17
Soloclim
GB
Maintenance
In case of malfunctioning, please refer to the following table. If, after performing the suggested
checks, the problem is not solved, please contact the authorised technical assistance.
An alarm code appears on the display in case of anomalies. Some of the functions
remain active nonetheless (see FUNCTIONING column).
The only way to solve the problem is to disconnect and
reconnect the appliance.If the alarm still appears, please
contact the authorised technical assistance.
* for DC Inverter models: lack of communication between the main, power, driver or display boards
Anomaly
Possible causes
Solution
The appliance
doesn't switch
on
No power supply
Check the voltage (by turning the light on, for example).
Check that the exclusive magneto-thermic switch that protects the appliance
hasn't intervened (if it has, reset it). If the problem repeats immediately, please
call the Service Centre and avoid trying to make the appliance work.
Batteries ran out
Check that the appliance can be turned on using the touch-screen display and
substitute the batteries.
The appliance
does not cool/
heat enough.
The temperature set is too high or too low.
Check and adjust the temperature on the remote
The air filter is clogged
Check the air filter and clean it if necessary
Check that there are no other obstacles of the
air flow both inside and outside.
Remove anything that might block the air flow.
The thermal refrigeration load has increased
(for example, a door or a window has been
left open or an appliance has been installed in
the room which generates a lot of heat).
Try to reduce the thermal refrigeration load of the room following instructions
below:
- Cover large windows exposed to sunlight with curtains or with external
maskings (blinds, porches, reflecting films, etc.).
- The room must remain closed for as long as possible.
- Avoid turning on halogen lamps or other high energy consumption
appliances such as small ovens, steam irons, cooking plates etc.
Alarm
Cause
Operation
E1
Broken room temperature RT
sensor
It is still possible to activate the Cooling, Dehumidification and Heating modes. It only monitors
the antifreeze function of the internal battery.
E2
Broken internal battery IPT sensor
None of the modes can be activated.
E3
Broken outside temperature OT
sensor
None of the modes can be activated.
E4
Broken outside battery OPT sensor
It is still possible to activate the Cooling, Dehumidification and Heating modes. Defrosting is
performed at fixed times.
E5
Broken internal fan motor
None of the modes can be activated.
E6
Broken external fan motor
None of the modes can be activated.
E7
Lack of communication with the
display *
None of the modes can be activated.
E8
Compressor discharge probe
failure *
None of the modes can be activated.
CP
Open CP contact
The appliance only works if the contact is closed. Check that the clamps are connected.
OF
Maximum level float intervention
During cooling and dehumidification, electronics switches the compressor off and keeps the
water distribution system active with the battery - together with the fan - to disperse excess
water in the container. During heating, condensations should drain freely through the specific
pipe. In the event of an alarm, check that the condensation pipe is not bent or obstructed, thus
preventing the water from flowing out.
Trouble shooting
Display alarms