background image

18

920-087-06

Cooling Mode

Pressing the ‘

Cool

’ button while the unit is in any mode, including 

off, will put the unit into cooling mode. Adjust the temperature 
readout to the desired room temperature and the unit will cycle 
the compressor on and off to maintain a comfortable room. The 
compressor will come on anytime that the room temperature is 
1.8°F above the desired temperature. The fan operation is de-
pendent on the fan mode selected, either continuous or cycling. 
See page 16 for fan cycle control. 

Heating Mode

Pressing the ‘Heat’ button while the unit is in any mode, including 
off, will put the unit into heating mode. 

Heat Pump Models (PDH)

When the ‘Heat’ button is pressed initially the unit will energize 
the electric resistance heat to quickly bring the room to the set 
temperature. When the desired room temperature falls 1.8°F 
below the desired set temperature the unit will cycle the com-
pressor on and operate as a heat pump to maintain the room 
temperature while running more ef

fi

 ciently than resistance heat 

only models. If the room temperature should fall more than 5°F 
from the set temperature the unit will run the resistance heater. 
The fan operation is dependent on the fan mode selected, either 
continuous or cycling. Dip switch 5 controls the fan mode, see 
page 17 for setting.
When the outdoor coil temperature falls below 30°F for more 
than 2 minutes the unit will operate the resistance heaters and 
not the compressor. When the outdoor coil temperature reaches 
45°F the compressor will be allowed to operate again.

Heat/Cool Models (PDE)

After pressing the ‘Heat’ button, adjust the temperature readout 
to the desired room temperature and the unit will cycle the re-
sistance heat on and off to maintain a comfortable room. The 
heater will come on anytime that the room temperature is 1.8°F 
below the desired temperature. The fan operation is dependent 
on the fan mode selected, either continuous or cycling. Dip switch 
5 controls the fan mode, see page 16 for setting.

Emergency Heat Operation

In the event of a compressor failure in heat pump mode the com-
pressor may be locked out to provide heat through the resistance 
heater. This feature ensures that even in the unlikely event of a 
compressor failure the room temperature can be maintained 
until the compressor can be serviced. Dip switch 7 controls the 
emergency heat setting, see page 16.

Fan Mode

Fan Only

Pressing the ‘

Fan Only

’ button will run the fan to allow for 

air circulation in the room without operating the compressor 
or heater regardless of the room or set temperature. The fan 
speed selection is made by pressing either the ‘

High Fan

’ or 

Low Fan

’ button.

Figure 12  

Digital Control Panel

Cycle/Continuous

The owner may choose between fan cycling or fan continu-
ous mode based on property preference (Note: Even  heat 
monitoring and quiet start/stop fan delay only operate in fan 
cycle mode). Fan continuous mode is used to keep constant 
air

fl

 ow circulation in the room during all times the unit is ‘ON’. 

Fan cycle will conserve energy by only operating the fan while 
the compressor or electric heater is operating. Dip switch 5 
controls the fan mode, see page 17 for setting.

Optional Hand Held Remote Control Operation

Friedrich PTAC units can be con

fi

 gured to operate via an op-

tional hand held remote control for added convenience. The 
PTAC control board comes shipped with all of the necessary 
hardware to communicate to the PDXRC remote control.  In 
order to operate the unit with the remote control, the remote 
control sensor must be enabled. Simply press and hold the 
‘Temp’   and   buttons simultaneously for three seconds, and 
the LED window will display and “

E

” for con

fi

 rmation when the 

remote is enabled. To disable the feature press ‘Temp’   and 

 buttons at the same time for three seconds. LED will display 

an “

O

” as acknowledgment for one second.

The remote control is now ready for use.  The temperature, mode 
and fan speed control from the remote control will operate the 
unit the same as the unit mounted controls.
NOTE: The hand held remote control cannot be used in conjunc-
tion with a wall mounted thermostat.

Figure 13

Remote Control

Low

Temperature

Cool

Power

Cooler

Fan

Only

Warmer

Heat

Fan

High

Fan

Содержание PDH07K3SB1

Страница 1: ...920 087 06 4 08 PTAC PACKAGED TERMINAL AIR CONDITIONERS HEAT PUMPS Standard Control Remote Thermostat Seacoast Protected INSTALLATION OPERATION GUIDE...

Страница 2: ...trol Diagnostics and Test Mode 26 Accessories 27 28 Warranty 29 Table of Contents Your safety and the safety of others are very important CAUTION NOTICE We have provided many important safety messages...

Страница 3: ...3 920 087 06 Typical Unit Components Front cover Chassis Wall sleeve Outdoor grille...

Страница 4: ...and install the equipment Installation must be in conformance with the NFPA 70 2008 National Electric Code or current edition and Uniform Mechanical Code current edition and applicable local or natio...

Страница 5: ...AC units should be installed no closer than 12 apart when two units are side by side If three or more PTAC units are to operate next to one another allow a minimum of 36 between units Also a vertical...

Страница 6: ...new Friedrich digital PTAC features a self diagnostic program that can alert maintenance to component failures or operating problems The internal diagnostic program saves properties valuable time whe...

Страница 7: ...cause the indoor coil to freeze When the indoor coil reaches 30 F the compressor is diabled and the fan continues to operate based on demand Once the coil temperature returns to 45 F the compressor re...

Страница 8: ...locally to connect the internal drain tube to the drain system in the building 6 Referring to Detail A on page 9 locate and assemble the 2 two cover plates and gaskets over the drain holes at the rear...

Страница 9: ...ard the wall sleeve 3 Attach the drain tube assembly to one of the two drain holes at the rear of the wall sleeve The large flange on the mounting plate is positioned at the bottom of the sleeve facin...

Страница 10: ...e higher than the back Electrical shock hazard Turn electric power OFF at the fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before co...

Страница 11: ...re not followed Figure7 NOTE Construct wall opening to comply with all applicable building codes Main studs Jack studs Main studs Jack studs Lintel Mounting screw holes No holes in bottom of wall slee...

Страница 12: ...Secure the wall sleeve extension to the wall sleeve before installing it in the wall Refer to Figure 8 for a guide for fabrication ofacondensatedrippanel ThepanelMUSTextendthefulldepth of the wall sl...

Страница 13: ...outs facing down From inside the building maneuver the grille through the wall sleeve and pull toward you until the screw heads are inserted into the keyhole slots at the top of the wall sleeve Tighte...

Страница 14: ...eets the UL and NEC requirements for cord connected air conditioners effective August 2004 To test your power supply cord 1 Plug power supply cord into a grounded 3 prong outlet 2 Press RESET 3 Press...

Страница 15: ...ressor Chassis shipping bracket Shipping pallet IMPORTANT WheninstallingaFriedrichP SeriesPTACintoan existing sleeve it is important to ensure that the unit is installed completely Inspection of the a...

Страница 16: ...g brackets on the wall sleeve flange two per side 6 Install the front cover assembly including the discharge grille by placing the top of the cover onto the 90 angle bracket along the top of the chass...

Страница 17: ...onditions and in the event that the room falls below 40 F the unit will cycle on high fan with the electric heater This occurs regardless of mode 4 Emergency Heat Override Switch 7 In the unlikely eve...

Страница 18: ...mergencyHeatOperation In the event of a compressor failure in heat pump mode the com pressormaybelockedouttoprovideheatthroughtheresistance heater This feature ensures that even in the unlikely event...

Страница 19: ...ommand to the PTAC unit The remote signal has some ability to bounce off of walls and furniture similar to a television remote control The diagram below shows the typical operating range of the contro...

Страница 20: ...To revert back to the Smart Center control of the unit replace the jumper wire between the GL and GH terminals that was removed in step 1 ThermostatConnections C Common Ground W Call for Heating Y Cal...

Страница 21: ...r tampering with the unit s internal wiring can void the equipmentwarrantyandmayresultinpropertydamage personal injury or death Other manufacturer s PTACs and even older Friedrich models may have diff...

Страница 22: ...ure components and accessories such as the control door and front cover Check the unit air filter condenser coil and evaporator coil for any obstructions Check for proper operation of all components I...

Страница 23: ...maintenance and service to the chassis Line Voltage Connections Figure18 5 Make the appropriate electrical connections within the control box then secure the box on the chassis Detailed instructions a...

Страница 24: ...coil cleaning agent on coils or base pan Use a biodegradable cleaning agent and degreaser NOTE Units are to be inspected and serviced by qualified service personnel only Discharge Air Grille Filters...

Страница 25: ...for proper sizing Istheoutdoortemperature60 Forbelow The unit is designed for outdoor temperatures above 60 F Istheindoortemperature80 Forabove Ambient indoor temperatures of 80 F or above will take...

Страница 26: ...rror code Leave unit running Defective sensor 05 Outdoor coil thermistor sensor open Or short circuit Set OD coil temp 20 F Alternately flash set point and error code Automatically change over to Elec...

Страница 27: ...to the outside of the wall sleeve when the wall is greater than 11 inches thick 9 when a subbase is used 10 inches when a lateral duct is used Up to three exten sions my be used together PXSB DECORAT...

Страница 28: ...r The extension can be cut to length by the installer Maximum allowable straight extension is 15 feet PXCJ CONDUIT KIT WITH JUNCTION BOX Hard wire conduit kit with junction box for 208 230V and 265V u...

Страница 29: ...sented to establish the original purchase date otherwise the beginning date of this certificate will be considered to be our shipment date plus sixty days Replacement parts can be new or remanufacture...

Отзывы: