INSTALLATION

Physical Installation

3

INSTALLATION

Physical Installation

1.

Install the pump on a flat surface.

Make sure the mounting surface will support the combined weight of the pump and water filled 
tank. 

The air vent openings around the motor housing must not be blocked or obstructed to allow the 
free flow of air. 

Ensure that the pump is level and the inlet is below the coil drain.

Piping Connections

Connect inlet and outlet tubing as follows:
1.

Cut end of pipe from evaporator drain at a 45° angle as 
shown to prevent pipe from sealing closed when sitting 
against the tank’s floor.

2. Route drain pipe downward into pump inlet opening. 

For plenum applications, use metal tubing such as 
copper, from evaporator.

3. Install outlet piping onto outlet check valve and secure 

with hose clamp (not provided). 

Use 3/8” inside diameter maximum tubing or piping 
to prevent excessive flow back to unit.

For plenum applications, use metal tubing such as copper.

Replace plastic check valve with brass check valve, Part Number 599063 (purchased separately).

NOTE:

 Thread sealant must be used when using the brass check valve.

4. Route outlet piping from pump straight up as high as necessary.

Do not extend higher than 75% of the total dynamic head capacity of the pump.

5. From the high point, slope discharge line down slightly to a point above the drain area. Then, turn down 

and route to a suitable drain at a point below or approximately level with the bottom of the pump, if 
possible. This will produce a siphoning effect which will improve efficiency of the pump.

6. If it is not possible to slope the discharge line down, make an inverted “U” trap directly above the pump 

at the highest point.

Electrical Connections

The pump has individual power conductors for making a hardwire connection to the power supply. It does 
not have a power cord or electrical plug. The power conductors must be connected to a constant source of 
power matching the voltage specified on the pump nameplate.

The pump should be connected or wired to its own circuit, with no other electric receptacles or equip

-

ment in the circuit. Do not connect to a fan or any device that runs intermittently.

The fuses or circuit breaker should be of ample capacity in the electrical circuit.

Connect to a circuit equipped with a ground fault circuit interrupter (GFCI) device if required by code.

Power connections must be made within a junction box, and must comply with the National Electrical Code. 
Wires are color coded as follows: 

Green/yellow = Ground;  Brown = Line;  Blue = Line (230 V) or Neutral (115 V)

Risk of damage to pump or other equipment.

There is a plastic plug inserted in the inlet opening beneath the conduit connector. Do not remove 
this plug and do not use this inlet opening.

Содержание Little Giant VCC-20-P

Страница 1: ...75 20 6 1 m VCC 20 P 230 50 60 0 6 0 5 58 60 17 5 2 m SAFETY INSTRUCTIONS Before Getting Started This equipment should be installed and serviced by technically qualified personnel who are familiar wi...

Страница 2: ...cord The pump should only be used with liquids compatible with pump component materials If the pump is used with liquids incompatible with the pump components theliquid can cause failure to the electr...

Страница 3: ...high point slope discharge line down slightly to a point above the drain area Then turn down and route to a suitable drain at a point below or approximately level with the bottom of the pump if possi...

Страница 4: ...al forexpected switch operationand wiring connections Connect the switch leads 7 in series with the low voltage thermostat circuit as specified in the heating cooling unit s operating manual 2 The ins...

Страница 5: ...down when float is raised If wired to NC terminal external component alarm or relay should activate when float is raised 6 Disconnect the pump from the power source 7 Replace the tank cover assembly...

Страница 6: ...rate correctly Check valve stuck or plugged Remove check valve and inspect for proper operation Outlet flow is blocked Check outlet tubing to ensure that it is not kinked or blocked Clear blocked tubi...

Страница 7: ...os Vatios Apagado VCC 20 P 115 60 1 5 75 20 6 1 m VCC 20 P 230 50 60 0 6 0 5 58 60 17 5 2 m INSTRUCCIONES SOBRE SEGURIDAD Antes de empezar La instalaci n y el mantenimiento de este equipo deben estar...

Страница 8: ...No use un prolongador La bomba solo se debe utilizar con l quidos compatibles con los materiales que componen la bomba Si la bomba se utiliza con l quidos incompatibles con los componentes de la bomb...

Страница 9: ...como sea necesario No extienda m s alto que un 75 la capacidad de la carga gal h de la bomba 5 Desde el punto alto baje la l nea de descarga ligeramente hasta un punto encima del rea del drenaje Lueg...

Страница 10: ...cables del interruptor 7 en serie con el circuito del termostato de vol taje bajo seg n se especifica en la manual operativo de unidad de calefacci n refrigeraci n 2 El instalador puede reconfigurar...

Страница 11: ...aire debe apagarse cuando se eleva el flotador Si est cableado al terminal NC el componente externo alarma o rel debe activarse cuando se eleva el flotador 6 Desconecte la bomba de la fuente de alime...

Страница 12: ...est bloqueado Verifique la tuber a de salida para asegurarse de que no est retorcida ni bloqueada Despeje la tuber a bloqueada de lodo y residuos Limpie la tuber a de entrada y de salida El impulsor d...

Страница 13: ...6 0 5 58 60 17 5 2 m CONSIGNES DE S CURIT Avant de commencer Cet quipement doit tre install et entretenu par des techniciens qualifi s capables de choisir et d utiliser les outils les quipements et l...

Страница 14: ...osants Si la pompe est utilis e avec des liquides incompatibles avec les composants de la pompe le liquide peut provoquer une d faillance du syst me d isolation lectrique entra nant un choc lectrique...

Страница 15: ...Ne pas d passer 75 de la charge hydraulique gal h de la pompe 5 partir du point le plus haut inclinez l g rement le tuyau de refoulement vers le bas jusqu un point au dessus de la zone d coulement En...

Страница 16: ...n comme indiqu dans le manuel de l unit de chauffage refroidissement 2 L installateur peut reconfigurer cet interrupteur la borne NF pour fermer un circuit basse tension en cas de niveau d eau lev afi...

Страница 17: ...enir niveau 3 Mettre la pompe sous tension 4 Tester l interrupteur de fonctionnement de la pompe en faisant mon ter le flotteur Le moteur devrait d marrer avant que le flotteur de l interrupteur ne to...

Страница 18: ...assurer que le conden sat r siduel ne cr e pas de poches d acide localis es qui pourraient causer des piq res 6 V rifier les tuyaux d aspiration et de refoulement Nettoyer au besoin V rifier l absenc...

Страница 19: ...lle n est pas cou d e ou obstru e Nettoyez la boue et les d bris de tout tuyau obstru Net toyez la tuyauterie d entr e et de sortie La roue de la pompe ne tourne pas Nettoyez toute obstruction dans le...

Страница 20: ...ic Co Inc Oklahoma City OK 73157 2010 800 701 7894 littlegiant com Pour l aide technique entrez s il vous pla t en contact Form 998922 R v 003 06 19 Droits d auteur 2019 Franklin Electric Co Inc Tous...

Отзывы: