background image

FPI FP90 Wood Fireplace

16

INST

ALLA

TION

Plan View

Jakel AX-2495 Blower

Angle View

Fan Transfer Plate

Right View

Front View

Fan 910-175 AX-3088

910-903 
910-516

Ground

Neutral - from Fan

910-811

Thermodisc 910-142 P60T12

Variable Switch 910-330

919-885

Power Chord 910-619

Ground

Hot - to Va

riable Switch

WIRING THE FP90

Field wire main power supply to fi replace blower 
system.  (All electrical connections should 
only be performed by a  licensed/certifi ed 
electrician).  

CAUTION:   Label all wires prior to 
disconnection when servicing controls. 
Wiring errors can cause improper and 
dangerous operation.

INSTALLING THE

BLOWER SYSTEMS

The FP90 Fireplace has been designed to 
meet a wide range of heating requirements.  
The radiant heat (through the large glass area) 
combined with the naturally convected heat, 
allows the FP90 Fireplace to adequately heat an 
average sized room.  A blower is recommended 
to assist in heating a larger area or one with wall 
separations.  Through the use of two separate 
blower systems, Regency has developed 
the basic blower wiring options listed in the 
diagrams shown.  

GRAVITY AIR FEED KIT OPTION

The Gravity Air Feed Kit is designed to extend the heat output vent 
above the FP90 to the front or the side. The upper louver opening 
is blocked off and fl ex vent is connected to the vent holes in the 
top of the unit and run to discharge vent grilles. Both 8" (203mm) 
diameter insulated Flex vents must be used along with one 30 sq. 
inch (194cm

2

) chase vent grill to bring additional air into the chase 

(for U.S. installations only).

Qty   Description

4  

 Connector 

Collars

4  

 Adjustable 

Clamps

2  

 

5’ lengths of fl exible vent pipe 

 

  (8” 

dia.)

2  

 Insulated 

Sleeves

1  

 

Block Off Plate

2  

 

Discharge Vent Mounting Frames

7  

 

1/4-20 x 1/2” Truss Head Screws 

 

  

(used for EX90/R90 only)

2  

 

16 x 8 Discharge Vent Grilles

4  

 #8 

Drywall 

Anchors

4  

 Insulation 

Strips

1  

 Chase 

Vent 

Frame 

 

  

(not required for FP90)

1  

 

8 x 8 Chase Vent Grille 

 

  

(not required for FP90)

Discharge Vent 
Grill

Chase Vent 
Grill  

30 sq.in. (194 sq.cm) 
opening

Alternate Position for 
Chase Vent Grill

Block-off Plate
(replace top louver)

Base of Stove

Vent Cover 'B'
(Inside)

Vent Cover 'A"

Center-line
of Vent

6" (152mm) Min.
To Rouch Opening

Ceiling

Flue

Flex Vent

Clamp

Connector
Collar

Connector
Collar

Outside Air
Intake

Insulation 
Strips

INSTALLATION

Internal Blower with Thermo-Disc

The thermodisc provides the user with more convenient control.  The fan operates automati-
cally - turn the knob to adjust to desired speed. The fan will turn on as the stove comes up to 
operating temperature. After the fi re cools to below a useful heat output range the fan will shut 
off automatically.

Place sticker on outside of bottom louver.

Содержание FP90

Страница 1: ...d by Installer Please complete the details on the back cover and leave this manual with the homeowner Homeowner Please keep these instructions for future reference Regency High Ef ciency EPA Certi ed...

Страница 2: ...of trouble free enjoyment This product has been certi ed by the Environmental Protection Agency of the United States This means that it meets the strictest standards in providing you with the latest...

Страница 3: ...n self Supporting Thin Veneer Facades Installation 17 Masonry Retainer Kit Option 18 Finishing Details 19 Completing The Mantle 19 Masonry Liner Bricks 20 Secondary Air Tube Installation 20 Glass Inst...

Страница 4: ...each Regency Fireplace It is located inside the lower louver opening on the left side We have printed a copy of the contents here for your review SAFETY LABEL NOTE Regency units are constantly being i...

Страница 5: ...eight 570 lbs 259kg Options Ashdrawer R90 EX90 Fan R90 EX90 Surround Black EX90 Surround Polished Gold EX90 Surround Antique Nickel EX90 Louver Flush Black R90 Louver Flush Black Gold R90 Louver Flush...

Страница 6: ...PLEASE RETAIN THIS MANUAL FOR FUTURE REFERENCE IMPORTANT Please read and follow these rules for safety 1 Before starting your replace installation read these installation instructions carefully to be...

Страница 7: ...s replace system is designed for installation in accordance with the National Fire Protection Standard for chimneys replaces and solid fuel burningappliances NFPA211andin accordance with codes such as...

Страница 8: ...he front and facing of the replace and nearby walls WARNING If insulation is used do not place the unit against it Insulation or vapor barriers if used must be secured to assure insulation and vapor b...

Страница 9: ...the front of the unit supporting the header The enclosure walls can be framed using any suitable material 2x4 2x6 studs plywood gyproc etc Normally framing will be set back to allow Non Combustible Ma...

Страница 10: ...ed to elevate the replace above the oor a Z type safety strip should be fabricated from 20 gauge galvanized sheet steel and used to protect the front surface of the wood support as well as the oor ben...

Страница 11: ...ed when installing the replace Do not alter or mix parts from other systems as this may cause a potential hazard and void Regency s limited warranty Chimney Height Thetotalheightofyourchimneysystemfro...

Страница 12: ...E MIN 10 254mm 84 2134mm CEILING NOTES 1 CHASE MUST BE 60 1524mm WIDE INSIDE AND UNIT TO BE CENTERED IN OPENING 2 MANTEL MIN HEIGHT OF 18 457mm FROM TOP OF LOUVER OPENING TO UNDERNEATH MANTEL or 55 1...

Страница 13: ...required at each oor penetration See Table 1 page 15 Check chimney manufacturer s framing opening sizes to allow for correct clearances All parts must be listed 4 Theroof ashingshouldbeinstalledmaking...

Страница 14: ...e House When there is no re in your unit there still should be suf cient draft to draw smoke from a burning piece of paper held under the baf e If your installation is correct smoke will go up the ue...

Страница 15: ...Floor into Attic CF Sentinal Intermediate Joist Shield Attic Insulation Shield Super Pro 2100 Attic Insulation Shield Attic Insulation Shield Super Vent 2100 Attic Insulation Shield Attic Insulation...

Страница 16: ...louver opening is blocked off and ex vent is connected to the vent holes in the top of the unit and run to discharge vent grilles Both 8 203mm diameter insulated Flex vents must be used along with one...

Страница 17: ...les used for fastening mesh penetrate studs at least 1 25mm 4 Mortar must be thin set or thin bed type inherentlypolymermodi ed Ifnotmodi ed you should add a synthetic latex additive Mix to a rm moist...

Страница 18: ...me Check dimen sionsfromopeningandmarkanddrillscrew holes Dependingontheinstallation heavier reinforcing wire screen may be required to bridge the stand off spacer area around the perimeter of the uni...

Страница 19: ...hers and screw top mesh C to top of grill frame This is attached with the top edge of the grill frame on piece B 10 Now fasten mesh to wall sheathing and blend in 11 Use only non combustible masonry p...

Страница 20: ...facing the right hand side of the rebox 2 Slide the air tube back towards the right side until it locks into place To lock into position use a pair of vise grips and tap them with a mallet until the t...

Страница 21: ...de the rebox and one on the underside of the rebox by removing the two nuts and bolts holding the 2 plates together from underneath the stove 4 Push the ash plug into the hole inside the rebox and rep...

Страница 22: ...nting Bracket located on the front of the fan transfer tray and secure with the 8 x 3 8 screw provided refer to Diagram 1 5 Install the wiring as shown on the wiring diagram Use the strength relief fo...

Страница 23: ...ARE ON THE SLOTTED HOLES ON RIGHT SIDE ONLY 43 000 1092mm 39 250 997mm ONCE THE TEMPLATE IS MOUNTED CHECK TO MAKE SURE THE SIDES ARE PLUMB AND 43 1092mm IN WIDTH NOTE THE TOP IS ANGLED BACK AT 5 DEGR...

Страница 24: ...D INSTALL THE SURROUND TEMPLATE ONTO THE UNIT WARNING KEEP MASONRY MATERIAL AT LEAST 1 2 13mm FROM THIS TOP FACING GUIDE THIS IS REQUIRED TO PREVENT MASONRY FACING MATERIAL FROM HITTING THE TOP STIFFE...

Страница 25: ...lled correctly according to the specification in the manual The nailing strips must be attached to the top and sides of the unit They must be positioned so that they are set back 13 mm from the face o...

Страница 26: ...p trim Center it and attach it to the top nailing strip with self drilling screws 8 It is recommended that the joints of the sheathing run horizontal from the top corners of the unit rather than verti...

Страница 27: ...w driver to let the screws for the handle through 2 Fasten the handles to the screen using the fasteners provided INSTALLING THE SCREEN ON THE FIREPLACE 1 Ensure doors are opened enough to allow fire...

Страница 28: ...ont of the fireplace and slide the louver down onto the screws Installing the Bottom Louver 3 Closethebottomlouverandsecureonthemagnetsprovided refer to Diagrams 1 and 2 1 Fasten the bottom louver fra...

Страница 29: ...he fireplace the facing guide must be installed 3 Attach the sides of the top louver opening adapter to the left and right facing guides with two 2 screws 8 x Optional 4 Install the optional masonry c...

Страница 30: ...move the handles by removing the nut and screw Install the new handles by placing them in position over the holes on the surround louver Put the screws through the holes and secure them by tightening...

Страница 31: ...e of local codes withthecurrentCanadianorNational Gas Codes CAN1 B149 or ANSI Z223 1 Installation Codes 2 The appliance when installed must be electrically grounded in accordance with local codes or i...

Страница 32: ...er Round Duct collar over hole and attach to the tabs using 3 screws B All Models 1 Determinethe locationoftheairregister fan housing assembly Cut a 5 x 16 121mm x 406mm hole between framing members w...

Страница 33: ...run Oval duct components are not supplied but can be purchased from an HVAC supplier OPERATION 1 Start the replace as per instructions and allow it to warm up 2 Turn the Wall Rheostat ON and adjust t...

Страница 34: ...ative pressure in the house allowing smoke to back into the home The preferred source of combustion air is from outside the building Ifpossible installthekitonthewind loading side of the building not...

Страница 35: ...y air tube and baf es b Removetheterminationcapbyremoving the screws and lifting c Make sure replace doors are shut to prevent soot and dirt from entering the loom d Clean chimney with either nylon or...

Страница 36: ...wer Complete Shelf Ash Drawer Ash Drawer Ash Drawer Lid 942 110 Ash Plug 820 375 Ash Hole Cover Plate Retainer Plate 9 948 326 Intake Pipe 6 948 327 Intake Pipe Insulation 948 416 6 Outside Air Kit Pa...

Страница 37: ...44 39 41 43 42 Brick Liner Bottom Left Vermiculite Liner Left Side Vermiculite Liner Right Side Brick Liner Back Left Brick Liner Back Right Vermiculite Liner Bottom Baffle Firebox Top Left and Right...

Страница 38: ...____________ ___________________________________________________ ___________________________________________________ ___________________________________________________ _______________________________...

Страница 39: ...s of workmanship from unauthorized service persons or dealers At all times FPI reserves the right to inspect product in the field which is claimed to be defective All claims must be submitted to FPI b...

Страница 40: ..._______________________________________ Printed in Canada Regency replace products are designed with reliability and simplicity in mind In addition our internal Quality Assurance Team carefully inspec...

Отзывы: