___________________________________________________________________________ 10NT 1965 A - 03/2019
Supply to L1, L2, L3 and N. Do not forget the connection to earth (PE).
NB
: the neutral connection is required to guarantee the operation of the control
components.
5.2
CONNECTION OF ACCESSORIES
5.2.1
REMOTE CONTROL
At the time of delivery, the remote control box is located in one of the machine tappings.
The product cannot operate
if the remote control is not connected
.
Connect the remote control to the control board located in the electrical cabinet, in accordance with the diagram
below:
To order cables that are longer than those supplied with the appliance, consult the France Air catalogue.
5.2.2
CIREC ELECTRIC PREHEATER
Range of CIREC circular electric heaters. Duct heating with single-phase or three-phase supply
(depending on the product and 0-10V DC control voltage).
The dimension of the supply cable must be selected based on the heating output and the installation
conditions. Refer to the CIREC manual.
Control cable. Cable with two conductors with min. diameter 0.5 mm2. Maximum length 50 m.
The 0-10 V input must always be connected between terminals 7 and 8. With this control method, all the control
elements of the controller (MIN, MAX, SET-P) are out of use.
Connection
7: AO2 right
8: AO2 left