English

5

Standby 

When pressing the   button for 3 seconds, the unit will enter the standby mode and display 

 (unless already 

in standby and then this will energise the controller to show the current unit temperature).

This ‘ 

 ’ indication will be displayed while the unit is not operating but the mains power is applied to the unit. 

This mode may be used for interval cleaning regimes and short periods when the unit is not required. For extend

-

ed periods of inactivity the mains supply should be isolated.

Access the menu and information

 

>

Press and immediately release the 

i

 button.

 

>

Using the 

 and or 

 buttons select the data you wish to display

 

>

Press the 

i

 button to display the current value.

 

>

To exit press the   button or wait 10 seconds.

To reset the THI and TLO:

 

>

Use the 

 and or 

 buttons to select the data to be reset

 

>

Display the value with the 

i

 button

 

>

While keeping the 

i

 button pressed, press the   button to reset.

Set Point and Display Modification 

 

>

Press button 

i

 and hold for half a second.  

 

>

By keeping button 

i

 pressed, use 

 and or 

 buttons to set the desired value (adjustment is with

-

in the minimum SPL and the maximum SPH limit)

 

>

When button 

i

 is released, the new value is stored. 

Keypad Security Settings

The keypad lock avoids undesired, potentially dangerous operations, which might be attempted when the control

-

ler is operating in a public place. 

Press briefly ‘

’ then use either ‘

‘ or ‘

‘ to select ‘

’. While holding ‘

’ use either 

‘ or ‘

‘to change from a ‘

’ to ‘

’. Leave for 10 seconds or briefly press ‘

’ to resume.

Defrost

Automatic Defrost 

Defrost starts automatically as soon as the time set with parameter DFT has elapsed.

 

>

Time Defrost

 With DFM = TIM defrost takes place at regular intervals when the timer reaches the value DFT. 

For example, with DFM = TIM and DFT = 06, a defrost will take place every 6 hours.

 

>

Defrost time count backup

 At power restoration, if DFB = YES, the defrost timer resumes the time count 

from where it was prior to the power interruption. If DFB=NO, the time count re-starts from 0. In stand-by the             

accumulated time count is frozen. 

Defrost Type

 – When defrost has started, compressor and defrost outputs are controlled according to the param

-

eter DTY. 

If FID = YES, the evaporator fans are active during defrost.

Resuming Thermostatic Cycle 

When defrost is complete, if DRN is greater than 0, all outputs will remain off for the DRN minutes.

Manual Defrost 

 

To initiate a manual defrost press and hold the defrost button 

 for 2 seconds.

Содержание SLIMLINE FSL400

Страница 1: ...Elizabeth II Suppliers of Commercial Refrigeration Foster Refrigerator King s Lynn Foster Refrigerator Oldmedow Road King s Lynn Norfolk PE30 4JU United Kingdom A division of ITW Ltd Email support fos...

Страница 2: ...information on every variation of this unit neither does it cover the installation or every possible operating or maintenance instruction for the units Health Safety Warnings Information Make sure th...

Страница 3: ...ely from other wastes as they are hazardous to the environ ment refrigerants polyurethane foam and oils 4 When arranging for disposal of waste ensure a waste transfer note or consignment note is compl...

Страница 4: ...L this denotes High or Low temperature units as with a G meaning it has glass doors and M denoting meat Both glass and solid doors are fitted with pivot hinges and also both have magnetic door gaskets...

Страница 5: ...e recorded Displayed only if enabled see configuration parameters Displayed only if ACC 0 User Functions Start Sequence For normal operation Press and hold the button for 3 seconds then release The cu...

Страница 6: ...ximum SPH limit When button i is released the new value is stored Keypad Security Settings The keypad lock avoids undesired potentially dangerous operations which might be attempted when the control l...

Страница 7: ...temperature and defrost SP HYS and DFT The controller will remain operating to the values of these settings unless through monitoring of the air temperature evapora tor temperature and door switch wh...

Страница 8: ...together for 5 seconds The first parameter will show on the display Using the and or buttons select the required parameter Press the i button to display its current value While keeping pressed use the...

Страница 9: ...s only in condition of frost accumulation DFT 0 99 hours Time interval between defrosts 6 DFB Defrost timer clock YES YES Following mains interruption timer resumes count NO Following mains interrupti...

Страница 10: ...pressor is on fans are on When compressor is off fans in accordance to parameters FT1 FT2 and FT3 FDT 120 0o Te Ta difference for fans to turn off after compressor stopped 1 Only if T2 EPO and FCM TMP...

Страница 11: ...ndenser cleaning period 0 With ACC 0 condenser cleaning is disabled IISM Switchover method to second parameter set HDD NON Second parameter set is excluded MAN Second parameter set is activated deacti...

Страница 12: ...itch function operates in series with DS LSM Light control mode NON NON Light output is excluded MAN Light output operation is activated deactivated by button M With OA1 LGT DOR Light output is switch...

Страница 13: ...217 CT1 0 min 30 min Thermostat run time with faulty T1 probe 6 6 6 6 6 218 CT2 0 min 30 min Thermostat off time with faulty T1 probe 4 4 4 4 4 219 CSD 0 min 30 min Compressor stop delay after door h...

Страница 14: ...Alarm probe T1 T1 T1 T1 T1 242 ATD 0 min 120 min Delay before alarm temperature warning 90 90 90 90 90 243 ADO 0 min 30 min Delay before door open alarm warning 8 8 8 8 8 244 AHM NON STP ALR Operatio...

Страница 15: ...0 0 0 250 T2 NON EVP CND T2 probe function NON EVP NON EVP EVP 251 OS2 12 5 C 12 50c T2 probe temperature offset 0 0 0 0 0 252 TLD 1 min 30 min Delay for min TLO and max THI temperature logging 10 10...

Страница 16: ...English Slimline High Temp Integeral and Remote Models Wiring Diagram 15...

Страница 17: ...English Slimline Low Meat Temp Integeral and Remote Models Wiring Diagram 16...

Страница 18: ...English Air and Evaporator Probe Details Diagram Probe Air 2 5M SN4K15H1 00 556284 Probe Evap 2 5M SN4K15H2 00 55627 17...

Страница 19: ...YES YES YES YES DLI 20 20 20 20 20 20 20 20 20 DTO 20 20 20 20 20 20 20 20 20 DTY OFF OFF OFF GAS GAS OFF OFF GAS GAS DPD 0 0 0 0 0 0 0 0 0 DRN 2 2 2 2 2 2 2 2 2 DDM DEF DEF DEF DEF DEF DEF DEF DEF D...

Страница 20: ...4 4 4 4 4 IIFC NON NON NON NON NON NON NON NON NON HDS 3 3 3 3 3 3 3 3 3 IIDF 6 6 6 6 6 6 6 6 6 SB YES YES YES YES YES YES YES YES YES DS YES YES NO YES YES YES NO YES YES DI2 NON NON NON NON NON DS2...

Страница 21: ...English Slimline High Temp Integeral Glass Door Models Wiring Diagram Post February 2019 20...

Страница 22: ...English Slimline Low Meat Temp Integeral Wiring Diagram Post February 2019 Models 21...

Страница 23: ...English Air and Evaporator Probe Details Diagram Probe Air 2 5M SN4K15H1 00 556284 Probe Evap 2 5M SN4K15H2 00 55627 22...

Страница 24: ...itches only displayed if applicable to model and enabled through parameters Compressor will not start No voltage in socket Use voltmeter to check Electrical conductor or wires may be cut Use ohmmeter...

Страница 25: ...purge and recharge Iced up evaporator coil Check temperature control refrigerant charge and defrost mechanism Remove all ice manually and start over Restriction in system Locate exact point of restric...

Страница 26: ...blade Compressor has an internal noise If the noise persists after all other measures have been taken it may be originating from the compressor Loose part s Locate and tighten loose part s Extreme con...

Страница 27: ...ith soap and water Check condition of gasket replace if necessary Dirty condenser coil Clean condenser coil Evaporator coil iced over Unplug unit and allow coil to defrost Make sure thermostat is not...

Страница 28: ...K Head Office Foster Refrigerator Oldmedow Road Kings Lynn Norfolk PE30 4JU a Division of ITW UK Ltd Tel 44 0 843 216 8833 Fax 44 0 843 216 4707 Email support foster uk com Website www fosterrefrigera...

Отзывы: