SSC3100 Operation & Calibration Manual
Troubleshooting and Error Conditions
16
System Status
Condition
Recommended Action
Fused Power Missing
The system is not detecting power on
the fused circuit which is used to run the
valve outputs.
Verify that the fuse is not
blown, if it is blown replace
with a 10 Amp
Stuck Remote Standby
The remote standby input was active
during startup.
Verify that the remote standby
input is not grounded.
Stuck Remote Blast
The remote blast input was active
during startup.
Verify that the remote blast
input is not grounded.
Improper Shutdown
The system detected an improper
shutdown caused by losing constant
power before the system completed its
shutdown process.
Verify that the dashkey wire is
properly connected to a
dashkey signal.
Verify that the constant power
wire is properly connected to a
voltage source that receives
constant power.
Verify that the voltage input for
the constant power connection
is stable and above 8 volts.
Corrupt calibration settings
The system detected an issue with the
stored calibration data. The calibration
data has been reset to the factory
defaults.
When calibrating the system
make sure to exit the
calibration menu before turning
off the spreader control.