Friedrich Digital Control Features

The new Friedrich digital PTAC has state of the art features to improve guest comfort, indoor air quality and conserve energy.  Through 
the use of speci

fi

 cally designed control software for the PTAC industry Friedrich has accomplished what other Manufacturer’s have only 

attempted – a quiet, dependable, affordable and easy to use PTAC.
Below is a list of standard features on every Friedrich PTAC and their bene

fi

 t to the owner.

Digital Temperature 
Readout

By digitally monitoring desired room temperature the room is controlled more precisely than conventional systems. The large, easy 
to read LED display can show either set-point or actual room temperature as selected by owner.

One-Touch Operation

When the unit is powered off the unit can be returned directly to heating or cooling mode by pressing the ‘Heat’ or ‘Cool’ buttons 
without the confusing power up sequence of some controls. One-touch control takes guesswork out of unit control delivering a more 
enjoyable experience and eliminating front-desk calls.

Individual Mode and 
Fan Control Buttons

By having separate control buttons and indicators for both fan and mode settings the Friedrich digital control eliminates the confusion 
of previous digital PTACs. The accurate temperature setting provides greater guest comfort than other systems.

Quiet Start/Stop
 Fan Delay

The fan start and stop delays prevent abrupt changes in room acoustics due to the compressor energizing or stopping immediately. 
Upon call for cooling or heating the unit fan will run for 

fi

 ve seconds prior to energizing the compressor. Also, the fan off delay allows 

for “free cooling” by utilizing the already cool indoor coil to its maximum capacity by running for 30 seconds after the compressor. 

Remote Thermostat 
Operation

Some applications require the use of a wall mounted thermostat. All new Friedrich PTACs may be switched from unit control to 
remote thermostat control easily without the need to order a special model or accessory kit.

Wireless Remote 
Control Ready

Guests can adjust the temperature and mode of the unit through the use of an optional hand held wireless remote, improving guest 
comfort and relaxation.

Internal Diagnostic 
Program

The new Friedrich digital PTAC features a self diagnostic program that can alert maintenance to component failures or operating 
problems. The internal diagnostic program saves properties valuable time when diagnosing running problems.

Service Error Code 
Storage

The self diagnosis program will also store error codes in memory if certain conditions occur and correct themselves such as extreme 
high or low operating conditions or activation of the room freeze protection feature. Storing error codes can help properties deter-
mine if the unit faced obscure conditions or if an error occurred and corrected itself.

Constant Comfort 
Room Monitoring

The on-board processor monitors time between demand cycles (heat or cool) and will cycle the fan every 9 minutes to sample the 
room condition and determine if the desired conditions are met. This allows the room to have similar bene

fi

 ts to a remote mounted 

stat without the complication or cost of a wall mounted thermostat. 

Electronic 
Temperature Limiting

By limiting the operating range the property can save energy by eliminating “max cool” or “max heat” situations common with older 
uncontrolled systems. The new electronic control allows owners to set operating ranges for both heating and cooling independently 
of one another.

Room Freeze 
Protection

When the PTAC senses that the indoor room temperature has fallen to 40

°

F the unit will cycle on high fan and the electric strip heat 

to raise the room temperature to 46

°

F then cycle off again. This feature works regardless of the mode selected and can be turned 

off. The control will also store the Room Freeze cycle in the service code memory for retrieval at a later date. This feature ensures 
that unoccupied rooms do not reach freezing levels where damage can occur to plumbing and 

fi

 xtures.

Random Compressor 
Restart

Multiple compressors starting at once can often cause electrical overloads and premature unit failure. The random restart delay 
eliminates multiple units from starting at once following a power outage or initial power up. The compressor delay will range from 
180 to 240 seconds.

Digital Defrost 
Thermostat

The new Friedrich PTAC uses a digital thermostat to accurately monitor the outdoor coil conditions to allow the heat pump to run 
whenever conditions are correct. Running the PTAC in heat pump mode saves energy and reduces operating costs. The digital 
thermostat allows maximization of heat pump run time.

Содержание PDH07K3SB1

Страница 1: ...920 087 06 4 08 PTAC PACKAGED TERMINAL AIR CONDITIONERS HEAT PUMPS Standard Control Remote Thermostat Seacoast Protected INSTALLATION OPERATION GUIDE...

Страница 2: ...trol Diagnostics and Test Mode 26 Accessories 27 28 Warranty 29 Table of Contents Your safety and the safety of others are very important CAUTION NOTICE We have provided many important safety messages...

Страница 3: ...3 920 087 06 Typical Unit Components Front cover Chassis Wall sleeve Outdoor grille...

Страница 4: ...and install the equipment Installation must be in conformance with the NFPA 70 2008 National Electric Code or current edition and Uniform Mechanical Code current edition and applicable local or natio...

Страница 5: ...AC units should be installed no closer than 12 apart when two units are side by side If three or more PTAC units are to operate next to one another allow a minimum of 36 between units Also a vertical...

Страница 6: ...new Friedrich digital PTAC features a self diagnostic program that can alert maintenance to component failures or operating problems The internal diagnostic program saves properties valuable time whe...

Страница 7: ...cause the indoor coil to freeze When the indoor coil reaches 30 F the compressor is diabled and the fan continues to operate based on demand Once the coil temperature returns to 45 F the compressor re...

Страница 8: ...locally to connect the internal drain tube to the drain system in the building 6 Referring to Detail A on page 9 locate and assemble the 2 two cover plates and gaskets over the drain holes at the rear...

Страница 9: ...ard the wall sleeve 3 Attach the drain tube assembly to one of the two drain holes at the rear of the wall sleeve The large flange on the mounting plate is positioned at the bottom of the sleeve facin...

Страница 10: ...e higher than the back Electrical shock hazard Turn electric power OFF at the fuse box or service panel before making any electrical connections and ensure a proper ground connection is made before co...

Страница 11: ...re not followed Figure7 NOTE Construct wall opening to comply with all applicable building codes Main studs Jack studs Main studs Jack studs Lintel Mounting screw holes No holes in bottom of wall slee...

Страница 12: ...Secure the wall sleeve extension to the wall sleeve before installing it in the wall Refer to Figure 8 for a guide for fabrication ofacondensatedrippanel ThepanelMUSTextendthefulldepth of the wall sl...

Страница 13: ...outs facing down From inside the building maneuver the grille through the wall sleeve and pull toward you until the screw heads are inserted into the keyhole slots at the top of the wall sleeve Tighte...

Страница 14: ...eets the UL and NEC requirements for cord connected air conditioners effective August 2004 To test your power supply cord 1 Plug power supply cord into a grounded 3 prong outlet 2 Press RESET 3 Press...

Страница 15: ...ressor Chassis shipping bracket Shipping pallet IMPORTANT WheninstallingaFriedrichP SeriesPTACintoan existing sleeve it is important to ensure that the unit is installed completely Inspection of the a...

Страница 16: ...g brackets on the wall sleeve flange two per side 6 Install the front cover assembly including the discharge grille by placing the top of the cover onto the 90 angle bracket along the top of the chass...

Страница 17: ...onditions and in the event that the room falls below 40 F the unit will cycle on high fan with the electric heater This occurs regardless of mode 4 Emergency Heat Override Switch 7 In the unlikely eve...

Страница 18: ...mergencyHeatOperation In the event of a compressor failure in heat pump mode the com pressormaybelockedouttoprovideheatthroughtheresistance heater This feature ensures that even in the unlikely event...

Страница 19: ...ommand to the PTAC unit The remote signal has some ability to bounce off of walls and furniture similar to a television remote control The diagram below shows the typical operating range of the contro...

Страница 20: ...To revert back to the Smart Center control of the unit replace the jumper wire between the GL and GH terminals that was removed in step 1 ThermostatConnections C Common Ground W Call for Heating Y Cal...

Страница 21: ...r tampering with the unit s internal wiring can void the equipmentwarrantyandmayresultinpropertydamage personal injury or death Other manufacturer s PTACs and even older Friedrich models may have diff...

Страница 22: ...ure components and accessories such as the control door and front cover Check the unit air filter condenser coil and evaporator coil for any obstructions Check for proper operation of all components I...

Страница 23: ...maintenance and service to the chassis Line Voltage Connections Figure18 5 Make the appropriate electrical connections within the control box then secure the box on the chassis Detailed instructions a...

Страница 24: ...coil cleaning agent on coils or base pan Use a biodegradable cleaning agent and degreaser NOTE Units are to be inspected and serviced by qualified service personnel only Discharge Air Grille Filters...

Страница 25: ...for proper sizing Istheoutdoortemperature60 Forbelow The unit is designed for outdoor temperatures above 60 F Istheindoortemperature80 Forabove Ambient indoor temperatures of 80 F or above will take...

Страница 26: ...rror code Leave unit running Defective sensor 05 Outdoor coil thermistor sensor open Or short circuit Set OD coil temp 20 F Alternately flash set point and error code Automatically change over to Elec...

Страница 27: ...to the outside of the wall sleeve when the wall is greater than 11 inches thick 9 when a subbase is used 10 inches when a lateral duct is used Up to three exten sions my be used together PXSB DECORAT...

Страница 28: ...r The extension can be cut to length by the installer Maximum allowable straight extension is 15 feet PXCJ CONDUIT KIT WITH JUNCTION BOX Hard wire conduit kit with junction box for 208 230V and 265V u...

Страница 29: ...sented to establish the original purchase date otherwise the beginning date of this certificate will be considered to be our shipment date plus sixty days Replacement parts can be new or remanufacture...