ACCESS LEVELS
There are four different access levels: user, maintenance, installer and manufacturer. There is also a menu for alarm
management as well as a history menu.
6.4
GENERAL MENU
The general menu provides access to the other system menus. It can be accessed by pressing and holding the ENTER
button for two seconds.
To select a menu, use the UP, DOWN and ENTER buttons
Press ESC on this page to return to the main page of the application.
6.5
USER MENU
The user menu allows you to change the following parameters:
•
Winter supply setpoint (W, parameter SPHM)
•
Summer supply setpoint (S, parameter SPCM)
•
Winter return setpoint (W, parameter SPHR)
•
Summer return setpoint (S parameter SPCR)
•
Season mode: manual/summer/winter (Mode parameter)
•
Manual speed (PF02)
This menu can be accessed if the appliance is in manual, summer or winter mode.
In automatic mode, the engine speed is pre-adjusted and modifiable via the installer menu (see 6.7 Menu Installateur,
page 18).
It is possible to change the password of the user menu (PSd1) by pressing on the RIGHT button.