________________________________________________________________________________________________________________________ 28NT 1965 A - 03/2019
Code
Parameter description
Default
Min
Max
UM
Menu
Note
PT02
Start of the ECONOMY time slot
20:00:00
00:00:00
23:59:59
-
OR
PT11
Sunday
0 worked
0 worked
1 open
-
OR
PT12
Monday
0 worked
0 worked
1 open
-
OR
PT13
Tuesday
0 worked
0 worked
1 open
-
OR
PT14
Wednesday
0 worked
0 worked
1 open
-
OR
PT15
Thursday
0 worked
0 worked
1 open
-
OR
PT16
Friday
0 worked
0 worked
1 open
-
OR
PT17
Saturday
0 worked
0 worked
1 open
-
OR
FANS
PF01
Fan setting type:
0: Manual
1: Automatic
2: Automatic with presence sensor
3: On CO2 sensor
0
0
3
IS-F
Depending on model
PF03
Fan speed in COMFORT slot
V2
V1
V3
IS-F
PF04
Fan speed in ECONOMY slot
V1
V0
V2
IS-F
PF05
Fan speed with incorrect RTC
V0
V0
V3
IS-F
Only if PF01=1/2/3
PF12
Speed of fans with active engagement of the presence sensor
V3
V1
V3
IS-F
PF13
Speed for non-worked day
V0
V0
V3
IS-F
PF27
BOOST operating duration
5
0
600
Min
IS-F
PF30
Activation of night-time ventilation
Yes (1)
No (0)
Yes (1)
-
IS-F
PF31
Speed for night-time ventilation
V3
V0
V3
IS-F
Only if PF30 = 1
PF32
Activation of morning soft start
No (0)
No (0)
Yes (1)
-
IS-F
PF33
Speed for morning soft start
V3
V0
V3
IS-F
Only if PF32 = 1
PF34
Duration of morning soft start
10
0
60
Min
IS-F
PF36
Speed for boost via button
V3
V0
V3
IS-F
Only if PF35 = 2
PF39
Activation of air flow rate offsetting
No (0)
No (0)
Yes (1)
IS -F
PF40
Speed difference for air flow rate offsetting
0
-2
+2
IS-F
SENSORS
Pb01
Heating adjustment sensor:
0: Supply air sensor
1: Return air sensor
0
0
1
IS-P