____________________________________________________________________________ 6NT 1965 A - 03/2019
Power Box Ready, size 3000
X = Distance to be left for removing the exchanger and filters
Size
A (mm)
B (mm)
C (mm)
T (mm)
U (mm)
X (mm)
Weight (kg)*
3000
1650
2240
660
583
599
575
309
* Maximum weight of the recovery unit with accessories
3.2
ELECTRICAL SPECIFICATIONS
3.2.1
POWER BOX READY WITHOUT HEATERS
Size
Power supply
Frequency
Power [kW] (1)
Total current [A] per
phase (2)
600
Single-phase 230V
50 Hz
344
1.5
1000
Single-phase 230V
50 Hz
460
2
2000
Single-phase 230V
50 Hz
1020
4.43
3000
Single-phase 230V
50 Hz
2752
11.96
(1)
Maximum consumed by the complete recovery unit.
(2)
Maximum current calculated based on the measured power.
3.2.2
POWER BOX READY WITH ELECTRIC HEATER
Model
Power supply (3) (4)
Frequency
Power [W] (1)
Total current [A] per
phase (2)
600
Single-phase 230V
50 Hz
3344
14.54
1000
Single-phase 230V
50 Hz
3460
15.05
2000
Three-phase 400 V + N
50 Hz
5520
8.75
3200
Three-phase 400 V + N
50 Hz
7252
12.5
(1)
Maximum consumed by the complete recovery unit.
(2)
Maximum current calculated based on the measured power.
(3)
The heating resistors are always supplied with 230V irrespective of the 230V/400V indication in the "Power supply" column
(4)
The TRI power supply must have a neutral.