FR500F Series Special Purpose Inverter
- 16 -
2: Editable via RS485
F00.08
Motor 1 control mode
0: Voltage/Frequency (V/F)
control
1
×
1:Sensor-less vector control 1
2: Sensor-less vector control 2
F00.09
DI7/HI input mode
0: Digital input terminal 7
0
×
1: Pulse input
F00.10
AI1\AI2\AI3 input mode
Unit's place: AI1
000
×
0: Analog input
1: Digital input
Ten’s place: AI2 (same as AI1)
Hundred’s place: AI3 (same as AI1)
F00.11
Y2/HO input mode
0: Digital 0utput terminal 2
0
×
1: Pulse output
F00.12
PWM optimization
Unit's place: PWM modulation
mode
0: Fixed carrier
1: Random carrier
2: Derating of fixed carrier
3: Derating of random carrier
000
×
Ten’s place: PWM modulation
mode
0: Seven-segment mode
1: Five-segment mode
2: Five-segment and
seven-segment automatic
switchover
Hundred’s place: over-modulation
coefficient
0: Invalid
1~9:
1.01~1.09
times
of
over-modulation
F00.13
Carrier frequency
0.700
~
16.000kHz
Model
defined
△
F00.14
Upper carrier
frequency
0.700
~
16.000kHz
8.000kHz
×
F00.15
Lower carrier
frequency
0.700
~
16.000kHz
2.000kHz
×
F00.16
Output voltage
5.0
~
150.0%
100.0%
×
F00.17
AVR
0: Disabled
0
×
1: Enabled
2: AVR is disabled if the DC
bus voltage > the rated
voltage of DC bus, and it will be
enabled if the DC bus voltage≤the
rated voltage of DC bus.
F00.18
Fan control
0: Run at power-on
1
×
1: Fan working during running
F00.19
Factory password
0
~
65535
0
×
F00.20
Inverter rated power
0.2
~
710.0kW
Model
defined
⊙
F00.21
Inverter rated voltage
60
~
660V
Model
defined
⊙
F00.22
Inverter rated current
0.1
~
1500.0A
Model
defined
⊙
F00.23
Software version
0.00
~
655.35
Model
⊙