FR500F Series Special Purpose Inverter
- 27 -
value under torque control
F10.19
Reverse speed limited
value under torque contro
0.00
~
Fmax
50.00Hz
△
F10.20
Set torque accel time
0.0
~
6000.0s
0.0s
△
F10.21
Set torque decel time
0.0
~
6000.0s
0.0s
△
F10.22
Static friction torque
compensation
0.0
~
100.0%
5.00%
△
F10.23
Static friction frequency
range
0.00
~
20.00Hz
1.00Hz
△
F10.24
Sliding friction torque
compensation
0.0
~
100.0%
1.0%
△
F10.25
SVC optimization mode
0: Optimization mode 0
1: Optimization mode 1
2: Optimization mode 2
1
×
F10.26
Max Frequency source
under torque control
0: Set by F10.18 & F10.19
0
×
1:Keypad potentiometer
2:AI1
3:AI2
4:AI3
5: Pulse setting ( DI7/HI )
Group F11 Protection Parameters
F11.00
Current limit control
0: Current limit disabled
2
×
1: Current limit mode 1
2: Current limit mode 2
F11.01
Current limit
100.0
~
200.0%
150.0%
×
F11.02
Frequency decreasing
time(limit current in
constant speed operation)
0.0
~
6000.0s
5.0s
△
F11.03
Current limit mode 2
proportion gain
0.1
~
100.0%
3.0%
△
F11.04
Current limit mode 2
integral time
0.000
~
1.000s
0.010s
△
F11.05
Overvoltage Stall Control
0: Overvoltage stall disabled
1
×
1: Overvoltage stall mode 1
2: Overvoltage stall mode 2
F11.06
Overvoltage Stall
Voltage
120.0
~
150.0%
130.0%
×
F11.07
Overvoltage Stall
Mode 2 Proportion Gain
0.1
~
100.0%
3.0%
△
F11.08
Overvoltage stall mode 2
frequency limit
0.00
~
50.00Hz
5.00Hz
×
F11.10
Protection action 1
Unit's place: Bus undervoltage
00330
×
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continue to
run
3: Fault protection disabled
Ten's place: Power input phase
Loss (Err09)(Same as unit's
place )
Hundred's place: Power output
phase loss(Err10)(Same as unit's
place )
Thousand's place: Motor overload
(Err11)(Same as unit's place )
Ten thousand's place: Inverter