OWNER’S MANUAL

Pressure Testing Gas Supply
Piping System

Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)

1.

Disconnect appliance with its appliance
main gas valve (control valve) and
equipment shutoff valve from gas
supply piping system. Pressures in
excess of 1/2 psig (3.5 kPa) will damage
fireplace gas regulator.

2.

Cap off open end of gas pipe where
equipment shutoff valve was con-
nected.

3.

Pressurize supply piping system by ei-
ther opening propane/LP supply tank
valve for propane/LP gas fireplace or
opening main gas valve located on or near
gas meter for natural gas fireplace, or
using compressed air.

4.

Check all joints of gas supply piping
system. Apply commercial leak test so-
lution to all gas joints. Bubbles forming
show a leak. Correct all leaks at once.

5.

Reconnect fireplace and equipment
shutoff valve to gas supply. Check re-
connected fittings for leaks.

CHECKING GAS
CONNECTIONS

 WARNING: Test all gas pip-

ing and connections for leaks
after installing or servicing. Cor-
rect all leaks at once.

  WARNING: Never use an open

flame to check for a leak. Apply
commercial leak test solution to
all gas joints. Bubbles forming
show a leak. Correct all leaks at
once.

Installation Items Needed

• 5/16" hex socket wrench or nut-driver

• sealant (resistant to propane/LP gas, not

provided)

1.

Open lower louver door panel by gen-
tly pulling forward.

2.    Route flexible gas supply line through

one of the access holes on side of fire-
place.

3.

Attach flexible gas line from gas sup-
ply  (see Figure 35) to fireplace gas
valve.

4.

Check all gas connections for leaks. See
Checking Gas Connections, pages 19
and 20.

CONNECTING FIREPLACE
TO GAS SUPPLY

FIREPLACE
INSTALLATION

Continued

To Gas Supply
(Natural)

To External Regulator
(Propane/LP)

Flexible Gas Line from
Equipment Shutoff Valve
Provided by Installer

Figure 35 - Attaching Flexible Gas Line to Control Valve

Continued

Equipment Shutoff
Valve

Control Valve

Содержание DVF34

Страница 1: ...assis tanceoradditionalinformationcon sult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by s...

Страница 2: ...cated on fire place nameplate 14 This appliance when installed must be electrically grounded in accordance with local codes or in the absence of local codes with the National Electri cal Code ANS NFPA...

Страница 3: ...piezo ignitor This sys tem requires no matches batteries or other sources to light fireplace Figure 1 FMI Direct Vent Fireplace DVF Series Glass Door Assembly Blower Adjustment Optional Installation...

Страница 4: ...for drywall facing Must maintain a minimum 1 clearance to combustibles 34 3 4 34 1 4 20 Vertical Termination 19 Horizontal Termination CLEARANCES Minimum clearances to combustibles for the fireplace...

Страница 5: ...mbustible material may be flush with the top front of fireplace with a maxi mum thickness of 3 4 Do not recess venting terminals into a wall or siding If exterior wall is vinyl you must use a vinyl si...

Страница 6: ...to a mechanical air supply inlet 72 inches 1829mm minimum L clearance above paved side walk or a paved driveway located on public property 84 inches 2133mm minimum M clearance under veranda porch deck...

Страница 7: ...ermination It is important to select the proper length of vent pipe for the type of termination you choose It is also important to note the wall thickness For Horizontal Termination Select the amount...

Страница 8: ...pipes and fittings have spe cial twist lock connections Assemble the desired combination of pipe and el bows to the appliance adaptor with pipe seams oriented towards the wall or floor Twist lock Pro...

Страница 9: ...or 10 hole on the exterior wall with the arrow on the vent cap pointing up Insure proper clearance of 1 to combustibles is maintained At tach the vent cap with four wood screws supplied see Figure 13...

Страница 10: ...cal pipe 90 elbow 67 min 60 max 79 min 84 max 96 min 20 max Note This configuration for use with corner installation Horizontal Termination Configurations Figures 16 through 19 show different con figu...

Страница 11: ...ax 20 max Venting with Two 90 Elbows Vertical V Horizontal H1 Horizontal H2 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max 20 max 20 max Figure 18 Horizontal Termination Configuration for Rigid Ve...

Страница 12: ...bers Note Pay special attention to these installation instruc tions for required clearances air space to combustibles when passing through ceilings walls roofs enclosures attic rafters etc Do not pack...

Страница 13: ...support box in place through the inside walls and into the roof sheathing 4 Using tin snips cut the supportbox from the top corners down to the roofline and fold the resulting flaps over the roof shea...

Страница 14: ...TING INSTALLATION Continued Venting with Two 90 Elbows Vertical V1 Horizontal H 5 min 6 max 6 min 12 max 7 min 18 max 8 min 20 max Note Vertical V1 Vertical V2 20 max Figure 26 Vertical Rigid Venting...

Страница 15: ...NENTS FMI Rigid Venting Number Description FD30 30 Starter Adapter 65 8 to7 6 per box FD60 60 Starter Adaptor 65 8 to7 6 per box F7030 7 to 12 Adjustable pipe length 6 per box D1031 7 to 12 Adjustable...

Страница 16: ...n system s circulating blower while using fireplace This will help circulate the heat through out the house In the event of a power outage you can use this fireplace as a heat source WARNING A qualifi...

Страница 17: ...ee Figure 32 Route power cord through both plastic bushing s and plug the power cord into a properly grounded 3 prong wall receptacle near the firebox b If your fireplace system installation is recess...

Страница 18: ...able alternative to test gauge connection Pur chase the CSA design certified equipment shutoff valve from your retailer WARNING A qualified ser vice person must connect fire place to gas supply Follow...

Страница 19: ...ected fittings for leaks CHECKING GAS CONNECTIONS WARNING Test all gas pip ing and connections for leaks after installing or servicing Cor rect all leaks at once WARNING Neveruseanopen flame to check...

Страница 20: ...valve see Fig ure 36 2 Open propane LP supply tank valve for propane LP fireplace or main gas valve located on or near gas meter for natu ral gas fireplace 3 Make sure control knob of fireplace is in...

Страница 21: ...MS2 includes 25 of wire for installation Your fireplace includes 15 of wire for accessoryinstallation Choosethe length that best fits your needs when installing this accessory 1 Connect one terminal o...

Страница 22: ...e method described in step 3 6 Slide the right retainer bracket against the right side brick panel Loosely se cure the bracket screw This secures the right side brick panel 7 Install rear brick panel...

Страница 23: ...the front right part of the grate making sure the notches fit over the prong of the grate see Figure 49 6 Place lava rock along sides and front of inside of firebox bottom It is not necessary to use a...

Страница 24: ...urn gas control knob counterclock wise to PILOT 9 Push in gas control knob all the way and hold Immediately light the pi lot by repeatedly depressing the piezo spark ignitor until a flame appears Cont...

Страница 25: ...ce off see To Turn Off Gas to Appliance page 24 see Troubleshooting pages 27 through 29 Figure 53 Pilot Assembly Thermocouple Thermopile 3 8 to 1 2 1 8 Pilot Burner Piezo Ignitor Figure 52 Setting the...

Страница 26: ...urn off fireplace and let cool before cleaning CAUTION Youmustkeepcon trol areas burners and circulat ing air passageways of fireplace clean Inspect these areas of fire place before each use Have fire...

Страница 27: ...valve damaged REMEDY 1 Reconnect ignitor cable 2 Free ignitor cable if pinched by any metal or tubing Keep ignitor cable dry 3 Tighten nut holding piezo ignitor Nut is located behind the mounting bra...

Страница 28: ...r until air is removed from line Have gas line checked by local pro pane LP or natural gas company 3 Clean burner see Cleaning and Mainte nance page 26 or replace burner orifice 1 Adjust the log set s...

Страница 29: ...2 Air holes at burner inlet blocked 3 Burner flame holes blocked OBSERVED PROBLEM Fireplace produces unwanted odors Fireplace shuts off in use Gas odor even when control knob is in OFF position Gas od...

Страница 30: ...connection when servicing controls Wiring errors can cause improper and dangerous operation Verify proper operation after servicing Note Use only original replacement parts Thiswillprotectyourwarranty...

Страница 31: ...upply Pressure 4 5 w c 11 0 w c Dimension Inches mm HxWxD Fireplace Actual size of firebox Measurements do not 32 3 16 x 34 3 8 x 18 1 2 32 3 16 x 34 3 8 x 18 1 2 include nailing flanges or 817 x 873...

Страница 32: ...P DVF34 DVF34P 47 1 2 3 4 6 6 35 5 5 5 11 Included in Hardware Pack 7 7 8 10 9 12 13 14 15 16 17 18 19 20 32 21 22 23 24 25 26 27 28 28 29 30 31 1 31 4 31 2 31 3 33 32 32 34 46 36 37 39 38 42 40 41 6...

Страница 33: ...Pilot Propane LP 19 104498 01 Thermocouple 1 20 104499 01 Thermopile 1 21 104500 01 Piezo Ignitor 1 22 104501 01 Ignitor Bracket 1 23 104502 01 Ignitor Screw 1 24 104503 01 Ignitor Wire 1 25 104504 0...

Страница 34: ...before installing on fireplace BRICK LINER D8037A Not Shown This brick liner adds a touch of style to your direct ventfireplaceandcomeswitheasyto follow instructions for installation ON OFF WALL MOUN...

Страница 35: ...___________________ _______________________________________________________________________________________________ ____________________________________________________________________________________...

Страница 36: ...pairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHEPRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRES...

Отзывы: