REFRIGERATED CABINETS  -  SERVICING 

 

FPG Settings

 

Note that the following settings are Dixell factory defaults.  Refer to the 
Specification section for the correct FPG settings for your cabinet. 

 

Dixell Default 
Settings

 

Label 

Name 

Range 

Default Setting 

Set 

Set point 

LS÷ US 

-5.0 

Hy 

Differential 

0,1÷25.5°C/ 1÷ 255°F 

2.0 

LS 

Minimum set point 

-50°C÷SET/-58°F÷SET 

-50.0 

US 

Maximum set point 

SET÷110°C/ SET ÷ 230°F 

110 

Ot 

Thermostat probe calibration 

-12÷12°C /-120÷120°F 

0.0 

P2P 

Evaporator probe presence 

n=not present; Y=pres. 

OE 

Evaporator probe calibration 

-12÷12°C /-120÷120°F 

0.0 

P3P 

Third probe presence 

n=not present; Y=pres. 

O3 

Third probe calibration 

-12÷12°C /-120÷120°F 

P4P 

Fourth probe presence 

n=not present; Y=pres. 

O4 

Fourth probe calibration 

-12÷12°C /-120÷120°F 

OdS 

Outputs delay at start up 

0÷255 min 

AC 

Anti-short cycle delay 

0 ÷ 50 min 

rtr 

P1-P2 percentage for regulation 

0 ÷ 100 (100=P1 , 0=P2) 

100 

CCt 

Continuous cycle duration 

0.0÷24.0h 

0.0 

CCS 

Set point for continuous cycle 

(-55.0÷150,0°C) (-67÷302°F) 

-5 

COn 

Compressor ON time with faulty probe 

0 ÷ 255 min 

15 

COF 

Compressor OFF time with faulty probe 

0 ÷ 255 min 

30 

CF 

Temperature measurement unit 

°C ÷ °F 

°C 

rES 

Resolution 

in=integer; dE= dec.point 

dE 

Lod 

Probe displayed 

P1;P2 

P1 

rEd2 

X-REP display 

P1 - P2 - P3 - P4 - SEt - dtr 

P1 

dLy 

Display temperature delay 

0 ÷ 20.0 min (10 sec.) 

dtr 

P1-P2 percentage for display 

1 ÷ 99 

50 

tdF 

Defrost type 

EL=el. heater; in= hot gas 

EL 

dFP 

Probe selection for defrost termination 

nP; P1; P2; P3; P4 

P2 

dtE 

Defrost termination temperature 

-50 ÷ 50 °C 

IdF 

Interval between defrost cycles 

1 ÷ 120 ore 

MdF 

(Maximum) length for defrost 

0 ÷ 255 min 

30 

dSd 

Start defrost delay 

0÷99min 

dFd 

Displaying during defrost 

rt, it, SEt, DEF 

it 

dAd 

MAX display delay after defrost 

0 ÷ 255 min 

30 

Fdt 

Draining time 

0÷120 min 

dPo 

First defrost after start-up 

n=after IdF; y=immed. 

dAF 

Defrost delay after fast freezing 

0 ÷ 23h e 50’

 

0.0 

ALc 

Temperature alarms configuration 

rE= related to set;  Ab = absolute 

Ab 

ALU 

MAXIMUM temperature alarm 

Set÷110.0°C; Set÷230°F 

110 

ALL 

Minimum temperature alarm 

-50.0°C÷Set/ -58°F÷Set 

-50.0 

Continued on next page 

Содержание IN 5C08

Страница 1: ...Refrigerated Cabinets...

Страница 2: ...re Products Group Limited All rights reserved No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying r...

Страница 3: ...oors 9 Square Glass Cabinets 9 Lighting 9 Controls 10 Control Panel 10 Power Switch 10 Refrigeration 10 Lights 10 Thermometer 10 Temperature Controller 11 Temperature Controller Adjustment 11 Preparat...

Страница 4: ...e Cabinet Base Cavity 18 Caution 18 Cleaning the Base Cavity 19 Cooling Fins 19 Temperature Probes 19 Condensate Tray 19 Routine 20 Schedules 20 Warning 20 Condenser Radiator 20 Removable Filters wher...

Страница 5: ...ondensate Disposal 25 ACR Fault Finding Guide 25 Condenser Radiator 26 Louver Panels 26 Temperature Regulator XR40CX 27 XR40CX Connections 33 Gaskets 34 Qlon Gaskets 34 Gasket Replacement 34 Rubber Ga...

Страница 6: ...2 SPARE PARTS 43 Cabinet Serial Number 43 Location of Glass Parts 44 MECHANICAL DRAWINGS 45 Cabinet Feet 45 Tilt Door Cabinets Types IN 5C08 12 15 45 Sliding Door Cabinets Types IN 5C08 12 15 46 Tilt...

Страница 7: ...ions both general and technical tell you how to operate and look after your inline food service cabinet so that you can receive the full benefits that this cabinet has to offer These instructions cann...

Страница 8: ...copies of service records in the event of compressor failure Damage resulting from maladjustment of the electronic refrigeration controller by an unqualified person Any damage or malfunction resulting...

Страница 9: ...All the refrigeration and control equipment is housed in the base of the cabinet Square Glass Cabinets The square glass cabinet does not have front opening doors It has rear sliding doors similar to t...

Страница 10: ...clockwise direction Note that the cabinet and condenser fans will operate as soon as the power is turned on Refrigeration To start refrigeration rotate the refrigeration switch in a clockwise directi...

Страница 11: ...air entering the cooling coil This is used to control the refrigeration condenser operation and will be marginally higher than the internal cabinet temperature Incorrect adjustment can cause the fins...

Страница 12: ...compressor and cabinet fans will run Turn on Refrigeration Turn on refrigeration switch as shown above The compressor will run and the cabinet temperature will begin to fall The temperature controlle...

Страница 13: ...lear of the shaded areas shown in the picture A minimum clearance of 40 mm should be maintained below the light fittings and air deflectors The air grills at the front and rear of the cabinet must not...

Страница 14: ...turn the cabinet on again turn off the lights and shut the doors The cabinet will cool down under minimum load and be ready for the next day s use De frost Cycle The cabinet will de frost automatical...

Страница 15: ...Ambient temperature 25 C Adjust store air conditioning Damaged or missing door seal Replace door seal Evaporator coil iced up De ice coil Condenser radiator blocked Remove dust and debris Thermostat...

Страница 16: ...on louvers This will maintain the refrigeration efficiency and prevent overheating Painted and Metal Surfaces Painted stainless steel or aluminium surfaces should be cleaned with hot soapy water or a...

Страница 17: ...iding door tracks should be vacuumed out regularly to keep doors sliding freely Failure to do so will damage the gliders and track Tilt Doors Tilt doors are not readily removable so the outer glass sh...

Страница 18: ...hese may damage surfaces Warning Dishwasher detergents will damage any anodised aluminium parts Access to the Cabinet Base Cavity Remove the front ticketing rail from the deck trays if fitted Lift out...

Страница 19: ...DO NOT attempt to hose food parts from fins Caution The fins are very sharp Take extra care when cleaning this area Do not bend the fins over as this would restrict the air flow and degrade cabinet p...

Страница 20: ...f dust and fluff but periodic cleaning of the fins by a refrigeration engineer is mandatory Removable Filters where fitted These air filters must be kept clean to maintain efficient refrigeration perf...

Страница 21: ...binet is supplied fully assembled but the shelf trays are packed separately Site Preparation Ensure the cabinet location and any bench cut outs are made to the precise measurements shown in the specif...

Страница 22: ...o the power supply check that the local supply is correct to that shown on the rating plate located on the rear of the cabinet Isolation If the cabinet is not connected by a plug and socket but is har...

Страница 23: ...ated on a separate chassis in the base of the cabinet Test Lighting Components Before replacing an LED strip check that the power supply is working If there is no dc voltage at the output the power su...

Страница 24: ...he cabinet at the main switch or unplugging it from the wall Access to Compressor etc To gain access to the refrigeration condenser radiator and ACR module etc the rear panels should be removed The co...

Страница 25: ...present Test Check if the Finder Level Control unit is faulty by disconnecting the probe wire from terminal B1 on the Finder Level Control unit With the cabinet power turned on and after waiting 10 s...

Страница 26: ...temperature may rise Regular vacuuming will prevent a build up of dust and fluff however three monthly service checks which include cleaning of the condenser using C02 by a refrigeration engineer are...

Страница 27: ...he keyboard or by use of a hot key XR40CX Compressor Control The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point i...

Страница 28: ...d value DOWN To see the min stored temperature in programming mode it browses the parameter codes or decreases the displayed value To switch the instrument off if onF oFF Not enabled To lock unlock th...

Страница 29: ...Press and immediately release the SET key or wait for 5 seconds to display the probe temperature again XR40CX Change the Set point To change the set point value press the SET key for more than 2 secon...

Страница 30: ...a key NOTE 1 If no parameter is present in Pr1 after 3s the noP message is displayed Keep the keys pushed till the Pr2 message is displayed NOTE 2 The set value is stored even when the procedure is e...

Страница 31: ...uous cycle duration 0 0 24 0h 0 0 CCS Set point for continuous cycle 55 0 150 0 C 67 302 F 5 COn Compressor ON time with faulty probe 0 255 min 15 COF Compressor OFF time with faulty probe 0 255 min 3...

Страница 32: ...ut alarm delay 0 255min 5 Nps Number of activation of pressure switch 0 15 15 odc Compress status when open door no Fan CPr F_C no rrd Regulation restart with door open alarm n Y y HES Differential fo...

Страница 33: ...ious external alarm i1 F bAL All outputs OFF CA Pressure switch alarm i1 F PAL All outputs OFF XR40CX Alarm Recovery Probe alarms P1 P2 P3 and P4 start some seconds after the fault in the related prob...

Страница 34: ...ions Gasket Replacement The top aluminium extrusion is in two halves with a 20mm gap at the centre The bottom extrusion has a gap at one side To replace the gasket pull the old one out of the extrusio...

Страница 35: ...Glass Slide Tilt or Fixed Glass Slide Tilt or Fixed Glass Slide Tilt or Fixed Glass Slide Tilt or Fixed Glass Slide Tilt or Fixed Glass Slide Tilt or Fixed Glass Slide Tilt or Fixed Glass Cabinet Wel...

Страница 36: ...er 1 42 kW 300W excl condenser 1 93 kW 360W excl condenser Current 4 4 A 5 3 A 6 7 A 1A excl condenser 6 2 A 1 3 A excl condenser 8 4 A 1 5 A excl condenser Connection Three core cable with 10A 3 pin...

Страница 37: ...C0F 6 6 6 6 Min Defrost Terminate Temp dtE 3 3 3 3 degC Interval Between Defrosts idF 4 4 4 4 Hrs Display During Defrost dFd DEF DEF DEF DEF rt it Set DEF Maximum Temperature Alarm ALU 12 12 110 110 d...

Страница 38: ...armonic current emissions equipment input current up to and including 16A per phase Part 3 Limits Section 3 Limitations of voltage changes voltage fluctuations and flicker in public low voltage supply...

Страница 39: ...posal procedures are required for the safe removal of refrigerant gasses and potentially flammable foam materials Pentane Dimethyl Ether Isobutene Butane and Propane may be present Hazardous Substance...

Страница 40: ...o 26107 Rev J August 2018 40 Inline 5000 Series Cabinets ELECTRICAL CIRCUIT DIAGRAMS Model IN 5C08 Inline 5000 Series 800mm Refrigerated Cabinet Model IN 5C12 Inline 5000 Series 1200mm Refrigerated Ca...

Страница 41: ...5C08 12 15 18 24 41 Future Products Group ELECTRICAL CIRCUIT DIAGRAMS Continued Model IN 5C15 Inline 5000 Series 1500mm Refrigerated Cabinet Model IN 5C18 Inline 5000 Series 1800mm Refrigerated Cabin...

Страница 42: ...Part No 26107 Rev J August 2018 42 Inline 5000 Series Cabinets ELECTRICAL CIRCUIT DIAGRAMS Continued Model IN 5C24 Inline 5000 Series 2400mm Refrigerated Cabinet...

Страница 43: ...for 5C15 Curved Square 70442 69706 Shelf Light Replacement Kit for 5C15 Curved Square 69801 69801 Top Light Replacement Kit for 5C18 Curved Square 69685 69799 Shelf Light Replacement Kit for 5C18 Curv...

Страница 44: ...e Glass Cabinet 18986 Front Panel 2400 Square Glass Cabinet 18988 Top Panel 800 Square Glass Cabinet 18983 Top Panel 1200 Square Glass Cabinet 18757 Top Panel 1500 Square Glass Cabinet 18985 Top Panel...

Страница 45: ...t Feet These drawings show cabinets fitted with the standard 150mm tapered feet Alternative 100mm cylindrical feet are available for special orders These will reduce the overall cabinet height and als...

Страница 46: ...Part No 26107 Rev J August 2018 46 Inline 5000 Series Cabinets Sliding Door Cabinets Types IN 5C08 12 15...

Страница 47: ...IN 5C08 12 15 18 24 47 Future Products Group Tilt Door Cabinets Type IN 5C18...

Страница 48: ...Part No 26107 Rev J August 2018 48 Inline 5000 Series Cabinets Sliding Door Cabinets Type IN 5C18...

Страница 49: ...12 15 18 Because the front face of Square glass cabinets is vertical deeper shelves can be fitted in the upper two levels This increases the display area by about 10 A 2400mm version of the square for...

Страница 50: ...Part No 26107 Rev J August 2018 50 Inline 5000 Series Cabinets Cabinet Type IN 5C24 Although shown with front sliding doors this cabinet is also available with a front tilt door...

Страница 51: ...IN 5C08 12 15 18 24 51 Future Products Group Square Glass Cabinet Type IN 5C24 Although shown with front sliding doors this cabinet is also available with a front tilt door...

Страница 52: ...change specifications and design without notice AUSTRALIA E ausales fpgworld com T 1800 813 745 CHINA ASIA E asales fpgworld com T 86 21 3351 3390 EUROPE E eusales fpgworld com T 31 6 5253 4769 INDIA...

Отзывы: