11 Technical specifications
11
46
Rittal Liquid Cooling Package
11.3 Low temperature unit
11.3.1 Low temperature condenser for ambient temperatures up to -40 °C
11.3.2 Winter kit module for operating the low temperature condenser unit
Technical specifications
Description/Model No.
Low temperature condenser
Dimensions and weight
Dimensions W x H x D ("H" version) [mm]
2282 x 818 x 552
Dimensions W x H x D ("V" version) [mm]
2282 x 510 x 480
Weight, max. [kg]
62
Electrical connection
Type of electrical connection
Connection clamp
Rated voltage [V, Hz]
230/1~/N/PE, 50
230/1~/N/PE, 60
Startup current [A]
2.7
2.7
Pre-fuse T [A]
6
6
Duty cycle [%]
100
Cooling circuit
Coolant/Fill volume [kg]
R410A/see tab. 22 "Total refrigerant charge"
Connection diameter refrigerant pipes [mm]
See tab. 23 "Refrigerant pipes"
External diameter of coolant lines [mm]
See tab. 23 "Refrigerant pipes" (1mm wall thickness)
Other information
Storage temperatures [°C]
-40…+55
Ambient temperature [°C]
-40…+45
Noise level [dB(A)]
(Open air above reflective flooring, distance 10 m)
45
Tab. 19:
Technical specifications for the low temperature condenser unit
Technical specifications
Description/Model No.
Winter kit module
Dimensions and weight
Dimensions W x H x D [mm]
505 x 400 x 305
Weight, max. [kg]
35
Electrical connection
Type of electrical connection
Connection clamp
Rated voltage [V, Hz]
230/1~/N/PE, 50
230/1~/N/PE, 60
Startup current [A]
0.6
0.6
Pre-fuse T [A]
6
6
Duty cycle [%]
100
Tab. 20:
Technical specifications for the winter kit module