SSC3100 Operation & Calibration Manual
Description of Calibration Values
13
Speedometer Configuration
The speedometer configuration item is used to enable the ground speed
interrupt. When the ground speed interrupt is enabled, the system will stop
spreading material when the vehicle is not moving. If ground speed
interrupt is to be enabled the proper speedometer signal type and input
pulse range needs to be selected. The system supports an electronic or
mechanical signal with a low pulse rate or high pulse rate. If the vehicles
pulses per mile is higher than 20,000 (pulses per kilometer is higher than
12,500) select the high pulse rate otherwise select the low pulse rate. The
setting is indicated by having the liquid dial illuminated at 7. The value is
indicated by the numbers around the spreader dial and the table below.
The default value is Disabled.
* When this calibration item is active, spreader dial position 10 will illuminate
in addition to the setting value when the system is detecting a speedometer
signal.
Spreader Dial
State
0
Disabled
1
Electronic
– Low Pulse Rate
2
Electronic
– High Pulse Rate
3
Mechanical
– Low Pulse Rate
4
Mechanical
– High Pulse Rate
*10
Signal Present
Liquid Mode
The liquid mode item determines how the liquid output on the controller will
operate. The setting is indicated by having the liquid dial illuminated at 8.
The value is indicated by the number around the spreader dial and the table
below. The default value is Disabled.
Spreader
Dial
Description
0
Disabled
The liquid output will not run regardless of the
system state
1
Gravity Prewet
The liquid output will function as an on/off output
used to operate a ball valve. The output will
only be active when the granular output is
active.
2
Prewet (No Liquid Blast)
The liquid output will only operate when the
granular output is active and the output rate will
not change when the blast feature is active.
3
Prewet (Liquid Output Blasts)
The liquid output will only operate when the
granular output is active and the output rate will
increase to the max setting when blast is active.
4
Direct (No Liquid Blast)