FPI FP90 Wood Fireplace

13

INST

ALLA

TION

There is also 1" unit base standoffs that are 
supplied with the unit. These are optional and 
are to be used to raise the unit. The thickness 
of the fi nished hearth will dictate the height of 
the stove. Please be careful to ensure that the 
bottom louver will open when unit is installed 
with the fi nished hearth.

IMPORTANT:  It is absolutely necessary 
to attach stand-offs to the unit to 
avoid combustion problems.  Serious 
overheating of combustible framing and 
possible fi re may result if stand-offs are 
not properly installed.

IMPORTANT: Under no circumstances 
can the fi replace top or side spacers be 
removed or modifi ed.  Do not notch the 
header to be installed closer than the 
fi replace outside facing spacers.

The fi replace may be installed directly on a 
combustible fl oor or raised on a platform of an 
appropriate height. Do not place fi replace on 
carpeting, vinyl or other soft fl oor coverings. It 
may, however, be placed on fl at wood, plywood, 
particle board or other hard surfaces. Be sure 
the fi replace rests on a solid  continuous fl oor 
or platform for support and to prevent cold air 
from entering the room from under the fi replace, 
if against an outside wall.

The fi replace may be positioned and then the 
framing built around it, or the framing may be 
constructed and the fi replace positioned into 
the opening.  

The minimum ceiling height is 7ft (2m) from the 
base of the unit. A suitable non-combustible 
hearth pad is mandatory in all  installations. 
See Framing Details.

 

 

INSTALLING THE 

CHIMNEY SYSTEM

Following are a set of general guidelines for 
installation of  the chimney system. The more 
detailed installation manual supplied with the 
specifi c chimney system must be followed.

1) 

Using standard construction framing 
techniques,  construct the opening for the 
chimney route up through the ceiling(s) and  
roof or through an outside chase. Framing 
must maintain adequate minimum air space 
clearance at all  times.  

  
 

CAUTION

:  Allow a minimum 2" (51mm) 

chimney air space or as specified by 
the owner's manual for the chimney, to 
combustible framing members throughout 
vertical or offset chimney installation.

2) 

Attach fi replace adaptor/anchor plate to 
the top of the fi replace.  It is important that 
a tight seal be made with  this part and the 
unit’s collar. This must be purchased with 
the fi replace.

3) 

Install fi restop, radiation shield, or attic 
insulation  shield as required at each fl oor 
penetration. See Table 1 (page 15). Check 
chimney manufacturer's framing opening 
sizes to allow for correct  clearances. All 
parts must be listed.  

4) 

The roof fl ashing should be installed making 
sure that alignment is correct with openings 
below.  

5) 

Chimney lengths may now be added until 
the required height is reached. A minimum 
fl ue height of 12ft. (4m) from the top of the 
unit is mandatory. Please refer to Table 2 
for Flue Heights (page 15).

INSTALLING THE 

STAND-OFFS

Stand-offs are installed to provide reduced 
temperatures and proper clearances for the 
safe installation of your product.  They consist 
of four 3" (76mm) stand-offs on the back, two 
3" (76mm) stand-offs on each side and one 8" 
(203mm) stand-off on the top of the unit.

Attach these stand-offs where indicated in the 
pre-drilled holes on the unit body.  

IMPORTANT: Insulation extends forward 
to seal against the back of the fi replace 
masonry or non-combustible face.

SET THE REGENCY 

FP90 INTO POSITION

1) 

Estimate the total weight of the fi replace 
system and  surround materials such as 
brick, stone, etc., to be installed.   Shipping 
weight is 612 lbs (278kg).  

2) 

Measure the square footage of the fl oor 
space to be occupied by the system, 
surrounds and hearth extensions.  

3) 

Note the fl oor construction, i.e. 2 x 10’s, (51 
x 250 mm), single or double joists, type and  
thickness of fl oor boards and consult your 
local building code to determine if you need 
additional support.  

4) 

Remove door, fi rebox bricks, louvers etc.  

 

Note:   Set aside Gold louvers away from 

harsh chemicals and away from 
abrasive materials to avoid damage, 
e.g. muriatic acid for masonry wash 
will strip the gold plate.  Firebricks 
are fragile and should be handled 
with caution.

INSTALLATION

ASSEMBLY STEPS

Note: The following steps represent the 

normal sequence of  installation. 

 

Each installation is unique, however, 

and might  require  different steps.  

Each step is dealt with in detail in the 

following pages.

1) 

Install stand-offs and insulation strip to the 
unit.  See Installing the Stand-offs section 
on this page.

2) 

Complete framing and installation of nailing 
strips for the FP90.  

 

I M P O R TA N T:     R e m o v e   g o l d 
accessories such as louvers 
while installing to avoid marking.

 
 

Position fi rebox prior to framing or into 
prepared framing. 

3) 

Install the Chimney System. 

4) 

Install Outside Combustion Air Kit . 

5) 

Hook-up the Wiring.  

6)

 Install 

the 

Blower. 

7) 

Gravity Air Feed Option. 

8) 

Complete fi nish wall material, surround and 
hearth extension to your individual taste.  

9) 

Position vermiculite liner/bricks and ceramic 
fi ber insulation in the unit.  Attach louvers, 
glass, doors, handles.

Содержание FP90

Страница 1: ...d by Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for future reference Regency High Ef ciency EPA Certi ed...

Страница 2: ...of trouble free enjoyment This product has been certi ed by the Environmental Protection Agency of the United States This means that it meets the strictest standards in providing you with the latest...

Страница 3: ...n self Supporting Thin Veneer Facades Installation 17 Masonry Retainer Kit Option 18 Finishing Details 19 Completing The Mantle 19 Masonry Liner Bricks 20 Secondary Air Tube Installation 20 Glass Inst...

Страница 4: ...each Regency Fireplace It is located inside the lower louver opening on the left side We have printed a copy of the contents here for your review SAFETY LABEL NOTE Regency units are constantly being i...

Страница 5: ...eight 570 lbs 259kg Options Ashdrawer R90 EX90 Fan R90 EX90 Surround Black EX90 Surround Polished Gold EX90 Surround Antique Nickel EX90 Louver Flush Black R90 Louver Flush Black Gold R90 Louver Flush...

Страница 6: ...PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE IMPORTANT Please read and follow these rules for safety 1 Before starting your replace installation read these installation instructions carefully to be...

Страница 7: ...s replace system is designed for installation in accordance with the National Fire Protection Standard for chimneys replaces and solid fuel burningappliances NFPA211andin accordance with codes such as...

Страница 8: ...he front and facing of the replace and nearby walls WARNING If insulation is used do not place the unit against it Insulation or vapor barriers if used must be secured to assure insulation and vapor b...

Страница 9: ...the front of the unit supporting the header The enclosure walls can be framed using any suitable material 2x4 2x6 studs plywood gyproc etc Normally framing will be set back to allow Non Combustible Ma...

Страница 10: ...ed to elevate the replace above the oor a Z type safety strip should be fabricated from 20 gauge galvanized sheet steel and used to protect the front surface of the wood support as well as the oor ben...

Страница 11: ...ed when installing the replace Do not alter or mix parts from other systems as this may cause a potential hazard and void Regency s limited warranty Chimney Height Thetotalheightofyourchimneysystemfro...

Страница 12: ...E MIN 10 254mm 84 2134mm CEILING NOTES 1 CHASE MUST BE 60 1524mm WIDE INSIDE AND UNIT TO BE CENTERED IN OPENING 2 MANTEL MIN HEIGHT OF 18 457mm FROM TOP OF LOUVER OPENING TO UNDERNEATH MANTEL or 55 1...

Страница 13: ...required at each oor penetration See Table 1 page 15 Check chimney manufacturer s framing opening sizes to allow for correct clearances All parts must be listed 4 Theroof ashingshouldbeinstalledmaking...

Страница 14: ...e House When there is no re in your unit there still should be suf cient draft to draw smoke from a burning piece of paper held under the baf e If your installation is correct smoke will go up the ue...

Страница 15: ...Floor into Attic CF Sentinal Intermediate Joist Shield Attic Insulation Shield Super Pro 2100 Attic Insulation Shield Attic Insulation Shield Super Vent 2100 Attic Insulation Shield Attic Insulation...

Страница 16: ...louver opening is blocked off and ex vent is connected to the vent holes in the top of the unit and run to discharge vent grilles Both 8 203mm diameter insulated Flex vents must be used along with one...

Страница 17: ...les used for fastening mesh penetrate studs at least 1 25mm 4 Mortar must be thin set or thin bed type inherentlypolymermodi ed Ifnotmodi ed you should add a synthetic latex additive Mix to a rm moist...

Страница 18: ...me Check dimen sionsfromopeningandmarkanddrillscrew holes Dependingontheinstallation heavier reinforcing wire screen may be required to bridge the stand off spacer area around the perimeter of the uni...

Страница 19: ...hers and screw top mesh C to top of grill frame This is attached with the top edge of the grill frame on piece B 10 Now fasten mesh to wall sheathing and blend in 11 Use only non combustible masonry p...

Страница 20: ...facing the right hand side of the rebox 2 Slide the air tube back towards the right side until it locks into place To lock into position use a pair of vise grips and tap them with a mallet until the t...

Страница 21: ...de the rebox and one on the underside of the rebox by removing the two nuts and bolts holding the 2 plates together from underneath the stove 4 Push the ash plug into the hole inside the rebox and rep...

Страница 22: ...nting Bracket located on the front of the fan transfer tray and secure with the 8 x 3 8 screw provided refer to Diagram 1 5 Install the wiring as shown on the wiring diagram Use the strength relief fo...

Страница 23: ...ARE ON THE SLOTTED HOLES ON RIGHT SIDE ONLY 43 000 1092mm 39 250 997mm ONCE THE TEMPLATE IS MOUNTED CHECK TO MAKE SURE THE SIDES ARE PLUMB AND 43 1092mm IN WIDTH NOTE THE TOP IS ANGLED BACK AT 5 DEGR...

Страница 24: ...D INSTALL THE SURROUND TEMPLATE ONTO THE UNIT WARNING KEEP MASONRY MATERIAL AT LEAST 1 2 13mm FROM THIS TOP FACING GUIDE THIS IS REQUIRED TO PREVENT MASONRY FACING MATERIAL FROM HITTING THE TOP STIFFE...

Страница 25: ...lled correctly according to the specification in the manual The nailing strips must be attached to the top and sides of the unit They must be positioned so that they are set back 13 mm from the face o...

Страница 26: ...p trim Center it and attach it to the top nailing strip with self drilling screws 8 It is recommended that the joints of the sheathing run horizontal from the top corners of the unit rather than verti...

Страница 27: ...w driver to let the screws for the handle through 2 Fasten the handles to the screen using the fasteners provided INSTALLING THE SCREEN ON THE FIREPLACE 1 Ensure doors are opened enough to allow fire...

Страница 28: ...ont of the fireplace and slide the louver down onto the screws Installing the Bottom Louver 3 Closethebottomlouverandsecureonthemagnetsprovided refer to Diagrams 1 and 2 1 Fasten the bottom louver fra...

Страница 29: ...he fireplace the facing guide must be installed 3 Attach the sides of the top louver opening adapter to the left and right facing guides with two 2 screws 8 x Optional 4 Install the optional masonry c...

Страница 30: ...move the handles by removing the nut and screw Install the new handles by placing them in position over the holes on the surround louver Put the screws through the holes and secure them by tightening...

Страница 31: ...e of local codes withthecurrentCanadianorNational Gas Codes CAN1 B149 or ANSI Z223 1 Installation Codes 2 The appliance when installed must be electrically grounded in accordance with local codes or i...

Страница 32: ...er Round Duct collar over hole and attach to the tabs using 3 screws B All Models 1 Determinethe locationoftheairregister fan housing assembly Cut a 5 x 16 121mm x 406mm hole between framing members w...

Страница 33: ...run Oval duct components are not supplied but can be purchased from an HVAC supplier OPERATION 1 Start the replace as per instructions and allow it to warm up 2 Turn the Wall Rheostat ON and adjust t...

Страница 34: ...ative pressure in the house allowing smoke to back into the home The preferred source of combustion air is from outside the building Ifpossible installthekitonthewind loading side of the building not...

Страница 35: ...y air tube and baf es b Removetheterminationcapbyremoving the screws and lifting c Make sure replace doors are shut to prevent soot and dirt from entering the loom d Clean chimney with either nylon or...

Страница 36: ...wer Complete Shelf Ash Drawer Ash Drawer Ash Drawer Lid 942 110 Ash Plug 820 375 Ash Hole Cover Plate Retainer Plate 9 948 326 Intake Pipe 6 948 327 Intake Pipe Insulation 948 416 6 Outside Air Kit Pa...

Страница 37: ...44 39 41 43 42 Brick Liner Bottom Left Vermiculite Liner Left Side Vermiculite Liner Right Side Brick Liner Back Left Brick Liner Back Right Vermiculite Liner Bottom Baffle Firebox Top Left and Right...

Страница 38: ...____________ ___________________________________________________ ___________________________________________________ ___________________________________________________ _______________________________...

Страница 39: ...s of workmanship from unauthorized service persons or dealers At all times FPI reserves the right to inspect product in the field which is claimed to be defective All claims must be submitted to FPI b...

Страница 40: ..._______________________________________ Printed in Canada Regency replace products are designed with reliability and simplicity in mind In addition our internal Quality Assurance Team carefully inspec...

Отзывы: