background image

FPI FP90 Wood Fireplace

9

INST

ALLA

TION

Building Structures Cannot Encroach on Chase

50-3/4"

(1289mm)

44"

(1118mm)

INSTALLATION OF 

NAILING STRIPS

1) 

Assemble 3 Nailing Strip Spacer Plates 

to the left and the right Nailing Strips as 
shown below.

Left Nailing Strip

Nailing 
Spacer

Right Nailing
Strip

x 12

Right Nailing Strip

Top Nailing
Strip

Left
Nailing
Strip

x 9

2)

  Mount Nailing Strips left, right and top to the 

positions indicated below.

NOTE

:

Nailing Strips are adjustable to allow for correct 
offset from the front of the fi replace for your 
current application.

There are two adjustments to allow for maximum 
offset (1" , 25mm recessed from front of fi replace 
or 1.25", 32mm  extending past front of fi replace). 
The Nailing Strip Spacers can be adjusted by 
loosening the two screws securing them to the 
Nailing Strips. The Nailing Strips can also be 
moved forward and back by adjusting the screws 
that mount them to the fi replace.

FIREPLACE 

ENCLOSURE FRAMING

As per the diagram, the framing of the main 
enclosure should not infringe on the area above 
the fi replace to the ceiling level.  The rear and 
side walls as well as the face above the fi replace 
must not extend into the area above the unit. 
The only structure allowed above the unit is on 
the stand-offs at the front of the unit supporting 
the header.

The enclosure walls can be framed using any 
suitable material (2x4 - 2x6 studs, plywood, 
gyproc, etc.), 

Normally, framing will be set 

back to allow Non-Combustible Material to 
be fl ush with the front of the fi replace.

There is framing only on the front of the unit. 
When framing in the header (directly above 
the fi replace) 

 DO NOT

 bring any combustible 

material lower than the top of the stand-offs. 
Framing header may be positioned on end 
directly on top of the front fi replace stand-offs. 
Be sure to seal the space between the fi replace 
and the enclosure above and on either side of 
the unit with Wonderboard, Durock or other 
similar non-combustible sheeting to prevent hot 
air from entering the enclosure.

C A U T I O N :   O N L Y   N O N -
C O M B U S T I B L E   M AT E R I A L 
L I K E   E X PA N D E D   M E TA L  O R 
CONCRETE BOARDS SUCH AS 
WONDERBOARD AND DUROCK, 
ETC. MAY BE USED IN THE 
SPACE BETWEEN THE UNIT AND 
THE FRAMING IN FRONT OF THE 
UNIT ONLY.

Note:   If the fi replace is being cantilevered 

through an outside wall, the entire 
enclosure (floor, wall and false 
ceiling) up to the fi rst ceiling level 
must be completely insulated and 
vapor sealed and sheathed, to avoid 
transfer of cold air through the 
fi replace when not in use.

Framing Specifi cations

INSTALLATION

44 " [1118mm]

" [248mm]

3
4

9

 " [2930mm]

8

3

115

18 " [457mm]

 " [370mm]

8

14

5

28 " [710mm]

 " [1465mm]

 " [2072mm]

81

2

1

8

5

57

4

1

31  " [795mm]

13  " [348mm]

3
4

60 " [1524mm] CHASE

 " [348mm]

3
4

13

Содержание FP90

Страница 1: ...d by Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for future reference Regency High Ef ciency EPA Certi ed...

Страница 2: ...of trouble free enjoyment This product has been certi ed by the Environmental Protection Agency of the United States This means that it meets the strictest standards in providing you with the latest...

Страница 3: ...n self Supporting Thin Veneer Facades Installation 17 Masonry Retainer Kit Option 18 Finishing Details 19 Completing The Mantle 19 Masonry Liner Bricks 20 Secondary Air Tube Installation 20 Glass Inst...

Страница 4: ...each Regency Fireplace It is located inside the lower louver opening on the left side We have printed a copy of the contents here for your review SAFETY LABEL NOTE Regency units are constantly being i...

Страница 5: ...eight 570 lbs 259kg Options Ashdrawer R90 EX90 Fan R90 EX90 Surround Black EX90 Surround Polished Gold EX90 Surround Antique Nickel EX90 Louver Flush Black R90 Louver Flush Black Gold R90 Louver Flush...

Страница 6: ...PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE IMPORTANT Please read and follow these rules for safety 1 Before starting your replace installation read these installation instructions carefully to be...

Страница 7: ...s replace system is designed for installation in accordance with the National Fire Protection Standard for chimneys replaces and solid fuel burningappliances NFPA211andin accordance with codes such as...

Страница 8: ...he front and facing of the replace and nearby walls WARNING If insulation is used do not place the unit against it Insulation or vapor barriers if used must be secured to assure insulation and vapor b...

Страница 9: ...the front of the unit supporting the header The enclosure walls can be framed using any suitable material 2x4 2x6 studs plywood gyproc etc Normally framing will be set back to allow Non Combustible Ma...

Страница 10: ...ed to elevate the replace above the oor a Z type safety strip should be fabricated from 20 gauge galvanized sheet steel and used to protect the front surface of the wood support as well as the oor ben...

Страница 11: ...ed when installing the replace Do not alter or mix parts from other systems as this may cause a potential hazard and void Regency s limited warranty Chimney Height Thetotalheightofyourchimneysystemfro...

Страница 12: ...E MIN 10 254mm 84 2134mm CEILING NOTES 1 CHASE MUST BE 60 1524mm WIDE INSIDE AND UNIT TO BE CENTERED IN OPENING 2 MANTEL MIN HEIGHT OF 18 457mm FROM TOP OF LOUVER OPENING TO UNDERNEATH MANTEL or 55 1...

Страница 13: ...required at each oor penetration See Table 1 page 15 Check chimney manufacturer s framing opening sizes to allow for correct clearances All parts must be listed 4 Theroof ashingshouldbeinstalledmaking...

Страница 14: ...e House When there is no re in your unit there still should be suf cient draft to draw smoke from a burning piece of paper held under the baf e If your installation is correct smoke will go up the ue...

Страница 15: ...Floor into Attic CF Sentinal Intermediate Joist Shield Attic Insulation Shield Super Pro 2100 Attic Insulation Shield Attic Insulation Shield Super Vent 2100 Attic Insulation Shield Attic Insulation...

Страница 16: ...louver opening is blocked off and ex vent is connected to the vent holes in the top of the unit and run to discharge vent grilles Both 8 203mm diameter insulated Flex vents must be used along with one...

Страница 17: ...les used for fastening mesh penetrate studs at least 1 25mm 4 Mortar must be thin set or thin bed type inherentlypolymermodi ed Ifnotmodi ed you should add a synthetic latex additive Mix to a rm moist...

Страница 18: ...me Check dimen sionsfromopeningandmarkanddrillscrew holes Dependingontheinstallation heavier reinforcing wire screen may be required to bridge the stand off spacer area around the perimeter of the uni...

Страница 19: ...hers and screw top mesh C to top of grill frame This is attached with the top edge of the grill frame on piece B 10 Now fasten mesh to wall sheathing and blend in 11 Use only non combustible masonry p...

Страница 20: ...facing the right hand side of the rebox 2 Slide the air tube back towards the right side until it locks into place To lock into position use a pair of vise grips and tap them with a mallet until the t...

Страница 21: ...de the rebox and one on the underside of the rebox by removing the two nuts and bolts holding the 2 plates together from underneath the stove 4 Push the ash plug into the hole inside the rebox and rep...

Страница 22: ...nting Bracket located on the front of the fan transfer tray and secure with the 8 x 3 8 screw provided refer to Diagram 1 5 Install the wiring as shown on the wiring diagram Use the strength relief fo...

Страница 23: ...ARE ON THE SLOTTED HOLES ON RIGHT SIDE ONLY 43 000 1092mm 39 250 997mm ONCE THE TEMPLATE IS MOUNTED CHECK TO MAKE SURE THE SIDES ARE PLUMB AND 43 1092mm IN WIDTH NOTE THE TOP IS ANGLED BACK AT 5 DEGR...

Страница 24: ...D INSTALL THE SURROUND TEMPLATE ONTO THE UNIT WARNING KEEP MASONRY MATERIAL AT LEAST 1 2 13mm FROM THIS TOP FACING GUIDE THIS IS REQUIRED TO PREVENT MASONRY FACING MATERIAL FROM HITTING THE TOP STIFFE...

Страница 25: ...lled correctly according to the specification in the manual The nailing strips must be attached to the top and sides of the unit They must be positioned so that they are set back 13 mm from the face o...

Страница 26: ...p trim Center it and attach it to the top nailing strip with self drilling screws 8 It is recommended that the joints of the sheathing run horizontal from the top corners of the unit rather than verti...

Страница 27: ...w driver to let the screws for the handle through 2 Fasten the handles to the screen using the fasteners provided INSTALLING THE SCREEN ON THE FIREPLACE 1 Ensure doors are opened enough to allow fire...

Страница 28: ...ont of the fireplace and slide the louver down onto the screws Installing the Bottom Louver 3 Closethebottomlouverandsecureonthemagnetsprovided refer to Diagrams 1 and 2 1 Fasten the bottom louver fra...

Страница 29: ...he fireplace the facing guide must be installed 3 Attach the sides of the top louver opening adapter to the left and right facing guides with two 2 screws 8 x Optional 4 Install the optional masonry c...

Страница 30: ...move the handles by removing the nut and screw Install the new handles by placing them in position over the holes on the surround louver Put the screws through the holes and secure them by tightening...

Страница 31: ...e of local codes withthecurrentCanadianorNational Gas Codes CAN1 B149 or ANSI Z223 1 Installation Codes 2 The appliance when installed must be electrically grounded in accordance with local codes or i...

Страница 32: ...er Round Duct collar over hole and attach to the tabs using 3 screws B All Models 1 Determinethe locationoftheairregister fan housing assembly Cut a 5 x 16 121mm x 406mm hole between framing members w...

Страница 33: ...run Oval duct components are not supplied but can be purchased from an HVAC supplier OPERATION 1 Start the replace as per instructions and allow it to warm up 2 Turn the Wall Rheostat ON and adjust t...

Страница 34: ...ative pressure in the house allowing smoke to back into the home The preferred source of combustion air is from outside the building Ifpossible installthekitonthewind loading side of the building not...

Страница 35: ...y air tube and baf es b Removetheterminationcapbyremoving the screws and lifting c Make sure replace doors are shut to prevent soot and dirt from entering the loom d Clean chimney with either nylon or...

Страница 36: ...wer Complete Shelf Ash Drawer Ash Drawer Ash Drawer Lid 942 110 Ash Plug 820 375 Ash Hole Cover Plate Retainer Plate 9 948 326 Intake Pipe 6 948 327 Intake Pipe Insulation 948 416 6 Outside Air Kit Pa...

Страница 37: ...44 39 41 43 42 Brick Liner Bottom Left Vermiculite Liner Left Side Vermiculite Liner Right Side Brick Liner Back Left Brick Liner Back Right Vermiculite Liner Bottom Baffle Firebox Top Left and Right...

Страница 38: ...____________ ___________________________________________________ ___________________________________________________ ___________________________________________________ _______________________________...

Страница 39: ...s of workmanship from unauthorized service persons or dealers At all times FPI reserves the right to inspect product in the field which is claimed to be defective All claims must be submitted to FPI b...

Страница 40: ..._______________________________________ Printed in Canada Regency replace products are designed with reliability and simplicity in mind In addition our internal Quality Assurance Team carefully inspec...

Отзывы: