ventinG instaLLation
Continued
Figure 27 - Vertical Venting
Configuration With No Horizontal Run
Vertical Venting
V = 40' max.
Note: Install restrictor
into 4" collar of burner
system as shown.
HIGH ALTITUDE INSTALLATION
Your cast iron stove and direct-vent burner
system has been tested and approved for
operation at altitudes from 0-2000 ft.
When installing this stove at an elevation
above 2000 feet, you may need to decrease
the input rating by changing the existing
burner orifice to a smaller size. Reduce input
4% for each 1000 feet above sea level. Check
with your local gas company for proper orifice
size identification and proper orifice for your
location.
For assistance with any high altitude in-
stallation contact FMI PRODUCTS, LLC at
1-866-328-4537.