___________________________________________________________________________ 18NT 1965 A - 03/2019
Press on “
Update
” to automatically set the old date to the current date, thus updating the parameter.
6.6.1.4
Page 4 - Delete history (PH18)
From the
Maintenance
menu, press on RIGHT until the following screen is displayed:
With parameter
PH18
, you can delete the history of all the stored elements; set the parameter to YES (1)
and wait for two seconds until the default value NO (0) is displayed again.
6.6.2
INPUTS/ OUTPUTS
This menu allows you to view the status of the corresponding sensor inputs.
6.6.3
FORCING
The FORCING menu enables you to force values considered as analogue and digital inputs. It also allows you to force
the value of the analogue and digital outputs.
Select the values to be considered by using the UP, DOWN and ENTER buttons.
Column ‘F’ indicates whether value forcing is active (Y) or not (N).
6.6.4
PROJECT INFO
The
PROJECT INFO
menu provides a variety of information such as the name of the appliance or the program version.
6.6.5
LAYOUT DIAGRAM
The
LAYOUT DIAGRAM
menu groups together the different air specifications and appliance specifications in graphical
form
The following are displayed:
•
The temperatures of the intake, supply, return and discharge air
•
The speeds of the supply and return fans (S and R)
•
The efficiency of the thermal exchange in the exchanger (EFF)
•
The power of the electric heater (P)
•
The status of the machine: On or off (M/A)
•
The status of the by-pass valve: ON or OFF (ByP)
6.7
INSTALLER MENU
The installer menu is a level 3 menu, which means an installer level password must be entered (1616) to view/change
the parameters in this menu.