background image

www.fmiproducts.com

112127-01C

2

saFety

 WARNING: Improper instal

-

lation,  adjustment,  alteration, 

service  or  maintenance  can 

cause injury or property damage. 

Refer to this manual for correct 

installation  and  operational 

procedures.  For  assistance  or 

additional  information  consult 

a  qualified  installer,  service 

agency or the gas supplier.

This appliance may be installed 

in an aftermarket,* permanently 

located, manufactured (mobile) 

home, where not prohibited by 

local codes.

This  appliance  is  only  for  use 

with the type of gas indicated on 

the rating plate. This appliance 

is  not  convertible  for  use  with 

other gases, unless a certified 

kit is used.

* Aftermarket: Completion of sale, not for pur-
pose of resale, from the manufacturer

State of Massachusetts: The instal-

lation must be made by a licensed 

plumber or gas fitter in the Com

-

monwealth of Massachusetts.

 WARNING: This product con

-

tains and/or generates chemicals 

known to the State of California 

to cause cancer or birth defects 

or other reproductive harm.

IMPORTANT: Read this owner’s 

manual carefully and completely 

before trying to assemble, oper

-

ate  or  service  this  stove  with 

burner system. Improper use of 

this  stove  with  burner  system 

can  cause  serious  injury  or 

death  from  burns,  fire,  explo

-

sion, electrical shock and carbon 

monoxide poisoning.

 DANGER: Carbon monoxide 

poisoning may lead to death!

This appliance complies with the current ANSI 
Z21.88 as a Vented Gas Fireplace Heater and 
is listed and tested by the PFS Corporation 
to the above test standards. This stove with 
burner system is a vented product. This stove 
with burner system will not produce any gas 
leakage into your home if properly installed. 
This unit must be properly seated and sealed. 
If this unit is not properly installed by a quali-

fied service person with glass door properly 

seated and sealed, gas leakage can occur.

Carbon  Monoxide  Poisoning:

  Early  signs 

of carbon monoxide poisoning resemble the 

flu,  with  headaches,  dizziness  or  nausea. 

If you have these  signs,  the burner system 
may not be working properly. 

Get fresh air 

at once!

 Have burner system serviced. Some 

people are more affected by carbon monoxide 
than others. These include pregnant women, 
people with heart or lung disease or anemia, 

those under the influence of alcohol and those 

at high altitudes.

taBLe oF Contents

Safety .................................................................. 2
Local Codes......................................................... 4

Product Identification

 ........................................... 4

Product Features ................................................. 5
PreInstallation Preparation .................................. 5
Unpacking............................................................ 6
Burner System Assembly .................................... 6
General Venting ................................................... 7
Venting Installation .............................................. 9
Installation ......................................................... 19
Operation ........................................................... 26

Inspecting Burners............................................. 28
Cleaning and Maintenance ................................ 28
Troubleshooting ................................................. 30

Specifications

 .................................................... 34

Wiring Diagram .................................................. 34
Service Hints ..................................................... 34
Technical Service............................................... 34
Replacement Parts ............................................ 35
Accessories ....................................................... 35
Parts .................................................................. 36
Warranty ..............................................Back Cover

Содержание Natural Gas Burner System SDVBND

Страница 1: ...s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the...

Страница 2: ...arbon monoxide poisoning DANGER Carbonmonoxide poisoning may lead to death This appliance complies with the currentANSI Z21 88 as a Vented Gas Fireplace Heater and is listed and tested by the PFS Corp...

Страница 3: ...This stove reaches high tem peratures Keep children and adults away from hot surface to avoid burns or clothingignition Stove will remain hot for a time after shutdown Allow surface to cool before to...

Страница 4: ...t Opening Glowing Embers Grate Assembly Rear Cover Cast Iron Stove Body Lava Rock Cast Iron Stove Body Piezo Ignitor Control Valve Log Set Stove Front Immediately call a qualified service person to ar...

Страница 5: ...WARNING A qualified in staller or service person must installstoveandburnersystem Follow all local codes CAUTION Thisstovecreates warm air currents These cur rentsmoveheattowallsurfaces next to stove...

Страница 6: ...reattach back panel later 5 Remove bubble wrapped log set rod and screen from stove Remove all protective packaging applied for shipment 6 Check heater for any shipping damage If heater is damaged cal...

Страница 7: ...ce between vent pipes and combustible materials is 1 2 5 cm except where stated otherwise Do not recess venting terminations into a wall or siding Install horizontal venting with a 1 4 rise for every...

Страница 8: ...minimum L clearance above paved side walk or a paved driveway located on public property 84 213 3 cm minimum M clearance under veranda porch deck 12 30 5 cm minimum N clearance above a roof shall ext...

Страница 9: ...tem Installation of any component part not manufactured or approved by FMI PROD UCTS LLC Installation other than as instructed by these instructions WARNING This gas stove with burner system and vent...

Страница 10: ...ide of a building A chase is not required for such venting NOTICE Treatment of firestops and construction of the chase may vary from building type to building type These instruc tions are not substitu...

Страница 11: ...re minimum clear ances Mark the wall for a 10 25 4 cm square hole for noncombustible material such as masonry block or concrete a 7 1 2 19 1 cm diameter hole is accept able See Figure 13 The center of...

Страница 12: ...yl Siding Away to Fit Standoff Wood Screw Bolt Standoff Vent Cap Apply Mastic to All Four Sides Vent Cap Horizontal Termination Interior Wall Surface Interior Wall Firestop Combustible Exterior Wall O...

Страница 13: ...ax 63 min 49 max 86 min 96 max 91 min 20 max Figure 18 Horizontal Termination Configuration for Venting Using Three 90 Elbows Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 6 min 4...

Страница 14: ...reach from the burner system flue up through the firestop Be sure all pipe and elbow connections are fully twist locked see Figure 12 page 11 3 Cut a hole in the roof using the locat ing hole as a cen...

Страница 15: ...nd into roof sheathing 4 Using tin snips cut support box from top corners down to roofline and fold resulting flaps over roof sheathing see Figure 23 Apply a bead of nonhardening mastic around top edg...

Страница 16: ...6 min 4 max 7 min 6 max 8 min 8 max 20 max 8 max Figure 25 Vertical Venting Configuration Using Three 90 Elbows with Two Horizontal Runs Note Install restrictor into 4 collar of burner system as show...

Страница 17: ...ystem has been tested and approved for operation at altitudes from 0 2000 ft When installing this stove at an elevation above 2000 feet you may need to decrease the input rating by changing the existi...

Страница 18: ...rictor 7 12 Adjustable Coaxial Pipe 6 Pipe Adaptor 12 Coaxial Pipe 4 Coaxial Pipe Firestop Decorative Trim Plate Roof Flashing Storm Collar and 18 Screws Number Description P 47 12 K 12 Black Coaxial...

Страница 19: ...tor notsupplied Installtheexternal regulator between the burner system and propane LP supply Figure 28 External Regulator with Vent Pointing Down Propane LP Only Propane LP Supply Tank External Regula...

Страница 20: ...off Valve with 1 8 NPT Tap 3 Minimum LP From External Regulator 11 W C to 14 W C Pressure Approved Flexible Gas Line Cap Pipe Tee Nipple Joint Sediment Trap Drip Leg Natural From Gas Meter 5 W C to 10...

Страница 21: ...meter to equipment shutoff valve see Figure 32 for propane LP or Figure 33 for natural gas Apply noncor rosive leak test solution to all gas joints Bubbles forming show a leak Correct all leaks at on...

Страница 22: ...e is attached to the underside of the burner system assembly 2 Disconnect from the valve the wires run ning from the ON OFF switch 3 Connect one terminal of the wire for the wall thermostat to the THT...

Страница 23: ...front panel on stove body CAUTION Do not operate this burner system with a bro ken glass door panel or without the glass door panel securely in place For replacement part information see Replacement P...

Страница 24: ...hes in the bottom of log fit over the grate see Figure 39 3 Rest log 2 large front log on the pins on the front part of grate see Figure 40 4 Place log 3 crossover log onto rear and front logs Make su...

Страница 25: ...on of front burner and along space between burner and grate prongs see Figure 43 This will create the glowing ember appearance as the flame touches the ember material Do not block air slots by using t...

Страница 26: ...ve Gas Control Knob Piezo Ignitor For your safety read before lighting WARNING If you do not fol low these instructions exactly a fire or explosion may result causing property damage per sonal injury...

Страница 27: ...minute Turn control knob to ON position Adjust flame adjustment knob anywhere be tween HI and LO Slide the selector switch to the REMOTE position see Figure 45 Note The burner may light if hand held r...

Страница 28: ...ling Call a qualified service person to readjust the pilot if necessary The height of the thermopile must be 3 8 to 1 2 above the pilot flame as shown in Figure 46 The flame from the pilot burner must...

Страница 29: ...lacing Glass Door page 23 for instructions for replacing glass door WARNING Do not operate burnersystemwiththeglassdoor removed cracked or broken CLEANING AND MAINTENANCE Continued Pilot and burners R...

Страница 30: ...ing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor Nut is located behind the mounting bracket 4 Replace ignitor cable 5 Replace piezo ignitor 6 Replace pilot assembly 7 Replace pilot assem...

Страница 31: ...pile leads discon nected or improperly con nected 4 Thermopile is defective 1 Clean burner see Cleaning and Maintenance page 28 or replace burner orifice 2 Contact local propane LP or natural gas comp...

Страница 32: ...ked with any type of material 3 Follow venting configuration instructions on pages 12 thru 16 Burner system produces a clicking ticking noise just after burners are lit or shut off 1 Metalexpandingwhi...

Страница 33: ...as leak See Warning statement page 37 1 Locate and correct all leaks see Checking Gas Connec tions page 20 Dark residue on logs or inside of burner system 1 Improper log placement 2 Air holes at burne...

Страница 34: ...5 W C Minimum Inlet Supply Pressure 5 W C Dimensions HxWxD 27 x 21 1 2 x 18 68 6 x 54 6 x 45 7 cm SDVBPD Rating 20 000 28 000 Btu Hr Gas Type Propane LP Gas Manifold Pressure 10 W C Minimum Inlet Sup...

Страница 35: ...propane LP gas to natural gas PcBv NS Conversion Kit For natural gas models Allows burner system to be converted from natural gas to propane LP gas Purchase these accessories from your local dealer I...

Страница 36: ...www fmiproducts com 112127 01C 36 Parts Models SDVBND and SDVBPD TPTH TP TH 4 19 20 21 23 26 1 26 4 26 2 26 3 6 24 4 25 4 1 28 28 4 7 8 9 18 10 11 13 12 15 16 17 4 2 3 22 27 14 4 5 22 23...

Страница 37: ...iezo 1 18 107014 01 Center Cast Stove Top Grate 1 19 14597 14598 Burner Natural Burner Propane LP 1 1 20 104506 16 104506 17 Orifice Natural Orifice Propane LP 1 1 21 14499 Brass Elbow 1 22 14264 Bras...

Страница 38: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Страница 39: ...______________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ____...

Страница 40: ...s product and or FMI PRODUCTS LLC who will provide original factory replacement parts Failure to use original factory replacement parts voids this warranty Travel handling transportation diagnostic ma...

Отзывы: