenser coil and evaporator coil for any obstructions Check for proper operation of all components I...

Страница 23: ...maintenance and service to the chassis Line Voltage Connections Figure18 5 Make the appropriate electrical connections within the control box then secure the box on the chassis Detailed instructions a...

Страница 24: ...coil cleaning agent on coils or base pan Use a biodegradable cleaning agent and degreaser NOTE Units are to be inspected and serviced by qualified service personnel only Discharge Air Grille Filters...

Страница 25: ...for proper sizing Istheoutdoortemperature60 Forbelow The unit is designed for outdoor temperatures above 60 F Istheindoortemperature80 Forabove Ambient indoor temperatures of 80 F or above will take...

Страница 26: ...rror code Leave unit running Defective sensor 05 Outdoor coil thermistor sensor open Or short circuit Set OD coil temp 20 F Alternately flash set point and error code Automatically change over to Elec...

Страница 27: ...to the outside of the wall sleeve when the wall is greater than 11 inches thick 9 when a subbase is used 10 inches when a lateral duct is used Up to three exten sions my be used together PXSB DECORAT...

Страница 28: ...r The extension can be cut to length by the installer Maximum allowable straight extension is 15 feet PXCJ CONDUIT KIT WITH JUNCTION BOX Hard wire conduit kit with junction box for 208 230V and 265V u...

Страница 29: ...sented to establish the original purchase date otherwise the beginning date of this certificate will be considered to be our shipment date plus sixty days Replacement parts can be new or remanufacture...

Отзывы: