FR500F Series Special Purpose Inverter
- 29 -
F11.19
Overload alarm threshold
20.0
~
200.0%
130.0%
×
F11.20
Overload alarm
activated time that
exceeding threshold
0.1
~
60.0s
5.0s
×
F11.21
Inverter overheat warning
threshold
50
~
overheat Temperature
Model
defined
×
F11.22
Detection level of power
loss
5.0
~
100.0%
20.0%
×
F11.23
Detection time of power
loss
0.1
~
60.0s
5.0s
×
F11.24
Action selection at
instantaneous power
failure
0: Disabled
1
×
1: Enabled
F11.25
Decel time at
instantaneous power
failure
0.0
~
6000.0s
5.0s
△
F11.26
Rapid current limit
0: Disabled
0
×
1: Enabled
F11.27
Times of automatic
reset
0
~
20
0
×
F11.28
Interval of automatic
reset
0.1
~
100.0s
1.0s
×
F11.29
DO action during fault auto
reset
0: Not act
0
×
1: Act
F11.30
Instantaneous power
off bus voltage
60.0%
~
Recovery voltage
80.0%
△
F11.31
Instantaneous power off
recovery voltage
Power off voltage
~
100.0%
85.0%
△
F11.32
Instantaneous power off
voltage detection time
0.01
~
10.00s
0.10s
△
F11.33
Instantaneous power off
Kp
0.1
~
100.0%
40.0%
△
F11.34
Instantaneous power off
integration time Ti
0.00
~
10.00s
(
0.00:Integration
invalid
)
0.10s
△
F11.35
Motor temperature sensor
type
0:None
1:PT100
2:PT1000
3:KTY84
0
×
F11.36
Zero drift value of motor
temperature sensor
-100
~
100
℃
0
△
F11.37
Reserved
F11.38
Motor temperature
warning action threshold
0
~
200
℃
90
℃
△
F11.39
Motor temperature
protection action threshold
0
~
200
℃
110
℃
△
Group F12: Multi-Reference and Simple PLC Function
F12.00
Reference 0
-100.0
~
100.0%
0.0%
△
F12.01
Reference 1
-100.0
~
100.0%
0.0%
△
F12.02
Reference 2
-100.0
~
100.0%
0.0%
△
F12.03
Reference 3
-100.0
~
100.0%
0.0%
△
F12.04
Reference 4
-100.0
~
100.0%
0.0%
△
F12.05
Reference 5
-100.0
~
100.0%
0.0%
△
F12.06
Reference 6
-100.0
~
100.0%
0.0%
△
F12.07
Reference 7
-100.0
~
100.0%
0.0%
△