11. Additional Settings for the Urinal
☞
These additional settings only apply for concealed urinal fittings operating on the mains.
Switching preliminary flushing on/off
☞
The preliminary flushing is switched off at the factory.
11.1
Press and hold the TEST key.
11.2
Press the
ON key within 2 s.
• The LED in the sensor of the fitting flashes:
– 4 x short: Preliminary flushing is switched on.
– 2 × long: Preliminary flushing is switched off.
11.3
Exit the adjustment mode.
• Press the TEST key.
or wait
• 60 s.
Switching intermediate flushing on/off
☞
Intermediate flushing is factory-set to ON.
11.4
Press and hold the TEST key.
11.5
Press the
OFF key within 2 s.
• The LED in the sensor of the fitting flashes:
– 4 x short: Intermediate flushing is switched on.
– 2 × long: Intermediate flushing is switched off.
11.6
Exit the adjustment mode.
• Press the TEST key.
or wait
• 60 s.
Setting the minimum retention time
☞
The minimum retention time is factory-set to 7 s.
11.7
Press and hold the TEST key.
11.8
Use the + and – (
) keys to adjust the minimum retention time in individual steps.
• The LED in the sensor of the fitting flashes:
– 4 × short for each adjustment by one step (approx. 1 s)
– 2 x long when the respective end setting is reached
11.9
Exit the adjustment mode.
• Press the TEST key.
or wait
• 60 s.