___________________________________________________________________________ NT 1965 A - 03/201941
13.3
REPLACING THE FAN
Open the fan access door (side doors) by releasing the closing latches using an Allen key (for hexagon socket bolts).
Remove the connection block located behind the motor by undoing the mounting bolts. The fan is attached to the
panel by an assembly of four specific support arms. To remove the fan from the recovery unit, undo the mounting
bolts on the support arms using a spanner (flat, ring, pipe, etc.). Then release the assembly of four fan support arms.
Replace the fan or perform the maintenance operation. Refit the fan using the same support system and connect it
using the connection block.
13.4
VENTILATION UNIT CLEANING INTERVALS
TECHNICAL ASSISTANCE
•
3 mm Allen key
•
vacuum cleaner
•
brush
•
cloth
•
neutral cleaning product (soapy water)
We recommend checking the ventilation unit and cleaning it every six months, but the intervals can be changed at
any time according to the local usage conditions. We recommend that the unit undergoes a complete clean each
year.
If the ventilation unit is not used for a long period of time, we recommend operating it for one hour every six months.
Unscrew the inspection cover(s). Check the weight of the inspection cover before removing it, in order to avoid injuries
caused by dropping it unexpectedly.
Clean the ventilation unit using a vacuum cleaner, brush, cloth and soapy water. To clean the ventilation unit, avoid
using sharp objects, aggressive chemical products, thinners, abrasive cleaning products, pressurised water,
compressed air or steam.