RWB II PLUS MICROPROCESSOR CONTROL

OPERATION

S70-200 OM

Page 7

PRELUBEFULL LUBE, or CYCLING - Pump type will be
indicated.

PGM/ - Microprocessor Program version.

LIQ INJ CON - The Liquid Injection Control, reported in de-
grees Fahrenheit, will shut off the liquid refrigerant supply
to the compressor if the oil temperature equals or falls be-
low this setpoint.

FILTER - The Oil Filter setpoint will trigger an alarm when
the differential pressure across the oil filter equals or ex-
ceeds 25 pounds per square inch (PSI) for 15 seconds, or
longer.

OIL HEATER - The Oil Heater setpoint, reported in degrees
Fahrenheit, turns on the oil separator heater(s) when the oil
temperature equals or falls below this setpoint whenever
the compressor is NOT running.

Compressor Differential Cutout - The differential cutout
has been lowered from 55 lb to 25 lb. Cutout will occur after
five minutes.  To allow operation at low differential pressures,
the micro will take the following steps:

A. Force unload the compressor to 50% and display an "F
Unload" when the oil pressure is within 10 lb of the main oil
injection port pressure and the slide valve position is greater
than 50%.

B. Prohibit the compressor from loading and display a "Ld
Inhib" message when the differential is within 15 lb of the
main oil injection port pressure.

Oil Pressure Alarm and cutout - Logic has been revised
to same logic as currently used on RXB/RXF.  The new logic
is as follows:

Prelube and Cycling Oil Pump version when pump is not
running.  Alarm will occur if oil pressure is 25 lb below dis-
charge pressure or within 10 lb of suction pressure for 30
seconds.  Cutout occurs if oil pressure is 30 lb below dis-
charge pressure or if oil pressure is within 7 lb of suction
pressure for 10 seconds and alarm has already been set.

Full Lube and Cycling Oil Pump version when oil pump is
running.  Alarm occurs if oil pressure is within 10 lb of dis-
charge pressure for 30 seconds.  Cutout occurs when oil
pressure is within 5 lb of discharge pressure for 10 seconds
and oil pressure alarm has been set.

Cycling Oil Pump Control - The oil pump will cut off when
differential pressure between suction and discharge pres-
sure is 55 lb or greater.  Upon pump termination the above
cutout logic (pump not running) is utilized.  Pump cut-in oc-
curs when the differential pressure between suction and dis-
charge is 45 lb or less.  Oil pressure alarm and cutout logic
(pump running) begins after a 30 second delay which al-
lows the oil pump to build pressure.

HOW TO  DETERMINE

ADJUSTABLE SETPOINTS:

Adjustable Setpoints should reflect values compatible with
normal system operation. Too high a Low Suction Pressure
Alarm setpoint may cause nuisance prealarms. Similarly,
cutout setpoints should not fall within what are considered
normal plant operation. As a rule of thumb, set the Low Suc-
tion Pressure Alarm 5 PSIG lower than the lowest normal
suction pressure. The Low Suction Pressure Cutout should
be 5 to 10 PSIG lower than the Low Suction Pressure Alarm
setpoint.

The High Discharge Pressure Cutout should be set at 90%
of the setting of the lowest high side relief valve. The High
Discharge Pressure Alarm should be set 10 PSIG lower than
the Cutout.

The Capacity Control setpoint should be the equivalent of
the normal suction condition.

FIXED SETPOINTS DISPLAY *

  FIXED SETPOINTS:     HIGH STAGE PRELUBE
                         OIL PUMP PGM/A
  Hi Disch Cut----[212F]
  Hi Disch Alarm--[194F] Liq Inj Con 113F

  Hi Oil Temp Cut-[167F] Filter------[25]
  Hi Oil Temp Alarm[158F]Oil Heater[113F]
  Lo Oil Temp Cut--[49F] Lo Oil Cut-[030]
  Lo Oil Temp Alarm[58F] Lo Oil Alrm[025]

The Fixed Setpoints display lists all fixed setpoints, program
version, plus low oil alarm and low oil cutout setpoints.  Fixed
Setpoints define the limits of acceptable compressor opera-
tion. Fixed Setpoints are factory determined, stored in pro-
grammed memory (PROM), and will remain in memory if
power to the microprocessor is interrupted.

HI DISCH CUT - The High Discharge Temperature Cutout,
reported in degrees Fahrenheit, will shut down the com-
pressor if the discharge temperature equals or exceeds this
setpoint.

HI DISCH ALARM - The High Discharge Temperature Alarm,
reported in degrees Fahrenheit, will trigger a prealarm if the
discharge temperature equals or exceeds  this setpoint.

HI OIL TEMP CUT - The High Oil Temperature Cutout, re-
ported in degrees Fahrenheit, will shut down the compressor
if the oil temperature equals or exceeds this setpoint.

HI OIL TEMP ALARM  -  The High Oil Temperature Alarm,
reported in degrees Fahrenheit, will trigger a prealarm if the
oil temperature equals or exceeds this setpoint.

LOW OIL TEMP CUT - The Low Oil Temperature Cutout,
reported in degrees Fahrenheit, will shut down the com-
pressor if the separator oil temperature equals or falls be-
low this setpoint.

LOW OIL TEMP ALARM  -  The Low Oil Temperature Alarm,
reported in degrees Fahrenheit, will trigger a prealarm if the
separator oil temperature equals or falls below this setpoint.

HIGH STAGE or BOOSTER - Compressor application indi-
cator.

 *Display for illustrative purposes only.

Содержание RWB II Plus

Страница 1: ...OPERATION MAINTENANCE MICROPROCESSOR CONTROL S70 200 OM DEC 99 File SERVICE MANUAL Section 70 Replaces S70 200 OM MAR 99 Dist 3 3a 3b 3c...

Страница 2: ...D PROGRAMMABLE CONTROLLER PROGRAM TO DECODE MICROPROCESSOR OUTPUT DATA CODES 14 MICROPROCESSOR OUTPUT DATA CODE 15 MICROPROCESSOR TELECOMMUNICATIONS 16 COMMUNICATIONS PROTOCOL SPECIFICATIONS 16 TROUBL...

Страница 3: ...the keyboard in the area outlined as a key will cause that function to be recognized by the microprocessor The keyboard has 32 membrane type keys In addition to the keyboard there is an emergency stop...

Страница 4: ...liquid crystal displays in an 8 line by 40 character format for a total of 320 characters There are 9 different display modes When power is first applied to the control panel the unit will be in the...

Страница 5: ...x pires and is intended to prevent damage to the compressor motor from successive restarts During Recycle Delay the microprocessor will alternatively flash RECYCLE DELAY and the remaining delay time i...

Страница 6: ...flashing brack ets will move or step to the next setpoint NOTE A setpoint entry outside the parameters of the Adjustable Setpoint display will be refused and the origi nal Adjustable setpoint will be...

Страница 7: ...nning begins after a 30 second delay which al lows the oil pump to build pressure HOW TO DETERMINE ADJUSTABLE SETPOINTS Adjustable Setpoints should reflect values compatible with normal system operati...

Страница 8: ...tpoints SHUTDOWN RECORD DISPLAY SHUTDOWN RECORD Thu 10 01 87 15 33 36 Use STEP key to advance PAGE Hi Oil Temp Cutout Wed 09 30 87 16 22 54 Comp Auxiliary Sat 08 22 87 09 47 02 Low Temp Cutout Thu 08...

Страница 9: ...Stop Start Stop Mon 06 00 Fri 16 00 Tue Sat Wed Sun Thu The F3 function key will call up the Setback display The Setback feature enables automatic operation at two sepa rate suction conditions on a p...

Страница 10: ...setpoints press for pressure capac ity control and temp for temperature capacity control CC The capacity control setpoint is for normal operation not setback CUTOUT This setpoint will stop the compres...

Страница 11: ...er 00 min Min SV 50 Active No for Temp Menu NOTE To change the Auto Cycle setpoints refer to TO CHANGE THE ADJUSTABLE SETPOINTS SUCTION PRESSURE Constantly monitors and displays the suction pressure i...

Страница 12: ...ust be less than or equal to the STOP setpoint in order to stop the compressor This setpoint works in conjunction with the Timer setpoint lo cated to the right of it on the Auto Cycle setpoints screen...

Страница 13: ...rted into binary code which the microprocessor understands The microprocessor scans the incoming data many times per second and compares the information it receives with the instructions programmed in...

Страница 14: ...mperature and reporting this information on the Operating display AT 158O F The microprocessor triggers the High Oil Temperature Alarm and displays the alarm on the Operating display and the Annunciat...

Страница 15: ...troller or Frick can supply this sequencer if desired contact Frick Company for pricing MASTER SEQUENCE CONTROLLER USUALLY PROGRAMMABLE CONTROLLER I O TYPICAL FOR EACH COMPRESSOR RWB II COMPRESSOR WIT...

Страница 16: ...pressor ID code I Return Status information command RETURNED ANSWER ie 090RRRN340 Character Description Position of returned data 1 2 3 Slide valve position 4 Remote Auto Manual slide valve 5 Delay re...

Страница 17: ...01A Start command sequence 01 Compressor ID code A Return full load amps command If the command was 01A then the micro processor would dump the full load amps value RETURNED ANSWER XXX 3 characters f...

Страница 18: ...oint y g or h for gauge or inches The following is the complete list of the setpoints that may be changed while in the change setpoints command 01xxxy Capacity Control Setpoint y deleted for KpaA BarA...

Страница 19: ...COMMAND Start command sequence ID Compressor ID code C Change setpoint command x numeric datum field y g or h for gauge or inches datum field or Sign datum field Command Prefix IDC datumID datum Desc...

Страница 20: ...other electromechanical functions The 0 15 volt DC side operates the computer and its various sensors The microprocessor console contains the SBC single board computer and two display screens When wo...

Страница 21: ...t the Oil Heater Relay is defective If you do not read 120VAC between Wires 9 and 2 when the LED for output 10 is on check the fuse FU10 SLIDE VALVE DOES NOT LOAD Verify that the Slide Valve is in the...

Страница 22: ...ditions are found check for 120VAC across Wires 10 and 2 If 120VAC is not found check the fuse FU9 CONTROL PANEL DOES NOT Inputs 2 through 4 can be used to operate the compressor from a remote RESPOND...

Страница 23: ...the oil pres sure transducer PE 1 and then open the vent valve which exposes the transducer to atmosphere 5 Once the time delays have expired 30 seconds for the alarm and an additional 10 seconds for...

Страница 24: ...ick Service for confirmation Dirty Filter 1 Push the key and record the Oil Pressure value from the analog offset display Example 2 2 With the machine running and maintaining good pres sures and tempe...

Страница 25: ...on the replacement board in exactly the same position as they were on the defective board 4 IMPORTANT Before installing the new board determine if there are gray yellow wires from P15 see the SBC wir...

Страница 26: ...L LEVEL SWITCH REMOTE RUN REMOTE LOAD REMOTE UNLOAD COMPRESSOR AUX COMPRESSOR START RELAY OIL PUMP SEL SW AUX 2 POWER POWER DATA BIT 0 DATA BIT 1 DATA BIT 2 DATA BIT 3 OIL HEATER RELAY OIL PUMP SEL SW...

Страница 27: ...13 GND 230 NEU 115 F1 1 P15 P10 BAT BATTERY 2 PORT OFF ON DIG I O EXPANSION 34 FUSES FU1 FU16 DIGITAL OUTPUT 16 DIG I O TERMS 17 MODULES MODULES 35 48 P6 PORT 1 3 U5 U4 C T SBC POWER SUPPLY WIRING 1A...

Страница 28: ...RATED FROM OTHER INDUCTIVE LOADS SUCH AS LIGHTING CIRCUITS OR FROM FRICK SUPPLIED OR SPECIFIED STARTER USE MINIMUM 12 AWG FOR FEED RED 25B 12 18 17 16 15 14 13 FU10 FU7 FU8 32 8 31 FU9 34 9 36 10 33 3...

Страница 29: ...OIL PUMP STARTER OL NEU OL NEU INDICATES DEVICES SUPPLIED ONLY WHEN OPTIONAL OR REQUIRED WIRING BY OTHERS ALL WIRING ENTERING CONTROL CENTER INCLUDING GROUND NEUTRAL TO BE 14 AWG STRANDED WIRES UNLESS...