![FRIEDHELM LOH 3313.290 Скачать руководство пользователя страница 45](http://html1.mh-extra.com/html/friedhelm-loh/3313-290/3313-290_assembly-and-operating-instructions-manual_2332658045.webp)
Rittal Liquid Cooling Package
45
11 Technical specifications
11
11.2 Standard condenser
IP protection category IEC 60529
IP 20 (indoor)
Colour
RAL 7035
Technical specifications
Description/Model No.
Standard condenser / 3311.363
Dimensions and weight
Dimensions W x H x D ("H" version) [mm]
2282 x 818 x 552
Dimensions W x H x D ("V" version) [mm]
2282 x 510 x 480
Weight, max. [kg]
68
Electrical connection
Type of electrical connection
Connection clamp
Rated voltage [V, Hz]
230/1~/N/PE, 50
230/1~/N/PE, 60
Startup current [A]
3
2.8
Pre-fuse T [A]
6
6
Duty cycle [%]
100
Cooling circuit
Coolant/Fill volume [kg]
R410A/see tab. 22 "Total refrigerant charge"
Connection diameter refrigerant pipes [mm]
See tab. 23 "Refrigerant pipes"
External diameter of coolant lines [mm]
See tab. 23 "Refrigerant pipes" (1mm wall thickness)
Other information
Storage temperatures [°C]
-20…+55
Ambient temperature [°C]
-20…+45
Noise level [dB(A)]
(Open air above reflective flooring, distance 10 m)
45
Tab. 18:
Technical specifications for the standard condenser unit
Technical specifications
Tab. 17:
Technical specifications LCP DX