7 Operation
7
36
Rittal Liquid Cooling Package
40
Memory alarm probe broken (analogic input
B4): LCP Server IN
–
0
1
R
Customer
41
Reserved – (not used or other special appli-
cation or internal debug)
–
0
1
R
Only for Service/
Manufacturer
42
Memory alarm probe broken (analogic input
B6): ROOM Server OUT
–
0
1
R
Customer
43
Memory alarm probe broken (analogic input
B7): ROOM Server OUT
–
0
1
R
Customer
44
Memory alarm probe broken (analogic input
B8): ROOM Server OUT
–
0
1
R
Customer
45
Memory alarm probe broken (analogic input
B9): Compressor Discharge Temperature
–
0
1
R
Customer
46
Memory alarm probe broken (analogic input
B10): Compressor Suction Temperature
–
0
1
R
Customer
47
Memory alarm probe broken (analogic input
B11): Compressor Discharge Pressure
–
0
1
R
Customer
48
Memory alarm probe broken (analogic input
B12): Compressor Suction Pressure
–
0
1
R
Customer
49…99
Reserved – (not used or other special appli-
cation or internal debug)
–
0
1
R
Only for Service/
Manufacturer
100
System reboot
–
0
1
R/W
Customer
101…207
Reserved – (not used or other special appli-
cation or internal debug)
–
0
1
R
Only for Service/
Manufacturer
Tab. 16:
LCP DX supervisory table – digital variables
BMS Ad-
dress
Description
UOM
Min
Max
Read/
Write
Note