Rittal Liquid Cooling Package
51
14 SNMP card
14
14
SNMP card
To incorporate the device into a building management
system, a pCO Web card is installed in the electronics
box.
Then the LCP DX website provides all essential informa-
tion on the homepage. For example, it depicts a collec-
tive alarm. The name and location of the LCP DX may
also be configured on this website. A second operating
level allows you to set the server air injection tempera-
ture.
Logging on to the LCP DX website
Open the browser and enter the IP address of the
LCP DX (or the pCO Web card) in the address line.
Example of a static IP address:
http://172.16.0.1
A dialogue will appear for logging onto the LCP DX.
Enter
rittal
as the user and
1234
as the password.
The LCP DX website will appear.
Fig. 41:
LCP DX homepage
The following parameters are displayed in tabular form
on the LCP DX homepage.
– Server Temp In (average)
– Server Temp Out (average)
– Evaporation Temperature
– Condensation Temperature
– Evaporation Pressure
– Condensation Pressure
– Setpoint
– Fans Speed
– Electronic Valve Opening
– Compressor Inverter Speed
– Compressor Motor Current
The following parameters are displayed in diagrammatic
form on the LCP DX homepage.
– Setpoint speed for the fans
– Server-in temperature (top, middle, bottom)
– Server-out temperature (top, middle, bottom)
– Position of the electronic expansion valve
– Compressor speed
The 2nd menu level,
Main Setup
, is password-protect-
ed. The server air injection temperature of the LCP DX
may be set here.
Click on the
Main Setup
entry in the left-hand section
of the website.
Alternatively, click on the stylised Allen key in the cen-
tral section of the website, under
LCP-DX Overview
.
A further dialogue will appear for authentication.
Fig. 42:
Logging on to the 2nd menu level (Main Setup)
Once again, enter
rittal
as the user and
1234
as the
password.
The following screen will appear:
Fig. 43:
Setting the server air injection temperature
Set the server air injection temperature to the required
value between 7 °C and 25 °C.
Confirm your entry by clicking on the
Send Parame-
ters
button.
Clicking on the
Homepage
button will take you back
to the LCP DX homepage.