FR500F Series Special Purpose Inverter
- 17 -
defined
F00.24
Dealer password
0
~
65535
0
×
F00.25
Setting operation time
0
~
65535h(0: Invaild)
0h
×
Group F00: Frequency Command
F01.00
Frequency source
selection
0: Master frequency source
0
×
1: Auxiliary frequency source
2: Auxiliary
3: Master - Auxiliary
4: MAX{Master, Auxiliary }
5: MIN {Master, Auxiliary }
6: AI1( Auxiliary)
7: AI2( Auxiliary)
F01.01
Master Frequency
Command Source
0:Master digital setting (F01.02)
1
×
1: keypad potentiometer
2: Analog input AI1
3: Communication
4: Multi-reference
5: PLC
6: Process PID output
7: X7/HI pulse input
8:AI2
9:AI3
F01.02
Digital Setting of Master
Frequency
0.00
~
Fmax
0.00Hz
△
F01.03
Auxiliary Frequency
Command Source
0: Auxiliary digital setting
(F01.04)
0
×
1: keypad potentiometer
2: Analog input AI1
3: Communication
4: Multi-reference
5: PLC
6: Process PID output
7: X7/HI pulse input
8: Analog input AI2
9: Analog input AI3
F01.04
Digital setting of
auxiliary frequency
0.00
~
Fmax
0.00Hz
△
F01.05
Range of auxiliary
frequency
0: Relative to maximum frequency
0
×
1: Relative to master frequency
F01.06
Coeff of auxiliary
frequency
0.0
~
150.0%
100.0%
△
F01.07
Jog frequency
0.00
~
Fmax
5.00Hz
△
F01.08
Maximum frequency
20.00
~
600.00Hz
50.00Hz
×
F01.09
Upper limit frequency
Fdown
~
Fmax
Lower limit frequency
~
maximum
frequency
50.00Hz
×
F01.10
Lower limit frequency
0.00
~
Fup
0.00Hz
×
F01.11
Operation when command
frequency lower than lower
limit frequency
0: Run at lower limit frequency
0
×
1: Run at 0 Hz would be activated
after the time delay set by F01.12
F01.12
Lower limit frequency
running time
0.0
~
6000.0s
60.0s
×
F01.13
Up to this frequency, start
frequency compensation
0.00~600.00Hz
50.00Hz
△