FR500F Series Special Purpose Inverter
- 28 -
overload(Err11)(Same as unit's
place )
F11.11
Protection action 2
External equipment fault
(
Err13)
00000
×
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continue to
run
Ten's place: EEPROM read/write
fault (Err15) (Same as unit's place)
Hundred's place: Communication
overtime error (Err18) (Same as
unit's place)
Thousand's place: PID feedback
loss (Err19) (Same as unit's place)
Ten thousand's place: Continuous
running time reached (Err20)
(Same as unit's place)
F11.12
Protection action 3
Unit's place: Module temperature
detection disconnection
(
Err24)
00030
×
0: Fault reported and coast to stop
1: Stop according to the stop mode
2: Fault reported but continue to
run
Ten's place: Load becoming 0
(Err25) (Same as unit's place)
F11.14
Frequency selection for
continuing to run upon
fault
0: Current running frequency
0
×
1: Set frequency
2: Frequency upper limit
3: Frequency lower limit
4: Backup frequency upon
abnormality
F11.15
Backup frequency upon
abnormality
0.00
~
Fmax
0.00Hz
×
F11.17
Motor overload protection
time
30.0
~
300.0s
60.0s
×
F11.18
Overload alarm
Unit's place: detection option:
0: Always detect
1: Detect at constant speed only
00
×
Ten's place : compared object
0: Rated current of motor
1: Rated current of drive
Hundred’s place: Fault reported
0:No fault reported
1:Fault reported
Thousand’s place: whether to
decelerate or not when overload
alarm
0: No deceleration
1: Deceleration
Ten thousand’s place: Overload
level given mode
0:F11.19 set
1:VP*F11.19
2:AI1*F11.19
3:AI2*F11.19
4:AI3*F11.19