![background image](http://html1.mh-extra.com/html/franke/2000101087/2000101087_installation-and-operating-instructions-manual_2327839017.webp)
17
ZMI
_001_
2000
1010
87-ZAQ
U
A09
1_#S
EN_#A
QU_#V
5.f
m
Hygiene Mode
Start hygiene flushing
11.6
Press the TEST key.
• The LED flashes 4 × briefly.
• The fitting goes into Hygiene Mode.
• The LED flashes at 1 second intervals.
11.7
Press the
ON key.
• Water flows for the set flushing duration.
Setting the Flushing Interval
11.8
Press the TEST key.
• The LED flashes 4 × briefly.
• The fitting goes into Hygiene Mode.
• The LED flashes at 1 second intervals.
11.9
Use the + and – (
) keys to adjust the flushing interval in individual steps.
• The LED in the sensor of the fitting flashes:
Setting the Flushing Time
11.10
Press the TEST key.
• The LED flashes 4 × briefly.
• The fitting goes into Hygiene Mode.
• The LED flashes at 1 second intervals.
11.11
Use the + and – (
) keys to adjust the flushing duration in individual steps.
• The LED in the sensor of the fitting flashes:
– 1 x short = Hygiene flushing off
– 2 × short = 2 h
– 5 × short = 24 h
– 3 × short = 8 h
– 6 × short = 48 h
– 4 × short = 12 h
– 7 × short = 72 h
☞
The flushing interval is factory-set to 24 h.
– 1 × short = 10 s
– 5 × short = 3 min
– 2 × short = 30 s
– 6 × short = 5 min
– 3 × short = 1 min
– 7 × short = 7 min
– 4 × short = 2 min
– 8 × short = 10 min
☞
The flushing duration is factory-set to 10s.